background image

Installation

GUNE-SVX001A-EN

17 

Additional Requirement for Canadian 
Installations

Refer to specification table and installation manual for 
proper usage.

The following instructions apply to Canadian installations 
in addition to installation and operating instructions.

1.

Installation must conform with local building codes, or 
in the absence of local codes, with current CSA B149.1, 
Installation Codes for Natural Gas Burning Appliances 
and Equipment, or CSA B149.2, Installation Codes for 
Propane Gas Burning Appliances and Equipment.

2. Any reference to U. S. standards or codes in these 

instructions are to be ignored, and the applicable 
Canadian standards or codes applied.

Vertically Vented Duct Furnaces 
(Category III)

Observe the following precautions when venting the unit: 

1.

Use flue pipe of the same size as the flue connections 
on the gas duct furnace (see 

Table 1, p. 8

). All heater

should be vented with UL Listed (UL 1738 in United 
States, UL S636 in Canada) double wall or single wall 
vent pipe, a factory built chimney, or a lined brick and 
mortar chimney that has been constructed in 
accordance with the National Building Code.

2. Provide as long a vertical run of flue pipe at the duct 

furnace as possible. A minimum of 5 feet (1.5 m) of 
vertical flue is required. The top of the vent pipe should 
extend at least 2 feet (0.61 m) above the highest point 
on the roof. Install a weather cap over the vent 
opening; cap should be a Breidert Type L or Fields 
Starkap vent cap. Consideration should be made for 
anticipated snow depth. Se

Figure 9, p. 19

.

3. Slope horizontal runs upward from the duct furnace at 

least 1/4 inch per foot (21 mm/m) minimum. Horizontal 
runs should not exceed 75 percent of the vertical 
height of the vent pipe, or chimney, above the flue pipe 
connections, up to a maximum length of 10 feet (3 m). 
Horizontal portions of the venting system shall be 
supported at minimum intervals of 4 feet (1.2 m) in the 
United States, and at minimum intervals of 3 feet (1 m) 
in Canada. Se

Figure 9, p. 19

.

4. Use as few elbows as possible.

5. Avoid running vent pipe through unheated spaces.

6. When this cannot be avoided, insulate the pipe to 

prevent condensation of moisture on the walls of the 
pipe.

7.

Do not damper the flue piping. Failure to open such 
damper prior to operating the duct furnace will result 
in the spillage of flue gas into the occupied space.

8. Avoid installing units in areas under negative pressure 

due to large exhaust fans or air conditioning. When 
required, a flue vent fan should be installed in 
accordance with the instructions included with the fan.

9. Vent connectors serving Category I and Category II 

heaters shall not be connected into any portion of 
mechanical draft systems operating under positive 
pressure.

Horizontally Vented Duct Furnaces 
(Category III)

Observe the following precautions when venting the unit: 

1.

Horizontal venting arrangements are designed to be 
used with single wall or double wall vent pipe. 
Horizontal venting arrangements must terminate 
external to the building using UL 1738 vent pipe in the 
United States. For installations in Canada, use vent 

Table 7.

Vent systems termination clearance requirements

Structure/Object

Minimum Clearance for Termination Locations

USA

CANADA

Door, window, or gravity vent inlet; 
combustion air inlet for other appliances

9 in. for 10,000 to 50,000 Btu/h input; 

12 inches for input exceeding 50,000 Btu/h

9 inches (230mm) for 10,000 to 50,000 Btu/h input; 
12 inches (305mm) for input exceeding 50,000 Btu/h

Forced air inlet within 10 feet

3 feet above

6 feet (1.8 m)

Adjoining Building or parapet

10 feet

10 feet (3.04 m)

Adjacent public walkways

7 feet above grade

7 feet (2.1 m) above grade

Electric, gas meters & regulators

4 feet horizontal

3 feet (0.9 m) horizontally from meter/regulator 

assembly. 6 feet (1.8 m), any direction, from a gas 

service regulator vent outlet

Above grade level

(a)

1 foot

1 foot (0.3 m)

(a) Minimum above maximum snow depth, or per local code, whichever is greater.

WARNING

Important Safety Precautions!

