86
RT-SVX063G-EN
Multi Zone-VAV units operate the supply fan under duct
static pressure control, unless commanded to go to
Maximum Heat.
Unoccupied Cooling
Unoccupied Cooling mode is used when the building is
unoccupied and the space conditions are exceeding
temperature limits. The unit is normally off in unoccupied
mode. If a valid space temperature input rises above the
Unoccupied Cooling Setpoint, unit operation starts
unoccupied cooling to manage space temperature. The
controller operates in Discharge Air Control with ventilation
disabled while DX or economizer cooling capacity
increases to satisfy the Discharge Air Cooling Setpoint.
Multi Zone VAV units operate the supply fan with duct static
pressure control, other units operate the supply fan at
maximum speed. Cooling continues until space
temperature is 4°F less than the Unoccupied Cooling
Setpoint, the unit will then cycle off.
Unoccupied Cooling Mechanical Enable and Unoccupied
Cooling Economizing Enable are settings to enable or
disable cooling in unoccupied mode.
Unoccupied Heating
When the unit is in unoccupied mode and the valid space
temperature input falls below the Unoccupied Heating
Setpoint, unit operation starts unoccupied heating to
manage space temperature. The controller operates in
Discharge Air Control with ventilation disabled while
heating capacity increases to satisfy the Discharge Air
Heating Setpoint. The supply fan operates according to
heat type installed, see Heat Types for more information.
Heating continues until space temperature is 4°F greater
than the Unoccupied Heating Setpoint, the unit will then
cycle off.
Unoccupied Heating Enable is a setting to enable or
disable heating in unoccupied mode at the Front Panel.
External Control
Symbio 800 provides the ability for an external controller or
program to control supply fan, exhaust fan, and outdoor air
damper. This capability allows for custom programming
suited for specific application needs.
External Supply Fan Control
External supply fan control applies to variable volume
supply fan equipment. Supply fan operation must prove
running and any unit startup timing must expire before
external control is allowed. Supply Fan Speed Control
Enabled provides an enabled status when Supply Fan
Speed Setpoint is in control. The controller will annunciate
External Supply Fan Control on the user interface,
operating modes screen when active.
Supply Fan Speed Setpoint will only override the
controller’s fan control in occupied Cool, Heat, and Fan
Only modes of operation. All other modes (such as Morning
Warm Up, Pre Cool, Daytime Warm Up) the supply fan is
operated under Symbio 800 control. Supply fan speed will
increase under Symbio 800 control according to heating
and cooling capacity requirements; space temperature
control unit configurations. Supply fan speed will decreases
under Symbio 800 control when high duct static pressure
limits are approached; discharge air control unit
configurations.
Table 36.
External supply fan control points
Object
Name
Description
Supply Fan
Speed
Setpoint
Enable
Enables supply fan speed setpoint control
Supply Fan
Speed
Control
Enabled
Supply fan speed is control via Supply Fan Speed
Setpoint. If disabled/inactive, speed control is under
Symbio 800 control
Supply Fan
Speed
Limited
Supply fan speed is being increased or decreased due
to a limit control action.
Supply Fan
Speed
Setpoint
External supplied supply fan speed setpoint value
Supply Fan
Speed
Setpoint
Active
Active setpoint input to supply fan speed control
Supply Fan
Speed
Status
Indicates the requested speed to the supply fan, 0%
when fan is off.
Table 37.
Supply fan speed setpoint summary
Supply Fan Speed
Setpoint Enable
Supply Fan Speed
Setpoint
Supply fan
operation
Disable
NA
Fan under Symbio
800 control
Enable
0%
Commands the fan off
Enable
1% to 37%
(a)
Fan operates at drive
minimum Hz setting
Enable
38% to 100%
Fan ramps between
drive min-Hz and
max-Hz setting.
(a)
For example, if drive setting is 22 min-Hz and 60 max-Hz, it will correlate to
37% reported fan speed.
External Relief Fan Control
External Relief fan control is allowed anytime a relief fan is
configured. Supply fan and relief fan operation is proven
before external fan control is allowed. Relief fan operation
is effectively interlocked with supply fan operation. No other
control limits are applied; building static pressure high limit
is not enforced.
Содержание IntelliPak with Symbio 800
Страница 16: ...16 RT SVX063G EN Figure 1 20 to 30 ton front view inches 40 28 90 63 27 31 FRONT VIEW 20 30T Dimensional Data ...
Страница 18: ...18 RT SVX063G EN Figure 3 40 to 55 ton front view inches 27 31 40 28 90 63 FRONT VIEW 40 55T Dimensional Data ...
Страница 64: ...64 RT SVX063G EN Figure 37 Dry bulb changeover map Startup the Unit ...
Страница 137: ...RT SVX063G EN 137 Notes ...
Страница 138: ...138 RT SVX063G EN Notes ...
Страница 139: ...RT SVX063G EN 139 Notes ...