RT-SVX36G-EN
45
Installation
If a Trane Curb Accessory Kit is Not Used:
a. The ductwork can be attached directly to the factory-provided flanges around the unit’s
supply and return air openings. Be sure to use flexible duct connections at the unit.
b. For “built-up” curbs supplied by others, gaskets must be installed around the curb perimeter
flange and the supply and return air opening flanges.
Notes:
•
If a “built-up” curb is provided by others, keep in mind that these commercial rooftop units do
not have base pans in the condenser section.
•
If this is a REPLACEMENT UNIT keep in mind that the CURRENT DESIGN commercial rooftop
units do not have base pans in the condenser section.
•
Trane roof curbs are recommended. If using a non-Trane roof curb with right-angle return
airflow approaches to a return fan inlet, a rigid, solid flow baffle wall should be installed across
the full width of the roof curb return airflow path in the position shown in
reduce potential airflow disturbances at the return fan inlet that could contribute to unusual
return fan noise.
Figure 14. Pitch pocket location
Table 15. Pitch pocket dimensions
Unit
Tonnage
“A” Dimension "B" Dimension
S*HL
20, 25 & 30
4' 5-9/16"
5-9/16"
S*HL
24, 29, & 36
6' 9-11/16”
5-1/2”
S*HL
40 - 89
9' 5-11/16"
5-1/2"
* = All unit functions (SAHL, SEHL, SFHL, SSHL, SLHL and SXHL)
Notes:
For design special evaporative-cooled condensing units, please
see the curb installers guide for proper pitch pocket locations.
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...