Electrical control wiring
Indoor and outdoor unit communication wires specifi cation and
attention
Indoor and outdoor unit communication wires are provided by Trane.
•
STP specifi cation is 0.5
ċ
1.25mm
2
and the lay is less than 10cm.
L
Lay
ǘ
10cm
STP legend
A
B
C
D
A: Outer sheath B: Shield layer C: Insulator D: Conductor
Do not connect the power supply wire with the communication wire terminal.
•
You have to connect control (communication) wire and the total length should be less than
•
1,000m.
Shield layer of the communication wire and the main unit must be grounded.
•
Install the communication wire before power on. Do not plug in and out with electricity,
•
avoiding communication chip damage.
Control signal circuit must use STP, avoiding strong electric signal interference. (Choose
•
network wire with tight shield layer and small lay.)
Control signal is divided into A and B, two polarities. Different polarities can
•
not be connected as followings (A can not connect with B):
A1
B1
Communication port
Control main board
Communication port
Control main board
A1
B1
It is wrong to connect A with B.
When power supply wire and communication wire are parallel wiring, please cover
•
conduits and keep a certain distance between them.
The communication wire passes through the side incoming hole and connects controller
•
CN2 terminals as followings:
RS485 wire sequence
A
B
Shield layer
CN2 terminal
A
B
G