54
RT-SVX063G-EN
Table 21.
Outside Air Pressure Drop (inches w.c.) – No Traq™ (continued)
No Traq™
CFM
Outside Air Damper Position
100%
75%
55%
45%
33%
22000
0.35
0.72
1.11
1.58
-
24000
0.40
0.85
1.33
1.90
-
26000
0.47
0.99
1.57
2.24
-
28000
0.53
1.14
1.83
2.61
-
30000
0.60
1.31
2.10
-
-
Table 22.
Outside Air Pressure Drop (inches w.c.) – Traq™
Traq™
CFM
Outside Air Damper Position
100%
75%
55%
45%
33%
60, 70 and 75 Ton
14000
0.34
0.48
0.61
0.78
1.28
16000
0.43
0.62
0.80
1.03
1.75
18000
0.54
0.78
1.02
1.33
2.30
20000
0.66
0.96
1.27
1.65
2.92
22000
0.78
1.15
1.55
2.02
-
24000
0.92
1.37
1.85
2.42
-
26000
1.07
1.60
2.18
2.85
-
28000
1.24
1.85
2.53
-
-
30000
1.41
2.12
2.91
-
-
Table 23.
Return Air Pressure Increase (inches w.c.)
CFM
Return Air Damper Position
100%
80%
65%
45%
60, 70 and 75 Ton
14000
0.00
0.02
0.04
0.37
16000
0.00
0.03
0.06
0.53
18000
0.00
0.04
0.08
0.71
20000
0.00
0.05
0.11
0.92
22000
0.00
0.06
0.14
1.15
24000
0.00
0.07
0.17
1.41
26000
0.00
0.08
0.21
1.70
28000
0.00
0.10
0.25
-
30000
0.00
0.11
0.30
-
Содержание IntelliPak with Symbio 800
Страница 16: ...16 RT SVX063G EN Figure 1 20 to 30 ton front view inches 40 28 90 63 27 31 FRONT VIEW 20 30T Dimensional Data ...
Страница 18: ...18 RT SVX063G EN Figure 3 40 to 55 ton front view inches 27 31 40 28 90 63 FRONT VIEW 40 55T Dimensional Data ...
Страница 64: ...64 RT SVX063G EN Figure 37 Dry bulb changeover map Startup the Unit ...
Страница 137: ...RT SVX063G EN 137 Notes ...
Страница 138: ...138 RT SVX063G EN Notes ...
Страница 139: ...RT SVX063G EN 139 Notes ...