120
RT-SVX072A-EN
Table 53.
Minimum starting temperatures for air-
cooled units
Unit
Size
Minimum Starting Ambient
Low Ambient
Standard
(a)
with HGBP
without HGBP
20 & 40
55°
10°
0°
25 & 30
50°
10°
0°
50, 55
35°
10°
0°
60
30°
10°
0°
70-130
45°
10°
0°
Note:
Min. starting ambients in °F and is based on unit operating
at min. step of unloading and 5 mph wind across condenser.
(a)
With or without HGBP
Standard Ambient Condenser Fans
Standard ambient units stage condenser fans down to
a minimum of one fan per circuit. All standard ambient
units ship with the Symbio
™
controller set to allow
mechanical cooling down to 50°F outdoor temperature.
This setting is adjustable. Below table lists the
minimum recommended mechanical cooling setting
for standard ambient units by application and unit type.
Table 54.
Minimum outside air temperature
Standard Unit Minimum
Outside Air Temperature for
Mechanical Cooling
Std &
High Cap
units
eFlex
™
™
units
20, 60,
70, 75
ton
25, 30,
40, 50,
55 ton
Economizer - A/C Applications
45°F
45°F
50°F
No Economizer - 80/67F design
return air
45°F
45°F
55°F
No Economizer - 90/78F design
return air
50°F
50°F
70°F
Low Ambient Condenser Fans
When a unit is ordered with the low ambient option (i.
e., Digit 19 is a “1” in the model number), it can affect
the selection of condenser fan motors. Please see the
table below and
“Compressor Blink Codes,” p. 115
to
see which fan motors will be variable speed.
Low Ambient Variable Speed
Condenser Fans
Ton-
nage
Efficiency
Tier
Circuit 1
Circuit 2
20
Std. & High
2M6
-
eFlex
All
-
25
Std.
2M6
-
High & eFlex
All
-
Low Ambient Variable Speed
Condenser Fans
Ton-
nage
Efficiency
Tier
Circuit 1
Circuit 2
30
Std. & High
2M6
-
eFlex
All
-
40
Std.
2M6
2M9
High & eFlex
All
All
50
Std.
2M6
2M9
High & eFlex
All
All
55
Std.
2M6
2M9
High & eFlex
All
All
60
Std. & High
2M6
2M9
eFlex
All
All
70
Std. & High
2M6
2M9
eFlex
All
All
75
Std. & High
2M6
2M9
eFlex
All
All
90
Any
2M6
2M9
105
Any
2M6
2M9
115
Any
2M6
2M9
130
Any
2M6
2M9
Electric, Steam and Hot Water
Start-Up
(Variable Air Volume Systems)
1. Ensure that the “System” selection switch at the
remote panel is in the Off position.
2. Close the disconnect switch or circuit protector
switch that provides the supply power to the unit
terminal block (1TB1) or the unit-mounted
disconnect switch (1S14).
W
WA
AR
RN
NIIN
NG
G
H
Ha
azza
arrd
do
ou
uss V
Vo
olltta
ag
ge
e!!
F
Fa
aiillu
urre
e tto
o d
diisscco
on
nn
ne
ecctt p
po
ow
we
err b
be
effo
orre
e sse
errv
viicciin
ng
g cco
ou
ulld
d
rre
essu
ulltt iin
n d
de
ea
atth
h o
orr sse
erriio
ou
uss iin
njju
urry
y..
D
Diisscco
on
nn
ne
ecctt a
allll e
elle
eccttrriicc p
po
ow
we
err,, iin
nccllu
ud
diin
ng
g rre
em
mo
otte
e
d
diisscco
on
nn
ne
eccttss b
be
effo
orre
e sse
errv
viicciin
ng
g.. F
Fo
ollllo
ow
w p
prro
op
pe
err
llo
occkko
ou
utt//tta
ag
go
ou
utt p
prro
occe
ed
du
urre
ess tto
o e
en
nssu
urre
e tth
he
e p
po
ow
we
err
cca
an
n n
no
ott b
be
e iin
na
ad
dv
ve
errtte
en
nttlly
y e
en
ne
errg
giizze
ed
d.. V
Ve
erriiffy
y tth
ha
att n
no
o
p
po
ow
we
err iiss p
prre
esse
en
ntt w
wiitth
h a
a v
vo
ollttm
me
ette
err..
Содержание IntelliPak 1
Страница 134: ...134 RT SVX072A EN Figure 108 Dry bulb changeover map T Tr ra an ne e S St ta ar rt tu up p C Ch he ec ck kl li is st t ...
Страница 161: ...RT SVX072A EN 161 N No ot te es s ...
Страница 162: ...162 RT SVX072A EN N No ot te es s ...
Страница 163: ...RT SVX072A EN 163 N No ot te es s ...