RT-SVX063G-EN
63
Table 27.
Startup checklist (continued)
Completed?
1
Electric heat circuits have continuity
Yes
No
2
Perform electric heat start up procedure
Yes
No
3
Verify heating system matches name plate
Yes
No
Gas Heat (if applicable)
1
Gas heat piping includes drip leg previously installed by installing contractor
Yes
No
2
Gas heat flue assembly fully installed
Yes
No
3
Gas heat condensate line and heat tape installed where applicable
Yes
No
4
Verify heating system matches name plate
Yes
No
5
Perform Gas Heat start up procedure in IOM
Yes
No
System Checkout
1
Verify system airflow
Yes
No
2
Verify dampers open and close properly
Yes
No
3
Adjust economizer damper travel
Yes
No
4
Verify compressor operation, voltage and amperage matches name plate information (please document on log sheet)
Yes
No
5
Electric heat operation verified
Yes
No
6
Incoming gas pressure does not drop below 7" water column when burner is on high fire
Yes
No
7
Gas heat operation has been verified with combustion analyzer
Yes
No
8
Operating log completed
Yes
No
9
All panels & doors secured
Yes
No
10
Complete all required documentation
Yes
No
Critical Control Parameters and Dry Bulb Changeover Map
Table 28.
Critical control parameters
Description
Suggested
Parameter
Economizer Settings
Region 1 Region 2 Region 3 Region 4 Region 5 Region 6 Region 7
Supply Air Temperature Control Setpoint
55°F
Supply Air Temperature Deadband
8°F
Supply Air Pressure Setpoint
1.8" w.c.
Supply Air Pressure Deadband
0.1" w.c.
Building Static Pressure Setpoint
0.03" w.c.
Building Static Pressure Deadband
0.04" w.c.
Standby Freeze Avoidance
20%
Relief Enable Setpoint
10%
Economizer Minimum Position Setpoint
10%
Fixed Dry Bulb Economizer C/O Type a (Moist)*
TOA > 65°
F
TOA > 65°
F
TOA > 65°
F
TOA > 65°
F
TOA > 70°
F
TOA > 70°
F
TOA > 70°
F
Fixed Dry Bulb Economizer C/O Type b (Dry)*
TOA > 75°F
Fixed Dry Bulb Economizer C/O Type c (Marine)*
TOA > 75°
F
TOA > 75°
F
TOA > 75°
F
Fixed Reference (Enthalpy Changeover)
HOA > 28 Btu
Differential Comparative (Enthalpy Changeover)
HOA > HRA
Notes:
1
.
See map in next figure for dry bulb changeover.
Examples:
- Minneapolis, Minnesota is in “Region 6" and resides in “Moist” subregion, thus designation is 6b. Economizer changeover setting should be 75°F.
- Charleston, South Carolina is in “Region 3" and resides in “Moist” subregion, thus the designation is 3c. Economizer changeover setting should be 65°F.
2
.
Go to SETUP menu and input setting for parameters listed in the table above.
3
.
Use the Dry bulb changeover map to determine region of country based on unit site location.
4
.
Fixed speed compressor units 8°F deadband.
5
.
eFlex™ compressor units 4°F deadband.
Содержание IntelliPak with Symbio 800
Страница 16: ...16 RT SVX063G EN Figure 1 20 to 30 ton front view inches 40 28 90 63 27 31 FRONT VIEW 20 30T Dimensional Data ...
Страница 18: ...18 RT SVX063G EN Figure 3 40 to 55 ton front view inches 27 31 40 28 90 63 FRONT VIEW 40 55T Dimensional Data ...
Страница 64: ...64 RT SVX063G EN Figure 37 Dry bulb changeover map Startup the Unit ...
Страница 137: ...RT SVX063G EN 137 Notes ...
Страница 138: ...138 RT SVX063G EN Notes ...
Страница 139: ...RT SVX063G EN 139 Notes ...