Programming SETUP
PKG-SVP01E-EN
23
Morning Warmup Function: ENABLED
Morning Warmup Type: FULL CAPACITY
Used With: Units when Electric, or Hydronic
Heat is installed.
Factory Presets: Function = Enabled; MWU
Type = Full Capacity
Possible Values: Function = Enabled,
Disabled; MWU Type = Full Capacity, Cycling
Capcity
1.
Press the NEXT key until the following screen is displayed (if applicable).
Supply Air Tempering Function: DISABLED
Warm Up Outside Air Used For Ventilation
Used With: All Units when Hydronic Heat is
installed
Factory Preset: Function = Disabled
Possible Values: Function = Enabled, Disabled
1.
Press the NEXT key until the following screen is displayed.
Unocc Mech Cooling Function: ENABLED
Used With: Cooling-only units
Factory Preset: Cooling and Heating Function
= Enabled
Possible Values: Cooling and Heating Function
= Enabled, Disabled
OR
Unocc Mech Cooling Function: ENABLED
Unocc Heating Function: ENABLED
Used With: All Units with electric, hydronic, or
external heat is installed
Factory Presets: Cooling & Heating =Enabled
Possible Values: Cooling & Heating = Enabled,
Disabled
1.
Press the NEXT key until the following screen is displayed (if applicable).
OA Preheater Output Control: ENABLED
Activate If Preheat Temp Below SETPOINT
Used With: Units with VCM installed
Factory Preset: Control = Disabled
Possible Values: Control = Enabled, Disabled
1.
Press the NEXT key until the following screen is displayed
Demand Limit Definition:
Cooling: 100%
Factory Presets: None
Possible Values: Cooling = None, 50 or 100%
1.
Press the NEXT key until the following screen is displayed.
Demand Limit Definition:
Used With: Units Electric or Hydronic heat.
Factory Presets: None
Possible Values: Cooling/Heating: None, 50 or
100%
Cooling: 100%
Heating: 100%
1.
Press the NEXT key until the following screen is displayed.
Compressor Lead/Lag Function: DISABLED
Vary Staging Order To Distribute Runtime
Factory Preset: Function = Disabled
Possible Values: Function = Enabled, Disabled
1.
Press the NEXT key until the following screen is displayed.
Reduce Multi-Unit Startup Power Demand
After Power-Up, Delay Unit Start:
0 Sec
Factory Preset: Start = 0 Seconds
Possible Values: Start = 0-255 Seconds
1.
Press the NEXT key until the following screen is displayed (if applicable).
Coil Frost Cutout Temperature:
Compressors If Evap Temp Is Below:
Shut off
30 F
Factory Preset: 30 F
Possible Values: 25 F to 35 F
1.
Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP
1.
Press the NEXT key to leave the submenu and show following screen.
VAV Control Functions Submenu
Press ENTER to Review or Adjust
1.
Press the NEXT key until the following screen is displayed.