72
RT-SVX063G-EN
Table 31.
Outdoor air damper minimum ventilation control
Traq
Outdoor Air Flow
Compensation
Demand Control
Ventilation
Description
Outdoor Air Damper
Controlling Setpoints
Enabled/Active
Disabled
Disabled
Damper controls to outdoor
air minimum flow setpoint
Setpoint:
Outdoor Air Minimum Flow
Setpoint Active
Outdoor Air Minimum Flow
Setpoint Status
Enabled/Active
Disabled
Enabled/Active
Outdoor Air Flow setpoint is
reset based on space CO
2
.
Setpoint:
Outdoor Air Minimum Flow
Setpoint Status
Settings:
Design Min Outdoor Air Flow
Setpoint
DCV Min Outdoor Air Flow
Setpoint
Disabled
Enabled/Active
Disabled
Outdoor Air Damper
Minimum Position is reset
based on supply fan speed.
Setpoint:
Economizer Minimum
Position Setpoint Active
Settings:
Design Min OA Damper Pos
Setpoint Max Fan
Design Min OA Damper Pos
Setpoint Mid Fan
Design Min OA Damper Pos
Setpoint Min Fan
Disabled
Enabled/Active
Enabled/Active
Outdoor Air Damper
Minimum Position is reset
based on supply fan speed
and space CO2.
Setpoint:
Economizer Minimum
Position Setpoint Active
Settings:
Design Min OA Damper Pos
Setpoint Max Fan
Design Min OA Damper Pos
Setpoint Mid Fan
Design Min OA Damper Pos
Setpoint Min Fan
DCV Min Outdoor Air Dampr
Pos at Max Fan
DCV Min Outdoor Air Dampr
Pos at Min Fan
Disabled
Disabled
Enabled/Active
Outdoor Air Damper
Minimum Position is reset
based on space CO
2
.
Setpoint:
Economizer Minimum
Position Setpoint Active
Settings:
Design Min OA Damper
Position
DCV Min Outdoor Air
Damper Pos Setpoint
Disabled
Disabled
Disabled
Outdoor air damper position
is control by
Setpoint:
Economizer Minimum
Position Setpoint Active
During normal occupied periods of heating and cooling
modes of operation, the outdoor air damper maintains
ventilation requirements via the minimum position control
methods. However, the following modes of operation will
override the damper minimum position setpoint to 0%.
•
Morning Warm Up
•
Pre cool
•
Night Purge
•
Unoccupied Heat
•
Unoccupied Cool
•
Off
Relief Fan and Space Static
Pressure Control
The primary role of relief fan is to relieve air from the
building to control space static pressure. This is common
Содержание IntelliPak with Symbio 800
Страница 16: ...16 RT SVX063G EN Figure 1 20 to 30 ton front view inches 40 28 90 63 27 31 FRONT VIEW 20 30T Dimensional Data ...
Страница 18: ...18 RT SVX063G EN Figure 3 40 to 55 ton front view inches 27 31 40 28 90 63 FRONT VIEW 40 55T Dimensional Data ...
Страница 64: ...64 RT SVX063G EN Figure 37 Dry bulb changeover map Startup the Unit ...
Страница 137: ...RT SVX063G EN 137 Notes ...
Страница 138: ...138 RT SVX063G EN Notes ...
Страница 139: ...RT SVX063G EN 139 Notes ...