Service and Maintenance
WARNING
Hazardous Voltage and Exposure to
Ultraviolet Radiation!
This product contains components that emit high-
intensity ultraviolet (UV-C) radiation which can be
harmful to unprotected eyes and skin, and cause
serious damage to the equipment.
Failure to disconnect power before servicing could
result in burns or electrocution which could result in
death or serious injury.
Disconnect all electrical power, including remote
disconnects, and make sure the UV lights are off
before servicing. Follow proper lockout/tagout
procedures to ensure the power cannot be
inadvertently energized.
Trane does not recommend field installation of
ultraviolet lights in its equipment for the intended
purpose of improving indoor air quality. Trane accepts
no responsibility for the performance or operation of
our equipment in which ultraviolet devices were
installed outside of the Trane factory or its approved
suppliers.
Compressor Circuit Breakers
Every fixed speed compressor is protected by a circuit
breaker. If replacement is necessary, please refer to the
circuit breaker nameplate to identify the part number and
manufacturer. Contact the circuit breaker manufacturer to
locate the datasheet for the circuit breaker to find the "must
hold / must trip" values.
Supply and Relief/Return Fan Overloads
When the VFD bypass option is selected, each supply and
relief/return fan is protected by a motor overload when in
VFD bypass mode. On 60-75T units with dual DDP supply
fan motors (with or without VFD bypass option), each
supply fan motor is protected by a motor overload in both
standard operation and VFD bypass mode. The motor
overloads are factory set to the motor FLA value and
should not be adjusted. If the current to the motor exceeds
the overload dial setting value, the overload relay auxiliary
contacts will trip and interrupt the control signal to the run
and bypass contactor coils. This will remove power from
the fan motor and stop operation.
Table 58.
Filter data
Unit
Tons
Evaporator Filters
Final Filters
2" Panel Filters (MERV 4
or MERV 8)
4" Panel Filters (MERV 8
or MERV 14)
2" Prefilters
Cartridge Filters
2" Prefilters
Cartridge Filters
Qty
Size of
Each
Face
Area
(ft
2
)
Qty
Size of
Each
Face
Area
(ft
2
)
Qty
Size of
Each
Qty
Size of
Each
Face
Area
(ft
2
)
Qty
Size of
Each
Qty
Size of
Each
Face
Area
(ft
2
)
20
4
16x20x2
32.2
4
16x20x4
32.2
4
16x20x2
4
16x20x12
33.3
4
16x20x2
4
16x20x12
33.3
6
20x20x2
6
20x20x4
4
20x20x2
4
20x20x12
4
20x20x2
4
20x20x12
2
20x24x2
2
20x24x4
4
20x24x2
4
20x24x12
4
20x24x2
4
20x24x12
25
4
16x20x2
32.2
4
16x20x4
32.2
4
16x20x2
4
16x20x12
33.3
4
16x20x2
4
16x20x12
33.3
6
20x20x2
6
20x20x4
4
20x20x2
4
20x20x12
4
20x20x2
4
20x20x12
2
20x24x2
2
20x24x4
4
20x24x2
4
20x24x12
4
20x24x2
4
20x24x12
30
4
16x20x2
32.2
4
16x20x4
32.2
4
16x20x2
4
16x20x12
33.3
4
16x20x2
4
16x20x12
33.3
6
20x20x2
6
20x20x4
4
20x20x2
4
20x20x12
4
20x20x2
4
20x20x12
2
20x24x2
2
20x24x4
4
20x24x2
4
20x24x12
4
20x24x2
4
20x24x12
40
3
20x20x2
39.7
3
20x20x4
39.7
2
20x20x2
2
20x20x12
41.6
4
20x20x2
4
20x20x12
39.1
7
20x24x2
7
20x24x4
6
20x24x2
6
20x24x12
6
20x24x2
6
20x24x12
2
24x24x2
2
24x24x4
4
24x24x2
4
24x24x12
2
24x24x2
2
24x24x12
50
3
20x20x2
39.7
3
20x20x4
39.7
2
20x20x2
2
20x20x12
41.6
4
20x20x2
4
20x20x12
39.1
7
20x24x2
7
20x24x4
6
20x24x2
6
20x24x12
6
20x24x2
6
20x24x12
2
24x24x2
2
24x24x4
4
24x24x2
4
24x24x12
2
24x24x2
2
24x24x12
Содержание IntelliPak with Symbio 800
Страница 16: ...16 RT SVX063G EN Figure 1 20 to 30 ton front view inches 40 28 90 63 27 31 FRONT VIEW 20 30T Dimensional Data ...
Страница 18: ...18 RT SVX063G EN Figure 3 40 to 55 ton front view inches 27 31 40 28 90 63 FRONT VIEW 40 55T Dimensional Data ...
Страница 64: ...64 RT SVX063G EN Figure 37 Dry bulb changeover map Startup the Unit ...
Страница 137: ...RT SVX063G EN 137 Notes ...
Страница 138: ...138 RT SVX063G EN Notes ...
Страница 139: ...RT SVX063G EN 139 Notes ...