54
RT-SVX36G-EN
Installation
2. Using two #10-32 x 1-3/4” screws provided, install the sensor's mounting bracket to the factory
installed bracket (near the filter section).
3. Using the #10-32 x 1/2” screws provided, install the O/A static pressure sensor vertically to the
sensor bracket.
4. Remove the dust cap from the tubing connector located below the sensor in the vertical
support.
5. Attach one end of the 50' x 3/16” O.D. factory provided pneumatic tubing to the sensor's top
port, and the other end of the tubing to the connector in the vertical support. Discard any excess
tubing.
Units with Statitrac:
6. Open the filter access door, and locate the DSP control devices illustrated in
. There
are three tube connectors mounted on the left of the solenoid and transducers. Connect one
end of the field provided 3/16” O.D. pneumatic tubing for the space pressurization control to
the bottom fitting. Route the opposite end of the tubing to a suitable location inside the building.
This location should be the largest open area that will not be affected by sudden static pressure
changes.
Remove Evaporative Condenser Fan Shipping Brackets
To remove shipping brackets
Important:
Remove fan shipping brackets before startup. Failure to remove brackets could result
in fan damage.
Evaporative condensers are shipped with fan shipping brackets to reduce damage caused by
vibration during shipment. The fan shipping brackets must be removed prior to unit startup.
To remove the shipping brackets start from the side opposite to the drain actuator
(see
1.
Loosen the screw for the bracket that holds the inlet louvers below the door side.
2. Remove inlet louvers and set to the side.
Note:
Service technician may need to step on the horizontal surface of FRP coated base.
Step with care.
3. Unscrew the bolt in the middle of the door. Keep the bolt in a safe place.
4. Lift one door with handle until it touches the top. Swivel bottom of door to remove it from the
door opening and set it to the side.
5. Slide and remove the middle mist eliminator section so that the shipping bracket is visible.
6. Use screw gun to unscrew the two screws that hold the fan shipping bracket. The bracket should
drop down but still remain engaged with a hook on the bracket.
7.
Go to the other side of the unit and follow the procedure for inlet louver and door removal
(see steps 1 - 6).
8. Hold the bracket with one hand and remove remaining two screws.
9. Remove the bracket and all the removed screws from the unit.
Important:
Make sure there are no screws remaining in the coil area.
10. Reinstall inlet louvers, mist eliminators and louvers.
Check that the direction of arrow on the inlet louver is correct.
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...