Table 24.
Electrical service sizing data — dual DDP supply fan motors WITHOUT bypass option — 60 to 75 tons
200 V
230 V
460 V
575 V
MOC
MOC
MOC
MOC
Motor Horsepower
2x Supply Fan Motors (4 pole)
2x 7.5HP
41.5
35.6
17.8
14.2
2x 10HP
53.6
45.8
22.9
18.4
2x 15HP
78.2
65.5
32.7
27.3
2x 20HP
N/A
N/A
44.9
35.5
2x 25HP
N/A
N/A
55.5
45.1
Motor Horsepower
2x Supply Fan Motors (6 pole)
2x 5HP
30.9
26.9
13.5
10.2
2x 7.5HP
45.5
40.0
20.0
16.4
2x 10HP
58.2
52.0
26.0
21.6
2x 15HP
85.5
74.5
37.3
29.6
Notes:
1
.
MOC (Max Operating Current) is VFD Input Current when fan motors are
operating at FLA
2
.
MOC for dual DDP supply fans without bypass represents the total VFD input
current for both supply fan motors.
3
.
Dual DDP fans selected under 1,700 RPM will have 6-pole motors
Table 25.
Electrical service sizing data —electric heat module (electric heat units only) — 20 to 130 tons
Module
kW
Electric Heat FLA
200V
230V
460V
575V
30
83.3
72.2
36.1
28.9
50
138.8
120.3
60.1
48.1
70
194.3
168.4
84.2
67.4
90
249.8
216.5
108.3
86.6
110
305.3
264.6
132.3
105.9
130
-
-
156.4
125.1
150
-
-
180.4
144.3
170
-
-
204.5
163.6
190
-
-
228.5
182.8
Note:
Electric heat FLA are determined at 208, 240, 480 and 600
volts.
Table 26.
Voltage utilization range
Unit Voltage
Voltage Utilization Range
200/60/3
180-220
230/60/3
207-253
460/60/3
414-506
575/60/3
517-633
Field Installed Control Wiring
The IntelliPak rooftop has many operating modes. The
flexibility of having several system modes depends
upon the type of sensor and/or remote panel selected
to interface with the Symbio 800. An overall layout of
the various control options available for a Single Zone
application, with the required number of conductors for
each device, is illustrated beginning with .
illustrates the various control options with the
required number of conductors for a Variable Air
Volume application.
N
No
otte
e:: All field wiring must conform to NEC guidelines
as well as state and local codes.
W
WA
AR
RN
NIIN
NG
G
H
Ha
azza
arrd
do
ou
uss V
Vo
olltta
ag
ge
e!!
F
Fa
aiillu
urre
e tto
o d
diisscco
on
nn
ne
ecctt p
po
ow
we
err b
be
effo
orre
e sse
errv
viicciin
ng
g cco
ou
ulld
d
rre
essu
ulltt iin
n d
de
ea
atth
h o
orr sse
erriio
ou
uss iin
njju
urry
y..
D
Diisscco
on
nn
ne
ecctt a
allll e
elle
eccttrriicc p
po
ow
we
err,, iin
nccllu
ud
diin
ng
g rre
em
mo
otte
e
d
diisscco
on
nn
ne
eccttss b
be
effo
orre
e sse
errv
viicciin
ng
g.. F
Fo
ollllo
ow
w p
prro
op
pe
err
llo
occkko
ou
utt//tta
ag
go
ou
utt p
prro
occe
ed
du
urre
ess tto
o e
en
nssu
urre
e tth
he
e p
po
ow
we
err
cca
an
n n
no
ott b
be
e iin
na
ad
dv
ve
errtte
en
nttlly
y e
en
ne
errg
giizze
ed
d.. V
Ve
erriiffy
y tth
ha
att n
no
o
p
po
ow
we
err iiss p
prre
esse
en
ntt w
wiitth
h a
a v
vo
ollttm
me
ette
err..
Содержание IntelliPak 1
Страница 134: ...134 RT SVX072A EN Figure 108 Dry bulb changeover map T Tr ra an ne e S St ta ar rt tu up p C Ch he ec ck kl li is st t ...
Страница 161: ...RT SVX072A EN 161 N No ot te es s ...
Страница 162: ...162 RT SVX072A EN N No ot te es s ...
Страница 163: ...RT SVX072A EN 163 N No ot te es s ...