Unit Nameplate
One Mylar unit nameplate is located on the outside
upper left corner of the control panel door. It includes
the unit model number, serial number, electrical
characteristics, refrigerant charge, unit wiring diagram
numbers, as well as other pertinent unit data. A small
metal nameplate with the Model Number, Serial
Number, and Unit Weight is located just above the
Mylar nameplate, and a third nameplate is located on
the inside of the control panel door.
Compressor Nameplate
The Nameplate for the Scroll Compressor is located on
the compressor lower housing. Max amps is listed on
the nameplate and is the absolute highest amp load on
the compressor at any operating condition (does not
include locked rotor amps or inrush). This value should
never be exceeded.
Gas Heat Nameplate
The nameplate for the Gas Heater is located on the
inside of the gas heat enclosure. Allowable operating
values of Min and Max input rate, manifold pressure,
and air rise for the heater is listed on the nameplate.
Unit Description
Each single-zone rooftop air conditioner ships fully
assembled from the factory. An optional roof curb,
specifically designed for the units is available from
Trane. The roof curb kit must be field assembled and
installed according to the latest edition of the roof curb
installation manual.
Trane Commercial Rooftop Units are controlled by a
Symbio 800 control system that consists of a network
of modules and are referred to as Low Level Intelligent
Devices (LLID). The acronym (LLID) is used extensively
throughout this document when referring to the control
system network. These modules through Proportional/
Integral control algorithms perform specific unit
functions which provide the best possible comfort level
for the customer.
They are mounted in the control panels and are factory
wired to their respective internal components. They
receive and interpret information from other unit
modules, sensors, remote panels, and customer binary
contacts to satisfy the applicable request for
economizing, mechanical cooling, heating, and
ventilation.