88
SCXF-SVX01B-EN
Do not exceed 200 psig when
leak testing the system. Damage
to the unit could result, or an
explosion may occur causing
injury or death.
In the event of required system repair,
leak test the liquid line, evaporator coil,
and suction line at pressures dictated by
local codes, using the following
guidelines.
1. Charge enough refrigerant and dry
weight. Use an accurate scale or
charging cylinder to determine the
exact weight of the refrigerant entering
the system. Failure to use either a scale
or a charging cylinder can lead to
undercharging or overcharging
resulting in unreliable operation.
Owner
Maintenance
WARNING
!
Do not apply flame to the
refrigerant container to increase
refrigerant pressure. Uncontrolled
heat may cause excessive drum
pressures and explosions,
resulting in injury or death and
equipment damage.
Do not allow liquid refrigerant to
come into contact with the skin.
If it does, treat the injury as if the
skin had been frostbitten or
frozen. Slowly warm the affected
area with lukewarm water and
seek medical attention
immediately.
To charge the system, complete the
following procedure:
1. Charge liquid refrigerant into the liquid
line service valve of each compressor
circuit. The vacuum will draw some of
the required refrigerant into the
system. See Figure O-M-9 on page 89.
2. Complete the charging process by
charging gaseous refrigerant into the
suction line shrader valve with the unit
running. However, make sure that
some refrigerant is present in each
circuit before starting the compressors.
The refrigerant container should be
upright so that gaseous refrigerant is
drawn off the top.
Note: Charge each circuit with R22. See
Tables O-M-3 and O-M-4.
Do not allow liquid refrigerant to
enter the suction line. Excessive
liquid will damage the
compressor.
WARNING
!
CAUTION
!
CAUTION
!
Table O-M-3. Water-Cooled Unit (SXWF) Refrigerant Charge.
Unit Size
Circuit A
Circuit B
Circuit C
Circuit D
Charge (lbs.)
Charge (lbs.)
Charge (lbs.)
Charge (lbs.)
SXWF 20
24
24
SXWF 22
SXWF 25
SXWF 29
28
24
SXWF 32
30
25
SXWF 35
24
24
24
SXWF 38
25
25
25
SXWF 42
28
24
24
SXWF 46
30
25
25
SXWF 52
28
28
28
SXWF 58
30
30
30
SXWF 65
28
28
28
24
SXWF 72
30
30
30
25
SXWF 80
32
32
32
32
Table O-M-4. Air-Cooled Unit (SXRF) Refrigerant Charge
Unit Size
Circuit 1
Circuit 2
Circuit 1
Circuit 2
Charge (lbs.)
Charge (lbs.)
SXRF 20
B-10 T
A-10 T
36
36
SXRF 25, 29
B-10 T
A- 15 T
36
58
SXRF 30, 35
A-10 T, B-10 T
C-10 T
72
36
manifolded
SXRF 40
A-15 T, B-10 T
C-10 T
94
36
manifolded
SXRF 50
A-15 T, B-15 T
C-10 T
115
56
manifolded
SXRF 60
A-15 T, B-15 T
C-15 T, D-15 T
115
125
manifolded
manifolded
Содержание IntelliPak Signature SCRF-020
Страница 16: ...16 SCXF SVX01B EN 42 80Ton Self Contained Dimensions and Weights Installation...
Страница 20: ...20 SCXF SVX01B EN Airside Economizer Dimensions and Weights Installation...
Страница 89: ...SCXF SVX01B EN 89 Figure O M 9 Typical water cooled SXWF compressor section components Maintenance Owner...
Страница 107: ...SCXF SVX01B EN 107...