Failure to follow instructions below could result in 
death, serious injury, and property damage.

WARNING

Important Safety Precautions!

Failure to follow instructions below could result in 
death, serious injury, and property damage.

Содержание GUNE

Страница 1: ...c knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in th...

Страница 2: ...and your local state electrical codes WARNING Personal Protective Equipment PPE Required Installing servicing this unit could result in exposure to electrical mechanical and chemical hazards Before in...

Страница 3: ...lane hangars when installed in accordance with current ANSI NFPA No 409 and in public garages when installed in accordance with current NFPA No 88A and NFPA No 88B If installed in Canada the installat...

Страница 4: ...e service panel and the heater To ensure a proper ground the grounding means must be tested by a qualified technician Do not insert fingers or foreign objects into the heater or its combustion air mov...

Страница 5: ...de 12 Gas Pipe Sizing 13 Pipe Sizing 13 Pipe Installation 14 Venting 16 Venting for Power Vented Duct Furnaces Category III 16 Vertically Vented Duct Furnaces Category III 17 Horizontally Vented Duct...

Страница 6: ...nic Modulating w Room Sensing J Electronic Modulating w Duct Thermostat L Electronic Modulation w External 4 20 mA Input M Electronic Modulation w External 0 10 Vdc Input T Single Stage Direct Spark I...

Страница 7: ...t Furnace is a factory assembled power vented and low static pressure type duct furnace with a low profile cabinet The duct furnace can also be easily field converted to separated combustion The desig...

Страница 8: ...33 5 33 5 33 5 831 831 831 851 851 851 851 F Flue Size Diameter 5 5 5 6 6 6 6 127 127 127 152 152 152 152 G Air Inlet Size Diameter 5 5 5 6 6 6 6 127 127 127 152 152 152 152 Gas Inlet Natural Gas inc...

Страница 9: ...ations between 0 and 2 000 feet 610m 2 For unit installations in U S A above 2 000 feet 610 m the unit input must be field derated 4 percent for each 1 000 feet 305 m above sea level refer to local co...

Страница 10: ...by a partition not less than 18 inches 457 mm high Refer to the latest edition of NFPA 88A Parking Structures In Canada installation must be in accordance with the latest edition of CSA B149 Installat...

Страница 11: ...ibration Air Flow The installation is to be adjusted to obtain an air throughput within the range specified on the appliance rating plate Combustion Inlet Air Ventilation Inlet Air From Another Room I...

Страница 12: ...reen and block off plate locations once the unit has been flipped However due to combustion noise it is recommended to keep the air inlet screen on top for overhead installations Important If unit acc...

Страница 13: ...on for use with propane bottled gas must be made by a qualified LP gas dealer or installer He She will ensure that proper joint compounds are used for making pipe connections that air is purged from l...

Страница 14: ...ze in Internal Diameter in Length of Pipe feet meters 10 20 30 40 50 60 70 80 90 100 125 150 175 200 3 0 6 1 9 1 12 2 15 2 18 3 21 3 24 4 27 4 30 5 38 1 45 7 53 3 61 0 1 2 0 622 175 120 97 82 73 66 61...

Страница 15: ...Damage Do not over tighten the inlet gas piping into the valve This may cause stresses that will crack the valve Figure 8 Pipe installation standard controls Table 5 Gas supply pressure a a Applicabl...

Страница 16: ...rom the venter outlet before installing an elbow in the vent system An elbow should never be attached directly to the venter Any run of single wall vent pipe exposed to cold air or passing through an...

Страница 17: ...ew elbows as possible 5 Avoid running vent pipe through unheated spaces 6 When this cannot be avoided insulate the pipe to prevent condensation of moisture on the walls of the pipe 7 Do not damper the...

Страница 18: ...sance or hazard or could be detrimental to the operation of regulators relief valves or other equipment Figure 10 p 19 and Table 7 p 17 for vent terminal height and snow consideration requirements 6 T...

Страница 19: ...Vertical Flue Height 1 4 per foot Min Slope 21 mm m Thimble Roof Use Insulated Stack Outdoors Approved Vent Terminal Figure 10 Horizontally vented Category III standard combustion D9378B Condensate Dr...

