Electrical
Requirements
Table I-ER-6. Electric Heat - Single Stage
SCWF
SCRF
Heat
200V
460V
Size
Size
Kw
Amps
Amps
20
-
18
50
21.7
22
-
18
50
21.7
25
20
18
50
21.7
29
25
23
63.8
27.7
32
29
23
63.8
27.7
35
30
27
75
32.5
38
35
27
75
32.5
42
-
31.5
87.4
37.9
46
40
31.5
87.4
37.9
52
-
39
108.3
46.9
58
50
39
108.3
46.9
65
-
48
133.2
57.7
72
-
48
133.2
57.7
80
60
48
133.2
57.7
Note: Electric heat amperage should not be considered when determining minimum circuit ampacity. The current of the
unit in the heating mode will not exceed the current of the unit in the cooling mode.
Selection Procedures
RLA = Rated Load Amps
Compressor LRA = Locked Rotor Amps
Fan Motor LRA = Locked Rotor Amps,
N.E.C. Table 430 - 150
FLA = Full Load Amps, N.E.C.
Table 430 - 150
Voltage utilization range is ±10 percent
Determination of minimum circuit
ampacity (MCA).
MCA = 1.25 x largest motor amps/VFD
amps (FLA or RLA) + the sum of the
remaining motor amps.
Determination of maximum fuse size
(MFS) and maximum circuit breaker size
(MCB).
MFS and MCB = 2.25 x largest motor
amps (FLA or RLA) + the sum of the
remaining motor amps.
For units with the dual power option,
there are two electrical circuits that need
calculations using the formulas above:
circuit #1 - fans
circuit #2 - compressors
If the rating value determined does not
equal a standard current rating of over
current protective device, use the next
lower standard rating for the marked
maximum rating.
Table I-ER-1. Number of Compressors per Unit
SCRF/SIRF
20
25 - 29
30 - 35
40
50
60
SCWF/SIWF 20 - 25
29 - 32
35 - 38
42 - 46
52 - 58
65 - 72
80
10
2
1
3
2
-
1
-
15
-
1
-
1
3
3
4
Table I-ER-2. SCWF/SIWF Compressor Electrical Data
200V
460V
575V
HP
RLA
LRA
RLA
LRA
RLA
LRA
10
33
269
14.5
117
11.5
94
15
46
409
20.5
178
16.5
143
Table I-ER-3. SCRF/SIRF Compressor Electrical Data
200V
460V
575V
HP
RLA
LRA
RLA
LRA
RLA
LRA
10
36.8
269
16.3
117
13.2
94
15
61.1
409
26
178
21.5
143
Table I-ER-4. Fan without VFD Data
200V
460V
575V
HP
FLA
LRA
FLA
LRA
FLA
LRA
5
16.1
105
6.7
46
5.4
37
7.5
25.0
152
10.8
66
8.2
54
10
32.9
193
14.2
84
11.4
66
15
44.8
290
20.3
126
16.2
102
20
61.0
373
25.0
162
20.0
132
25
74.0
469
31.0
204
24.2
162
30
87.0
552
36.0
240
28.6
192
40
113.0
718
47.8
312
38.0
246
50
NA
NA
62.0
390
49.2
312
Table I-ER-5. Fan with VFD
200V
460V
HP
FLA
LRA
FLA
LRA
7.5
29.4
152
13.9
66
10
37.9
193
17.6
84
15
51.4
290
24.8
126
20
66.5
373
31.9
162
25
91.4
469
44
204
30
91.4
552
44
240
40
116.0
718
57.1
312
50
NA
NA
68.3
390
Installation
Содержание IntelliPak Signature SCRF-020
Страница 16: ...16 SCXF SVX01B EN 42 80Ton Self Contained Dimensions and Weights Installation...
Страница 20: ...20 SCXF SVX01B EN Airside Economizer Dimensions and Weights Installation...
Страница 89: ...SCXF SVX01B EN 89 Figure O M 9 Typical water cooled SXWF compressor section components Maintenance Owner...
Страница 107: ...SCXF SVX01B EN 107...