RT-SVX063G-EN
87
Important:
A valid space static pressure sensor is not
required for external relief fan control;
therefore, proper building static pressure
control must be considered.
The controller will annunciate External Relief Fan Control
on the user interface, operating modes screen, when
active. All modes of operation are supported, except when
supply fan is off. If the supply fan cycles off with capacity,
the relief fan will also turn off. External relief fan speed is
also interlocked with relief damper position and relief
damper diagnostics. The relief damper movement will limit
relief fan speed changes accordingly. The controller will
impose speed limitations as required.
Table 38.
External relief fan control points
Object Name
(a)
Description
Object States or
values
Exhaust Fan Speed
Setpoint Enable
Enables Relief fan
speed setpoint control
0 = Disable
1 = Enable
Exhaust Fan Speed
Control Enabled
Relief fan speed is
control via Exhaust
Fan Speed Setpoint.
If disabled/inactive,
speed control is under
local control.
0 = Disabled
1 = Enabled
Exhaust Fan Speed
Setpoint
External supplied
exhaust fan speed
setpoint value
0 to 100%
Exhaust Fan Speed
Setpoint Active
Active setpoint input
to relief fan speed
control
0 to 100%
Exhaust Fan Speed
Status
Indicates the
requested speed to
the relief fan, 0%
when fan is off.
0 to 100%
(a)
Reference Integration Guide ACC-SVP02B (or later)
Table 39.
Exhaust fan speed setpoint summary
Exhaust Fan
Speed Setpoint
Enable
Exhaust Fan
Speed Setpoint
Exhaust fan
operation
Disable
NA
Fan under local
control
Enable
0%
Commands the fan off
Enable
1% to min speed%
Fan operates at drive
minimum setting
(a)
Enable
>min speed% to
100%
Fan ramps between
motors min-rpm and
the Relief Fan
Maximum Speed
Setpoint (rpm),
adjustable at the
unit’s front panel
display, service
settings screen.
(a)
The drive minimum RPM setting is 10 percent of nameplate rated speed. The
min speed% is equal to: 100 x (drive minimum RPM / Relief Fan Maximum
Speed Setpoint).
External Outdoor Air Damper Control
To control the outdoor damper directly, via TGP2 or an
external control, a setpoint can be written to Economizer
Minimum Position Setpoint BAS. The controller will limit the
damper movement. The commanded position reports at
Outdoor Air Damper Position.
To have complete damper control, the following functions
should be disabled or removed from configuration via
Tracer TU or front panel display. However, the controller
must be configured with an Economizer damper.
•
Economizer Airside Enable Default = Disabled
•
Demand Control Ventilation Enable = Disabled
•
Traq Enable = Disabled
•
Outdoor Air Flow Compensation Enable = Disable
Morning Warm Up, Pre-Cool, Night Purge, Unoccupied,
and Off modes of operation will override damper minimum
position to 0%.
Overrides
The controller normally provides heating, cooling and
ventilation for building comfort. The below control functions
can intervene or override normal operation. These
functions allow control over the IntelliPak unit as well as a
means for the Service Technician to accomplish their tasks.
The order of priorities are listed. For example, an External
Stop will prevent the unit from performing Ventilation
Override.
1. Local Stop
2. Emergency Stop
3. External Stop
4. Manual Control
5. Ventilation Override
6. Emergency Override
7. Operating Mode Off
8. Normal operating modes
If local stop, emergency stop, or external stop request a
Stop, the unit will shut down and not resume operation until
all inputs allow automatic operation.
Local Stop
Local Stop is performed by the Front Panel Stop button on
the front panel display. The controller will perform a Normal
Shutdown process unless, the user additionally selects
Immediate Shutdown at the front panel when prompted.
Normal Shutdown Process
In a normal shutdown situation, compressors, fans, and
other systems of the unit are allowed to go through an
orderly shutdown sequence. For example, compressors
continue to run for any remaining Minimum Run time.
If a Service Tool requires the unit to be in Front Panel Stop
for an operation, e.g. binding, configuration, or software
Содержание IntelliPak with Symbio 800
Страница 16: ...16 RT SVX063G EN Figure 1 20 to 30 ton front view inches 40 28 90 63 27 31 FRONT VIEW 20 30T Dimensional Data ...
Страница 18: ...18 RT SVX063G EN Figure 3 40 to 55 ton front view inches 27 31 40 28 90 63 FRONT VIEW 40 55T Dimensional Data ...
Страница 64: ...64 RT SVX063G EN Figure 37 Dry bulb changeover map Startup the Unit ...
Страница 137: ...RT SVX063G EN 137 Notes ...
Страница 138: ...138 RT SVX063G EN Notes ...
Страница 139: ...RT SVX063G EN 139 Notes ...