LED Status Codes

LED Activity

Description

Color

Lockout Period

(a)

Comments

OFF (No LED

Activity)

No 24 VAC Power to
Control

N/A

Check incoming voltage ~120VAC

Red, Amber,

Green

Power-up verification
of LED

N/A

Displayed at power up or after any successful control
reset, a one second display of each color in sequence.

Steady ON

Control Fault Detected
Hard Lock-Out

RED

Until fault is removed

Control faults include relay failures, memory failures,
or other hardware failures detected during power-up
self-test or during other continuous operating checks.

Rapid Flash

Reversed Line Voltage
Polarity

RED

Until fault is removed

Call For Heat Not required.

No “W” nor “Y” or “G”

input calls for heating, cooling, or continuous fan
operation will be acknowledged until the fault is
corrected.

1 Flash

System Lockout
Retries Exceeded

RED

1 Hour Fixed

Retries

are defined as failed ignition attempts, i.e. no

flame sense established during the trial for ignition
period and maintained through the flame stabilization
period.

Recycles

are defined as loss of flame following

completion of a successful ignition while in the run
state, and there is no limit to the number of recycles.
If the blower is already on when flame loss occurs,
then it will remain on during the recycle light-off
attempt.

2 Flashes

Pressure Sensor Null
Error: Inconsistent
reading with inducer
OFF, sensor may be
electrically unplugged

RED

30 second lockout during
Call For Heat

Control waits 5 seconds after call for heat before
displaying fault. Fault is displayed until fault condition
corrects and lockout expires or call for heat is
removed.

3 Flashes

Pressure Sensor Span
Error: Inconsistent
reading with inducer
ON, or inducer fails to
reach target pressure.

RED

5 minute lockout during
Call For Heat

Span test maximum duration is 90 seconds. Once the
span test fails, the fault is displayed until the lockout
expires or Call For Heat is removed. Could be blocked
vent, poor air hose connection, or an open circuit in
the inducer harness.

4 Flashes

High Limit Switch Open

RED

Until limit closes or Call For
Heat is removed or 5
minutes during a Call For
Heat or 1 hour lockout
after 3 faults in a single
Call For Heat

When an open limit is detected during a Call For Heat,
the control energizes the blower on the heating
speed, sets the inducer to maximum, and displays the
fault. Lockout is until the limit closes and either a
minimum of 5 minutes if during a Call For Heat, or
upon removal of the Call For Heat. Three open limit
events in a single Call For Heat results in a 1 hour
lockout. Outside of a Call For Heat, an open high limit
switch is ignored.

5 Flashes

Flame Present with Gas
Valve OFF

RED

5 minutes during Call For
Heat

When detected, the control energizes the inducer at
the "Run" setting, energize the blower on Heat speed,
and displays fault - No Call For Heat required. The
control will perform a post-purge when the fault
condition is corrected and then it will resume normal
operation after any lockout has expired.

6 Flashes

Auxiliary Limit Open

RED

Until limit closes or Call For
Heat is removed or 5
minutes during Call For
Heat

When detected during a Call For Heat, the control
energizes the blower on the heating speed, sets the
inducer to maximum, and displays the fault. Lockout
is until the limit closes and either a minimum of 5
minutes if during a Call For Heat, or upon removal of
the Call For Heat. Outside of a Call For Heat, an open
auxiliary limit switch is ignored.

7 Flashes

Gas Valve Circuit
Shorted

RED

1 hour lockout

Voltage sensed at the gas valve terminal with the
safety relay in the de-energized state. The inducer is
set to maximum speed.

Steady ON

OEM Factory Test Mode

AMBER

N/A

Cycle power to the furnace.

1 Flash

Low Flame Sense

AMBER

N/A

Flame Sense Current is weak, less than 3 µAmp

Содержание L8X1B060U3XSAA

Страница 1: ...utions in the literature and on the tags stickers and labels that are attached to the equipment May 2020 1 18 8 C CE E0 07 7D D1 1 1 1C C E EN N Upflow Horizontal Left Right Gas Fired Single Stage Ind...

Страница 2: ...EC CT TR RI IC CA AL L S SH HO OC CK K F FI IR RE E O OR R E EX XP PL LO OS SI IO ON N H HA AZ ZA AR RD D F Fa ai il lu ur re e t to o f fo ol ll lo ow w t th hi is s W Wa ar rn ni in ng g c co ou ul...

