Chiller Troubleshooting
72
ARTC-SVX002A-EN
FF61
ID run
Motor ID run was not completed
successfully.
Check the nominal motor values in
parameter group 99 Motor data.
Check that no external control system is
connected to the drive.
Cycle the power to the drive (and its
control unit, if powered separately).
Check that no operation limits prevent
the completion of the ID run. Restore
parameters to default settings and try
again.
Check that the motor shaft is not locked.
FF81
FB A force trip
A fault trip command has been received
through fieldbus adapter A.
Check the fault information provided by
the PLC.
FF8E
EFB force trip
A fault trip command has been received
through the embedded fieldbus
interface.
Check the fault information provided by
the PLC.
Code (hex)
Fault / Aux. code
Cause
What to do