Programming SETUP
24
PKG-SVP01E-EN
Supply Air Temp Reset Type:
Used With: Units without heat
Factory Presets: None
Possible Values: Cooling = None, Zone, OA
Cooling: ZONE
1.
Press the NEXT key until the following screen is displayed.
Supply Air Temp Reset Type:
Heating: ZONE
Used With: Units with hydronic heat
Factory Presets : None
Possible Values: Cool/Heat = None, Zone, OA
Cooling: ZONE
1.
Press the NEXT key until the following screen is displayed.
Supply Air Temp Zone Reset For Cooling:
Used With: Units when Zone Cooling Reset is
selected.
Possible Values: Cooling/Heating = Zone, OA;
Start Temp Zone = 209 OS = 70; End Temp Zone
= 210 OA = 71
Start Temp: 72 F
End Temp: 69 F
1.
Press the NEXT key until the following screen is displayed.
Supply Air Temp Outside Air Reset For Cooling:
Possible Values: Cooling/Heating = Zone, OA;
Start Temp Zone = 209 OS = 70; End Temp Zone
= 210 OA = 71
Start Temp: 90 F
End Temp: 70 F
1.
Press the NEXT key until the following screen is displayed.
Supply Air Temp Zone Reset For Cooling:
Used With: All Units when Outside Air cooling
reset is selected.
Possible Values: SAT = Zone, OA; Reset
(Zone) = 72; Reset (OA) = 72
Maximum Amount of Reset Applied:
5 F
1.
Press the NEXT key until the following screen is displayed.
Supply Air Temp Outside Air Reset For Cooling:
Used With: All Units when Outside Air cooling
reset is selected.
Possible Values: SAT = Zone, OA; Reset
(Zone) = 72; Reset (OA) = 72
Maximum Amount of Reset Applied:
5 F
1.
Press the NEXT key until the following screen is displayed.
Supply Air Temp Outside Air Reset For Heating:
Used With: All Units when Outside Air heating
reset is selected.
Factory Presets: Start = 10 F; End = 60 F
Possible Values: Start OA Temp = 73 F; End
OA Temp = 74 F
Start Temp: 10 F End Temp: 60 F
1.
Press the NEXT key until the following screen is displayed.
Supply Air Temp Zone Reset For Heating:
Used With: Units when Zone Air heating reset
is selected.
Factory Presets: Start = 65 F, End = 68 F
Possible Values: Start OA Temp = 211; End
OA Temp = 212
Start Temp: 65 F End Temp: 68 F
1.
Press the NEXT key until the following screen is displayed.
Supply Air Temp OA Reset For Heating:
Used With: All Units when Zone Heating is
selected.
Possible Values: SAT temp = Zone, OA; Zone
Reset = 75; OA Reset = 75
Maximum Amount of Reset Applied: 10 F
1.
Press the NEXT key until the following screen is displayed.
Supply Air Temp Zone Reset For Heating:
Used With: All Units when outside heating is
selected.
Possible Values: SAT temp = Zone, OA; Zone
Reset = 75; OA Reset = 75
Maximum Amount of Reset Applied: 10 F
1.
Press the NEXT key until the following screen is displayed.
VAV Box Max Stroke Time: 0 Min
Factory Presets: 6 Min
Possible Values: 0 to 10
1.
Press the NEXT key until the following screen is displayed.
Max Occupied IGV/VFD Command: 100%
Used With: Units with IGV/VFD installed
Factory Presets: 100%
Possible Values: 0 to 100%
1.
Press the NEXT key until the following screen is displayed.