Страница 3: ...I IN NG G E EL LE EC CT TR RI IC CA AL L S SH HO OC CK K H HA AZ ZA AR RD D F Fa ai il lu ur re e t to o f fo ol ll lo ow w t th hi is s W Wa ar rn ni in ng g c co ou ul ld d r re es su ul lt t i in n...

Страница 4: ...y y i in ns sp pe ec ct te ed d t to o i in ns su ur re e n no o c cr ra ac ck ks s o or r o ot th he er r p po ot te en nt ti ia al l a ar re ea as s f fo or r f fl lu ue e g ga as s l le ea ak ks s...

Страница 5: ...c co ou ul ld d r re es su ul lt t i in n p pe er rs so on na al l i in nj ju ur ry y D Do o N NO OT T t to ou uc ch h i ig gn ni it te er r I It t i is s e ex xt tr re em me el ly y h ho ot t C CA AU...

Страница 6: ...te ed d t to o t th he e v ve en nt ti in ng g s sy ys st te em m T Tu ur rn n o on n a an ny y e ex xh ha au us st t f fa an ns s s su uc ch h a as s r ra an ng ge e h ho oo od ds s s so o t th he e...

Страница 7: ...put Check 17 Gas Valve Adjustment 18 High Altitude Derate 19 General Venting 20 Air for Combustion and Ventilation 22 Duct Connections 25 Return Air Filters 32 Electrical Connections 34 Field Wiring 3...

Страница 8: ...ting ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result i...

Страница 9: ...inal air conditioning CFM delivered when pressurized to 5 water column with all inlets outlets and drains sealed General Guidelines The manufacturer assumes no responsibility for equipment installed i...

Страница 10: ...t permit removal of the largest component 4 Are there at least 3 inches of clearance between the Furnace combustion air openings in the front panel and any closed panel or door provided 5 Are the vent...

Страница 11: ...ent wave solutions b Chlorinated waxes and cleaners c Chlorine based swimming pool chemicals d Water softening chemicals e De icing salts or chemicals f Carbon tetrachloride g Halogen type refrigerant...

Страница 12: ...12 18 CE07D1 1C EN Outline Drawings Table 2 17 5 Width Cabinet...

Страница 13: ...l furnace installation in an attic should be on a service platform large enough to allow for proper clearances on all sides and service access to the front of the furnace See the Line contact is only...

Страница 14: ...al Shut off Main Manual Shut off Valve Ground Union Joint Drip Leg 1 8 NPT Test Fitting Furnace in upflow orientation with gas piping on right Note For ease of installation optional accessory part PIP...

Страница 15: ...ing out bottom Automatic Gas Valve with Manual Shut off Main Manual Shut off Valve Ground Union Joint Drip Leg 1 8 NPT Test Fitting Furnace in horizontal right orientation with gas piping out top Auto...

Страница 16: ...y piping system during any pressure testing of that system at test pressures in excess of 1 2 psig 3 5 kPa The furnace must be isolated from the gas supply piping by closing its individual manual shut...

Страница 17: ...utility company and compare to the nameplate rating This must not exceed the nameplate rating Gas Flow in Cubic Feet Per Hour 2 Cubic Foot Dial Sec Flow Sec Flow Sec Flow Sec Flow 10 732 31 236 52 141...

Страница 18: ...ude d Replace and tighten the regulator cover screw securely 6 To adjust the light off manifold pressure remove the low LO adjustment regulator cover screw a To increase outlet pressure turn the regul...

Страница 19: ...ust be changed PART NUMBERS FOR REPLACEMENT ORIFICES DRILL SIZE PART NUMBER B60 23 B80 15 Turn the main Gas Valve toggle switch within the unit to the OFF position Turn the external gas valve to ON Pu...

Страница 20: ...SONRY CHIMNEYS Venting of fan assisted appliances into a lined internal masonry chimney is allowed only if it is common vented with at least one natural draft appliance OR if the chimney is lined with...

Страница 21: ...on of the National Fuel Gas Code ANSI Z223 1 latest edition 10 Vent connectors serving appliance vented by natural draft or non positive pressure shall not be connected into any portion of a mechanize...

Страница 22: ...air and fireplaces must be considered to avoid unsatisfactory Furnace operation Furnace location may be in an unconfined space or a confined space Unconfined space are installations with 50 cu ft or m...

Страница 23: ...d washing material Note Extended warranties are not available in some instances Extended warranty does not cover repairs to equipment installed in establishments with corrosive atmospheres including b...

Страница 24: ...e with the outdoors Refer to the Minimum Free Area in square inches for confined spaces table for minimum open areas required CONFINED SPACE AIR FROM OUTDOORS CONFINED SPACE OUTLET OUTDOOR AIR DUCTS I...

Страница 25: ...aces not equipped with a cooling coil it is recommended that the outlet duct be provided with a removable access panel The opening shall be accessible when the furnace is installed and shall be of suc...

Страница 26: ...uide holes are located on the coil 4 Seal per local codes and requirements Furnace in Horizontal Left with Coil 1 Bend furnace flanges up 2 Support the furnace and coil independently 3 Screw through t...

Страница 27: ...port the furnace and coil independently 3 Match the coil up flush to the back of the furnace 4 Seal per local codes and requirements Note Flat or dedicated horizontal coils may require flanges to be b...

Страница 28: ...rain pan must be installed in all applications over a finished ceiling to prevent property damage Minimum return air is 55oF and maximum is 80oF Upflow Furnace with Bottom Return in Closet with Remote...

Страница 29: ...rom a remote location 3 Install filter at a remote location 4 Seal per local codes and requirements Upflow Furnace with Bottom Return Mounted on a Ducted Pedestal with Filter Box 1 Remove the bottom p...

Страница 30: ...ote The furnace bottom pedestal must be a minimum of 6 in height 3 Match the filter cabinet flush to the back and bottom sides of the furnace cabinet and secure in place with screws 4 Mark the two are...

Страница 31: ...turns Important One of the sides must have a transition to allow the thermostat wiring to exit the cabinet Important If a transition is not a viable option a hole will need to be drilled in the side o...

Страница 32: ...rn air duct systems should provide for installation of return air filters 1 Determine the appropriate position to set the furnace in order to connect to existing supply and return ductwork 2 For upflo...

Страница 33: ...ts to the furnace If only the front of the furnace is accessible it is recommended that both supply and return air plenums are removable 3 When replacing a furnace old duct work should be cleaned out...

Страница 34: ...d furnace control is polarity sensitive The hot leg of the 120V power supply must be connected to the black power lead as indicated on the wiring diagram Refer to the SERVICE FACTS literature and unit...

Страница 35: ...off For complete shutdown Turn the toggle or control switch located on the main gas valve inside the unit to the OFF position and the external main gas shutoff valve to the OFF position Disconnect th...

Страница 36: ...otated if needed Table 5 Venting Options for Upflow Applications Refer to the illustrations below to find the approved venting options for upflow furnace Note Left side venting is not allowed for upfl...

Страница 37: ...cabinet and remove the cutout if necessary Note When rotating the inducer it may be necessary to cut the wire tie A new wire tie must be installed once the inducer is rotated Note Self tapping screws...

Страница 38: ...ded for attaching the vent pipe to the inducer outlet Horizontal left orientation with top venting Before proceeding lay unit on its back to make the conversion easier The following changes need to be...

Страница 39: ...ucer RPM Feedback Inducer Ignitor Connector Not Used Heat Delay ID Plug Connector Status LED Neutral Connections 12 Pin Connector Line Motor Transformer Humidifier EAC Flame Rod Chassis Ground Heat Fa...

Страница 40: ...e Airflow CFM Vs External Static Pressure in W C Model Tap 0 1 0 3 0 5 0 7 0 9 L8X1B060U3PXAA 1 SCFM 829 689 549 410 270 Watts 83 95 107 119 130 2 SCFM 1087 985 884 782 681 Watts 163 179 195 210 226 3...

Страница 41: ...ration is 90 seconds Once the span test fails the fault is displayed until the lockout expires or Call For Heat is removed Could be blocked vent poor air hose connection or an open circuit in the indu...

Страница 42: ...be released within 5 seconds after the LED begins this flash sequence 1 Flash Call for Heating GREEN N A W or W G or W Y or W Y G 2 Flashes Call for Cooling GREEN N A Y or Y G 3 Flashes Continuous Fan...

Страница 43: ...e e If additional retries are needed the ignitor warm up time is successively increased to a maximum of 30 seconds 5 After the ignitor warm up the 1st stage of the gas valve is energized allowing gas...

Страница 44: ...nd Blower On Delay the indoor blower ramps to the HP heating airflow N No ot te e The blower on delay can be field adjusted to 45 seconds if desired but cannot be turned OFF 4 When the temperature is...

Страница 45: ...18 CE07D1 1C EN 45 N No ot te es s...

Страница 46: ...46 18 CE07D1 1C EN N No ot te es s...

Страница 47: ...18 CE07D1 1C EN 47 N No ot te es s...

Страница 48: ...lications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and spe...

Отзывы: