RT-SVX36G-EN
119
Unit Start Up
Fan Performance Tables
Figure 49. 20 & 25 / 24 & 29 Ton supply fan performance
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
0
2000
4000
6000
8000
10000
12000
14000
16000
18000
20000
CFM
STATIC PRESSURE, Inches w
.c.
40% w
ocfm
50%
60%
S_HL*20 & 25, 24 & 29 Ton
Dual 15 X 15 Fans
Entrance Losses
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust Fan
Fan Curve Limits
- Minimum Motor HP = 3
- Maximum Motor HP
C20 & C25 = 15 HP
- Maximum RPM
3 HP - 5 HP = 1100
7.5 HP - 15 HP = 1655
- Maximum CFM
C20 = 9,000
C25 = 11,000
- Maximum Static Pressure
Leaving the Unit = 4.0" w.c.
90%
80%
70%
1700 RPM
1600 RPM
1500 RPM
1400 RPM
1300 RPM
1200 RPM
1100 RPM
1000 RPM
900 RPM
800 RPM
700 RPM
600 RPM
500 RPM
15 HP
10 HP
7.5 HP
5 HP
3 HP
20 HP
Figure 50. 30/36 ton supply fan performance
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
0
2000
4000
6000
8000
10000
12000
14000
16000
18000
20000
CFM
STATIC PRESSURE, Inches w.c.
1400 R P M
800 R P M
900 R P M
1000 R P M
1100 R P M
1200 R P M
1300 R P M
600 R P M
700 R P M
500 R P M
S_HL* 30/36 Ton
Dual 18 X 18 Fans
Entrance Losses
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust
Fan Curve Limits
- Minimum Motor HP = 5
- Maximum Motor HP = 20
- Maximum RPM = 1379
- Maximum CFM = 13,500
- Maximum Static Pressure
Leaving the Unit = 4.0" w.c.
5 HP
7.5 HP
10 HP
25 HP
15 HP
20 HP
3 HP
40%
w
o
c
fm
50%
60%
80%
90% wocfm
70%
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...