Страница 20: ...ameter stated in these instructions 5 Long runs of single wall combustion air piping passing through an unheated space may require insulating if condensation becomes noticeable 6 The combustion air sy...

Страница 21: ...stems longer than 5 feet 1 5 m the system must be supported from overheard building structures at 4 feet 1 22 m maximum intervals in the United States and at 3 feet 1 m maximum intervals in Canada 9 T...

Страница 22: ...Leg and Cleanout Cap Roof Flashing Breidert Type L or Fields Approved Terminal 10 ft 3 04m Min to Wall or Adjoining Building 2 ft 609m Min Plus Max Snow Depth for Area 3 ft 1m Min Plus Max Snow Depth...

Страница 23: ...Installation GUNE SVX001A EN 23 Figure 14 Vertical arrangement single wall vent system to single wall termination Figure 15 Horizontal arrangement single wall vent system to single wall termination...

Страница 24: ...Installation 24 GUNE SVX001A EN Figure 16 Vertical arrangement single wall vent system to double wall termination Figure 17 Horizontal arrangement single wall vent system to double wall termination...

Страница 25: ...Outside walls or areas where drafts may affect the operation of the control 2 Hot Areas Areas where the sun s rays radiation or warm air currents may affect the operation of the control 3 Dead Areas A...

Страница 26: ...al Connections 26 GUNE SVX001A EN Figure 21 Tubular duct furnaces equipped with natural gas or propane LP gas single stage Figure 22 Tubular duct furnaces equipped with natural gas or propane LP gas t...

Страница 27: ...mperature of the space being heated The thermostat must be mounted on a vertical vibration free surface free of air currents and in accordance with the furnished instructions also refer to Electrical...

Страница 28: ...ust be maintained for proper operation of the duct furnace If the duct furnace is equipped with a pressure regulator on the combination gas valve follow Step 1 through Step 4 above If the duct furnace...

Страница 29: ...2 2292 96 3 001 4 000 916 1 220 2 9 722 8 4 2092 92 4 001 5 000 1 221 1 525 2 7 673 7 7 1918 88 5 001 6 000 1 526 1 830 2 4 598 7 0 1744 84 6 001 7 000 1 831 2 135 2 2 548 6 4 1594 80 7 001 8 000 2 1...

Страница 30: ...owed when the equipment was installed Have all field installed controls been installed Do you understand all the controls on this equipment If not contact your wholesaler or rep DO NOT START this equi...

Страница 31: ...ir inlet for blockage debris Clear if any found 7 Reassemble the duct furnace by replacing all parts in reverse order 8 Complete the appropriate unit start up procedure as given in the Operation secti...

Страница 32: ...lar duct furnace component index 1 Vestibule panel tube assembly heat exchanger 2 Manifold 3 Manifold bracket sub assembly 4 Inshot burner 5 Burner orifice 6 Gas valve 7 Gas inlet pipe 8 Gas inlet gro...

Страница 33: ...nd the following information to your local representative if further assistance is needed contact the manufacturer s customer service department Unit number Serial number Part description and number a...

Страница 34: ...logged main burners Clean main burner ports Misaligned orifices Replace manifold assembly Insufficient combustion air Refer to Clearances p 10 and Venting p 16 to ensure unit is properly mounted and v...

Страница 35: ...inal strip R and W Shorted circuit Check thermostat circuit for shorts or any staples piercing wires Defective thermostat If thermostat is calling after set point has been satisfied replace Defective...

Страница 36: ...or 24 V on terminals R and W1 on terminal strip Loose wiring or connection Check all wiring in the power vent circuit to ensure good connection including neutral Motor overload protection is tripping...

Страница 37: ...tus Indicates Check Repair Slow Flash Control OK no call for heat Not Applicable Fast Flash Control OK call for heat present Not Applicable Steady Off Internal control fault or no power 1 Line voltage...

Страница 38: ...drocarbons precipitated in the air to any workmanship of the installer of the Product This limited warranty is conditional upon advising the installing contractor who in turn notify the distributor or...

Страница 39: ...lio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www Trane com Trane has a policy of continuous product and product data improvement and r...

Отзывы: