RT-SVX063G-EN
109
☐
Inspect the unit air filters. If necessary, clean or replace
them.
☐
Check supply fan motor bearings; repair or replace the
motor as necessary.
☐
Inspect both the main unit control panel and heat
section control box for loose electrical components and
terminal connections, as well as damaged wire
insulation. Make any necessary repairs.
☐
Gas units only - Check the heat exchanger(s) for any
corrosion, cracks, or holes.
☐
Gas units only - Check the combustion air blower and
venting system for dirt or blockage from animals or
insects. Clean as necessary.
☐
Gas units only - Check that burner, tubes, and orifices
are free of debris or blockage from insects.
☐
Check gas piping for leaks.
☐
Gas units only - Open the main gas valve and apply
power to the unit heating section; then initiate a “Heat”
test using the startup procedure described in
Modulating, and Ultra Modulating,” p. 59
WARNING
Hazardous Gases and Flammable
Vapors!
Failure to observe the following instructions could
result in exposure to hazardous gases, fuel
substances, or substances from incomplete
combustion, which could result in death or
serious injury. The state of California has
determined that these substances may cause
cancer, birth defects, or other reproductive harm.
Improper installation, adjustment, alteration,
service or use of this product could cause
flammable mixtures or lead to excessive carbon
monoxide. To avoid hazardous gases and
flammable vapors follow proper installation and
setup of this product and all warnings as provided
in this manual.
Coil Cleaning
Regular coil maintenance, including annual cleaning
enhances the unit’s operating efficiency by minimizing the
following:
•
Compressor head pressure and amperage draw
•
Water carryover
•
Fan brake horsepower
•
Static pressure losses
At least once each year—or more often if the unit is located
in a “dirty” environment—clean the evaporator coils using
the instructions outlined below. Be sure to follow these
instructions as closely as possible to avoid damaging the
coils.
WARNING
Hazardous Chemicals!
Failure to follow this safety precaution could result in
death or serious injury. Coil cleaning agents can be
either acidic or highly alkaline and can burn severely
if contact with skin or eyes occurs.
Handle chemical carefully and avoid contact with
skin. ALWAYS wear Personal Protective Equipment
(PPE) including goggles or face shield, chemical
resistant gloves, boots, apron or suit as required. For
personal safety refer to the cleaning agent
manufacturer’s Materials Safety Data Sheet and follow
all recommended safe handling practices.
Refrigerant Coils
To clean refrigerant coils, use a soft brush and a sprayer.
For evaporator and reheat coil cleaners, contact the local
Trane Parts Center for appropriate detergents.
1. Remove enough panels from the unit to gain safe
access to coils.
2. Straighten any bent coil fins with a fin comb.
3. For accessible areas, remove loose dirt and debris
from both sides of the coil. For dual row microchannel
condenser coil applications, seek pressure coil wand
extension through the local Trane Parts Center.
4. When cleaning evaporator and reheat coils, mix the
detergent with water according to the manufacturer’s
instructions. If desired, heat the solution to 150° F
maximum to improve its cleansing capability.
Important:
DO NOT use any detergents with
microchannel coils. Pressurized water or
air ONLY.
5. Pour the cleaning solution into the sprayer. If a high-
pressure sprayer is used:
a. The minimum nozzle spray angle is 15 degrees.
b. Do not allow sprayer pressure to exceed 600 psi.
c. Spray the solution perpendicular (at 90 degrees) to
the coil face.
d. For evaporator and reheat coils, maintain a
minimum clearance of 6" between the sprayer
nozzle and the coil. For microchannel condenser
coils, optimum clearance between the sprayer
nozzle and the microchannel coil is 1"-3”.
6. Spray the leaving-airflow side of the coil first; then
spray the opposite side of the coil. For evaporator and
reheat coils, allow the cleaning solution to stand on the
coil for five minutes.
7. Rinse both sides of the coil with cool, clean water.
8. Inspect both sides of the coil; if it still appears to be
dirty, repeat Steps 6 and 7.
9. Reinstall all of the components and panels removed in
Step 1; then restore power to the unit.
10. For evaporator and reheat coils, use a fin comb to
Содержание IntelliPak with Symbio 800
Страница 16: ...16 RT SVX063G EN Figure 1 20 to 30 ton front view inches 40 28 90 63 27 31 FRONT VIEW 20 30T Dimensional Data ...
Страница 18: ...18 RT SVX063G EN Figure 3 40 to 55 ton front view inches 27 31 40 28 90 63 FRONT VIEW 40 55T Dimensional Data ...
Страница 64: ...64 RT SVX063G EN Figure 37 Dry bulb changeover map Startup the Unit ...
Страница 137: ...RT SVX063G EN 137 Notes ...
Страница 138: ...138 RT SVX063G EN Notes ...
Страница 139: ...RT SVX063G EN 139 Notes ...