![Trane GXAA Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/trane/gxaa/gxaa_installation-operation-and-maintenance-manual_1149991039.webp)
MUA-SVX006B-EN
39
•
It is recommended that air filters be changed or cleaned at least four times a year. More
frequent attention to filters is required if the air being handled by the unit is unusually dirty.
Air flow reduction, caused by the dirty air filters, will increase the discharge air temperature
and may cause unit cycling on the primary limit.
•
Filters (by others) should be serviced regularly and changed or washed when necessary to
maintain the required air throughput. In a dusty environment, filters may clog up in less than
one month.
Table 2. Standard CFM Blower Air Filter Size Requirements
Unit Input
Number of Filters
Required
Figure 22.
Standard CFM Blower
A
A
16 x 20 (in)
20 x 20 (in)
100 MBtuh (29.3 kW)
4
150 MBtuh (44.0 kW)
4
200 MBtuh (58.6 kW)
4
250 MBtuh (73.2 kW)
4
300 MBtuh (87.9 kW)
4
2
350 MBtuh (102.6 kW)
4
2
400 MBtuh (117.2 kW)
6
500 MBtuh (146.5 kW)
4
600 MBtuh (175.8 kW)
4
2
700 MBtuh (205.1 kW)
4
2
800 MBtuh (234.4 kW)
6
Table 3. High CFM Blower Air Filter Size Requirements
Unit Input
Number of Filters
Required
Figure 23.
High CFM Blower
A
B
16 x 20 (in)
20 x 20 (in)
100 MBtuh (58.6 kW)
8
150 MBtuh (58.6 kW)
8
200 MBtuh (58.6 kW)
8
250 MBtuh (73.2 kW)
8
300 MBtuh (87.9 kW)
8
4
350 MBtuh (102.6 kW)
8
4
400 MBtuh (117.2 kW)
12
500 MBtuh (146.5 kW)
8
600 MBtuh (175.8 kW)
8
4
700 MBtuh (205.1 kW)
8
4
800 MBtuh (234.4 kW)
12
1,200 MBtuh (351.6kW)
12
Air Blower
B
Be
elltt T
Te
en
nssiio
on
n A
Ad
djju
ussttm
me
en
ntt
Содержание GXAA
Страница 16: ...16 MUA SVX006B EN Figure 7 Flexible Connector Kit Install I In ns st ta al ll la at ti io on n...
Страница 17: ...MUA SVX006B EN 17 Figure 8 Flexible Connector Kit Install I In ns st ta al ll la at ti io on n...
Страница 18: ...18 MUA SVX006B EN Figure 9 Flexible Connector Kit Install I In ns st ta al ll la at ti io on n...
Страница 19: ...MUA SVX006B EN 19 Figure 10 Flexible Connector Kit Install I In ns st ta al ll la at ti io on n...
Страница 48: ...48 MUA SVX006B EN Dimensional Data Arrangements Indoor Arrangement A Capacity 50 80...
Страница 55: ...MUA SVX006B EN 55 Motor Electric Data Table 4 Full Load Current in Amperes...
Страница 58: ...58 MUA SVX006B EN Coil Cabinet Dimensional Data Figure 25 Coil Cabinet Dimensional Data...
Страница 62: ...62 MUA SVX006B EN Gas Equipment Start Up...
Страница 63: ...MUA SVX006B EN 63 N No ot te es s...