Programming Status
16
PKG-SVP01E-EN
WSM Ent Cond Water Temp Input
Low Water Temp Compressor Lockout
65.2 F
34 F
Used With: All water-cooled units only.
Possible Lockout Values: Lockout Temperature =
0 - 99 F
1.
Pressing the NEXT key will scroll forward through the screens.
Compressor Module Ckt 1
Evap Temp 75.0 F
Sat Cond Temp 81.0 F
1.
Press the NEXT key until the following screen is displayed. (if applicable)
Compressor Module Ckt 2
Evap Temp 72.0 F
Sat Cond Temp 97. 0F
1.
Press the NEXT key until the following screen is displayed.
Compressor Module Ckt 3
Used With: All SCWF/SIWF 35-80 ton units only.
Evap Temp 72.0 F
Sat Cond Temp 97 .0 F
1.
Press the NEXT key until the following screen is displayed.
Compressor Module Ckt 4
Used With: All SCWF/SIWF 60-80 ton units only.
Evap Temp 72.0 F
Sat Cond Temp 97 .0 F
1.
Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP
1.
Press the NEXT key until the following screen is displayed.
Economizer Status Submenu
Used With: Units with a waterside or airside
economizer only.
Press ENTER to View Data in This Submenu
1.
Press the NEXT key until the following screen is displayed.
Water Economizing: DISABLED
Used With: Units with a waterside economizer only.
Possible Values: Economizer = Disable, enable;
Water econ position - opening to/closing to 0-100%
Outside Air Damper Pos:
10%
1.
Press the NEXT key until the following screen is displayed.
WSM Mixed Air Temperature:
68 F
Used With: Units with a waterside economizer or
condenser only.
WSM Entering Water Temperature:
60 F
1.
Pressing the NEXT key will scroll forward through the screens.
Water Econ Bpass Pos:
10%
Used With: Units with a waterside economizer and
condenser only.
1.
Pressing the NEXT key will scroll forward through the screens.
Air Economizing: DISABLED
Used With: Units with an airside economizer only.
Possible Values: Economizer = Disable, enable;
Outside air = opening to/closing to 0-100%
Outside Air Damper Pos:
0%
1.
Pressing the NEXT key will scroll forward through the screens.
Active Outside Air Enthalpy
12.0 BTU/LB
Used With: Units with an airside economizer and
comparative enthalpy only.
Possible Values: 10-99 BTU/LB
ECEM Return Air Enthalpy
34.0 BTU/LB
1.
Pressing the NEXT key will scroll forward through the screens.
Active Outside Air Temperature
86.0 F
Used With: Units with an airside economizer only.
ECEM Return Air Temperature
78.0 F0
1.
Pressing the NEXT key will scroll forward through the screens.