Component Static Pressure
Drops
Table 54.
Static pressure drops — relief dampers
Nominal Tons
CFM
Relief Damper
Pressure Drop (in
w.c.)
20-40 Single Fan
2,000
0.04
4,000
0.16
6,000
0.37
8,000
0.65
10,000
1.02
30-55 Dual Fan
4,000
0.04
6,000
0.09
8,000
0.16
10,000
0.26
12,000
0.37
14,000
0.5
16,000
0.65
18,000
0.83
20,000
1.02
22,000
1.24
60-75 Dual or Three-Fan Array
6,000
0.07
8,000
0.12
10,000
0.19
12,000
0.27
14,000
0.37
16,000
0.48
18,000
0.61
20,000
0.75
22,000
0.91
24,000
1.08
26,000
1.27
28,000
1.47
Notes:
1
.
Relief damper static pressure drop is used only for relief fan selections.
2
.
Use Relief CFM to determine pressure drop to add to return duct static pressure for
relief fan selection.