RT-SVX063G-EN
103
T
able
55.
Component
static
pressure
drops
(in.
H
2
O)
(continued)
T
ons
CFM
Std
Evap
Coil
HGRH
Heating
System
Filters
Economizer
Standard
High
Efficiency
V
ariable
Gas
Electric
Pre
Evap
Panel
Pre
Evap
Cart
Final
Cart
Return
Air
Outside
Air
W/O
T
raq
Outside
Air
W/
T
raq
Dry
Wet
Dry
Wet
Dry
Wet
250
MBh
350
MBh
500
MBh
850
MBh
1200
MBh
All
kW
2"
Merv
4
2"
Merv
8
4"
Merv
8
4"
Merv
14
75
15000
0.47
0.51
0.24
0.26
0.24
0.26
0.03
0.56
0.70
0.63
0.26
0.08
0.14
0.13
0.38
0.34
0.38
0.22
0.25
0.25
18000
0.58
0.00
0.29
0.35
0.28
0.35
0.04
0.80
1.01
0.90
0.38
0.1
1
0.21
0.18
0.55
0.49
0.55
0.32
0.36
0.36
21000
0.68
0.88
0.32
0.45
0.34
0.45
0.06
1.09
1.38
1.23
0.52
0.15
0.28
0.25
0.74
0.66
0.75
0.44
0.49
0.49
24000
0.85
1.08
0.39
0.55
0.39
0.55
0.08
1.42
1.80
1.60
0.68
0.20
0.37
0.33
0.97
0.87
0.98
0.57
0.63
0.63
27000
1.03
1.29
0.48
0.67
0.48
0.67
0.10
1.80
2.28
2.03
0.86
0.25
0.47
0.41
1.23
1.10
1.24
0.73
0.80
0.80
30000
1.22
1.51
0.57
0.79
0.57
0.79
0.12
2.22
2.81
2.50
1.06
0.31
0.58
0.51
1.52
1.35
1.53
0.90
0.99
0.99
Notes:
1
.
Static
pressure
drops
of
accessory
components
must
be
added
to
determine
total
static
pressure
for
fan
selections.
2
.
Gas
heat
section
maximum
temperature
rise
of
60°F
.
3
.
Economizer
static
pressure
value
for
sizing
supply
fan
is
the
highest
of
the
following:
a)
Return
air
static
pressure
drop
plus
customer
return
duct
static
pressure
and
b)
Outside
air
static
pressure
drop.
Содержание IntelliPak with Symbio 800
Страница 16: ...16 RT SVX063G EN Figure 1 20 to 30 ton front view inches 40 28 90 63 27 31 FRONT VIEW 20 30T Dimensional Data ...
Страница 18: ...18 RT SVX063G EN Figure 3 40 to 55 ton front view inches 27 31 40 28 90 63 FRONT VIEW 40 55T Dimensional Data ...
Страница 64: ...64 RT SVX063G EN Figure 37 Dry bulb changeover map Startup the Unit ...
Страница 137: ...RT SVX063G EN 137 Notes ...
Страница 138: ...138 RT SVX063G EN Notes ...
Страница 139: ...RT SVX063G EN 139 Notes ...