58
RT-SVX063E-EN
Direct-Drive Supply Fan Speed
Adjustment
Units equipped with a DDP Supply Fan do not use belt/
sheave arrangements to adjust fan speed.
This adjustment (if required) is made through the Fan
VFD by setting the supply fan Min/Max frequency at
each supply fan VFD using
Table 23, p. 58
.
Table 23.
RPM and Hz ranges for DDP supply fan
speed adjustments
Fan Speed (RPM)
VFD Frequency Range (Hz)
Max
Min
Max
Min
2400
888
83
31
2300
851
79
29
2200
814
76
28
2100
777
72
27
2000
740
69
26
1900
703
66
24
1800
666
62
23
1700
629
59
22
1600
592
83
31
1500
555
79
29
1400
518
74
27
1300
481
68
25
1200
444
63
23
Table 23.
RPM and Hz ranges for DDP supply fan
speed adjustments (continued)
Fan Speed (RPM)
VFD Frequency Range (Hz)
Max
Min
Max
Min
1100
407
58
21
1000
370
53
20
N
No
otte
e:: Maximum operating speed cannot exceed fan
wheel mechanical limit.
System Airflow Measurements
VAV and CV Systems with DDP Supply
Fan and Motorized Impeller Relief Fan
(optional)
Supply and Relief Airflow Measurement
Piezometer pressure taps are available to measure
supply and relief airflow. Piezometer pressure taps can
interface with customer-supplied airflow monitoring
systems using the F or K-factors and equation shown in
the tables below. Attach one end of the pressure
differential gauge to a connection in the fan cone
throat, and the second to the fan inlet plate to read
pressure immediately upstream of the fan.
Table 24.
Piezo airflow calculation
Unit
Fan
dia, in
F
C1
A
20,25,30
16.5
1518.6
753.06
0.55
40,50,55
18.2
1821.9
692.03
0.72
20,25,30,-
40,50,55
20
2185.8
692.03
0.87
20,25,30,-
60,70,75
22.2
2713.9
692.03
1.07
40,50,55
24.5
3285
692.03
1.3
60,70,75
27
3397.6
692.03
1.58
Notes:
1
.
Measure pressure from inlet side of fan to piezo
tap at the cone throat.
2
.
Fan inlet will be the high pressure side.
3
.
dP can be up to 25 in h
2
0.
4
.
Coefficients are for one fan. For two fans double
result or F and C1 values.
5
.
For standard density of 0.075 lb/ft^3, Supply Fan
CFM = CFM = F * √ dP
6
.
For non-standard density, Supply Fan CFM = CFM
= C1 * A * √ (dP / ρ), where dP is the piezo
pressure differential and rho is the actual air
density.