66
RT-SVX063G-EN
provided. Temperature control is determined by energy
conservation and building protection thresholds.
Occupied Bypass Operation
: The IntelliPak unit is
temporarily in an Occupied state for some period of time
and will automatically return to unoccupied operation when
the bypass timer expires. The Occupied Bypass Timer is a
user-adjustable field. However setting the timer to 0
minutes effectively disables Timed Override at the
equipment controller.
Occupied Standby Operation
: Standby does not apply to
a discharge air controller (VVDA, CVDA unit type). These
units treat Standby as Occupied. Space temperature
control units in an Occupied-Standby state are controlling
to occupied standby temperature setpoints. Normal
operation will resume when Occupancy Status goes to an
Occupied state.
Table 29.
Occupancy Status
Occupancy
Request
Occupancy
Input
Bypass
Timer
Occupancy
Status
Occupied
Occupied
Any Number
Occupied
Occupied
Unoccupied
Zero
Standby
Occupied
Unoccupied
Not Zero
Bypass
Unoccupied
Any State
Zero
Unoccupied
Unoccupied
Any State
Not Zero
Bypass
Bypass
Occupied
Any Number
Occupied
Bypass
Unoccupied
Zero
Standby
Bypass
Unoccupied
Not Zero
Bypass
Standby
Any State
Zero
Standby
Standby
Any State
Not Zero
Bypass
Auto
Occupied
Any Number
Occupied
Auto
Unoccupied
Zero
Unoccupied
Auto
Unoccupied
Not Zero
Bypass
Timed Override
Timed Override (TOV) is a function that allows a user,
located in the conditioned space, to temporarily override
the IntelliPak operation from unoccupied mode to occupied
mode (referred to as Occupied-Bypass). To accomplish
this, Trane wired or wireless zone sensor devices are
equipped with “On” and “Cancel” push buttons. Some
sensors refer to the buttons as “Occupied” and
“Unoccupied”. Timed override operation applies, in some
way, to all unit types.
On Wired sensors, the timed override request (ON) and
timed override cancel (CANCEL) buttons momentary
modify the zone temperature thermistor resistance to a
value outside the normal zone temperature operating
range. The Symbio 800 controller detects this change;
however, this momentary button press does not disrupt the
space temperature value being used. The press duration is
0.5 to 8 seconds.
Wireless sensors process the timed override request/
cancel signal at the sensor and communicate the
appropriate timed override status (mode).
Service Pin Message Request
A secondary feature of wired zone sensors is Service Pin
Message Request, not associated with TOV. An On/
Occupied push button press for 8 to 30 seconds can initiate
Neuron ID and Program ID message broadcast on a LON
network. This function is used to install and troubleshoot
LON networks. This feature benefits installation of a LON
device by initiating the service pin message from a zone
sensor rather than at the equipment.
Sensors
The IntelliPak unit uses many types of sensors. Many
sensors are factory installed. Some sensors are field
installed and may be wired or wireless. Field installed wired
sensors are available from Trane and many other sources.
In every case, the correct type of sensor must be used.
All sensors are factory calibrated and require no field re-
calibration. See the Product Catalog for more information
on sensors.
Heat Cool Mode Status
Heat Cool Mode Status reports the unit mode of operation.
The Symbio 800 can receive mode inputs from different
external and local input sources that are arbitrated;
however, the control active operating mode represents the
capacity being delivered to the building and reported via
Heat Cool Mode Status.
Heat
In this mode, the controls provide heating capacity per heat
type installed, active heat setpoint, and occupancy.
Application requirements such as full or modulating air flow
are also considered in heating mode. All forms of cooling
capacity are effectively disabled.
If Heat is the requested mode when the unit does not have
heat capacity configured or heat is disabled, Heat is
reported as Heat Cool Mode Status. If the unit cannot
provide heat, the supply fan is enabled to operate (as
configured) to provide ventilation during occupied modes of
operation.
Содержание IntelliPak with Symbio 800
Страница 16: ...16 RT SVX063G EN Figure 1 20 to 30 ton front view inches 40 28 90 63 27 31 FRONT VIEW 20 30T Dimensional Data ...
Страница 18: ...18 RT SVX063G EN Figure 3 40 to 55 ton front view inches 27 31 40 28 90 63 FRONT VIEW 40 55T Dimensional Data ...
Страница 64: ...64 RT SVX063G EN Figure 37 Dry bulb changeover map Startup the Unit ...
Страница 137: ...RT SVX063G EN 137 Notes ...
Страница 138: ...138 RT SVX063G EN Notes ...
Страница 139: ...RT SVX063G EN 139 Notes ...