SCXF-SVX01B-EN
31
Pre-Startup
Requirements
Hydronic Coil Installation
Steam and Hot Water Coil
Note: The hydronic coil options are also
available factory mounted.
1. Position the coil box behind the unit
with open side facing the unit inlet.
2. An envelope containing the gasket and
mounting screws to attach the coil to
the unit ships in the bottom of the unit.
Install the pressure sensitive gasket to
the unit side of the vertical flange on the
coil box in two places.
3. Remove the six two-inch filter adapters
from filter rack when using four-inch
filters.
4. Before attaching the coil box, connect
the coil duct static pressure tube. This
must be done before the coil box is
bolted to the unit. If the unit connection
does not have a static pressure tube,
then no connection is required.
5. Apply the edge protector to the flange
on the unit. Remove knockout on the
unit filter cover and install the bushing
in the plastic bag. Run the wires through
the bushing and connect wires to the
unit.
6. After connecting wires and the static
pressure tube, raise the coil box up
against the unit and install the mounting
screws. Recommended lifting points
are at each end of the coil box.
7. Avoid routing wires over devices and
sharp edges. Use wire ties about every
12 inches to secure wires to other wire
harnesses.
8. Move the entering air temperature
sensor upsteam of the coil to ensure
proper operation.
Installation
Содержание IntelliPak Signature SCRF-020
Страница 16: ...16 SCXF SVX01B EN 42 80Ton Self Contained Dimensions and Weights Installation...
Страница 20: ...20 SCXF SVX01B EN Airside Economizer Dimensions and Weights Installation...
Страница 89: ...SCXF SVX01B EN 89 Figure O M 9 Typical water cooled SXWF compressor section components Maintenance Owner...
Страница 107: ...SCXF SVX01B EN 107...