28

RT-SVX50J-EN

ON after a Cooling call is cleared, the Supply Fan will
remain energized at Low Speed for 60 seconds as on
traditional units.

If the economizer is enabled and is being utilized as the
first stage of cooling (Y1 active), if the unit receives a
Y2 request, the unit will energize the first compressor
and will switch the supply fan to high speed until the
Y2 request is cleared.

Economizer Minimum Position Handling
for 2–Speed Fan

Due to the low and high speeds of the indoor fan, when
the unit is in Fan Only, Cool 1, or Economizer Only and
the indoor fan is at low speed, the unit will not be
bringing in as much fresh air as normal. By setting a
higher minimum damper position this problem could
be solved, but that would mean more fresh air than
may be desired when the supply fan is at high speed.
To overcome these situations, the control will require
the setting of two economizer minimum positions to be
used when the fan is at low and high speed to
compensate for the lower amount of fresh air at lower
fan speeds and the potential for more fresh air than
desired at higher fan speeds. These minimum positions
will be obtained from the Bldg Design Min Position and
DCV Min Position pots on the RTEM-EM. The
economizer minimum position that will be utilized
while the supply fan is at low speed will be set with the
DCV Min Position pot with a range of 0-100% and the
minimum position that will be utilized while the supply
fan is at high speed will be set with the Building Design
Min Position pot with a range of 0-50%. If the Building
Design Min Position is set to be higher than the DCV
Min Position, the setpoints will be capped at the DCV
Min Position and the setpoint for the min position at
low and high fan speed will be the DCV Min Position.

Phase Monitor

The phase monitor is a 3 phase line monitor module
that protects against phase loss, phase reversal and
phase unbalance. It is intended to protect compressors
from reverse rotation. It has an operating input voltage
range of 190-600 Vac, and LED indicators for ON and
FAULT. There are no field adjustments and the module
will automatically reset from a fault condition.

Low Pressure Cutout

The low pressure cutouts are wired in series with the
high pressure cutouts and the temperature discharge

limits. If this circuit is open before a compressor is
started, the compressor in that circuit will not be
allowed to operate.

Anytime this circuit is opened, the compressor in that
circuit is turned off immediately.

High Pressure Cutout and Temperature
Discharge Limit

The high pressure controls and temperature discharge
limit are wired in series between the compressor
outputs on the LTB and the compressor contactors. If
the high pressure safety or temperature discharge limit
opens, the compressor on the affected circuit is turned
off.

Locking Safety Device with Compressor
Anti Short Cycle Timer

This device monitors compressor safety switch trips to
prevent short cycling, protecting the compressor. A
manual reset is required after a fourth safety switch
trip.

Coil Frost Protection

The Frostat

control monitors the evaporator coil

temperature to prevent the evaporator from freezing
due to low operating temperatures whenever there is a
demand for cooling. When a open circuit has occurred,
the Frostat opens the 24 Vac ground and opens all of
the cooling contactors.

Heating Operation

Standard unit operation for heating will continue on
units equipped with a two-speed indoor fan. During
heat mode, all units configured with staged electric or
gas heat will heat the supply air and space as normal
utilizing full speed indoor fan.

Emergency Stop

This input de-energizes the 24 Vac output from the
phase monitor and can be activated by opening a field
supplied device connected to the LTB.

S

Stta

arrtt U

Up

p

Содержание Foundation EBC180

Страница 1: ...Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the t...

Страница 2: ...r p pr ro op pe er r P PP PE E f fo or r t th he e j jo ob b b be ei in ng g u un nd de er rt ta ak ke en n c co ou ul ld d r re es su ul lt t i in n d de ea at th h o or r s se er ri io ou us s i in...

Страница 3: ...ma ay y a af ff fe ec ct t t th he e w wa at te er r t ti ig gh ht t i in nt te eg gr ri it ty y o of f t th he e u un ni it t a an nd d l le ea ad d t to o w wa at te er r l le ea ak ks s i in nt to...

Страница 4: ...5 Verifying Proper Air Flow Units with Belt Drive Indoor Fan 25 Electromechanical Controls Test Procedure 25 Start Up 26 Electromechanical Controls Sequence Of Operation 26 Cooling without an Economiz...

Страница 5: ...tch 37 Cooling Season 37 Heating Season 38 Coil Cleaning 38 Troubleshooting 41 Standard Troubleshooting 41 Failures 41 Low Leak Economizer LLE Troubleshooting 41 Resetting Cooling and Heating Lockouts...

Страница 6: ...omizer Dry Bulb w o Barometric Relief L Downflow Low Leak Economizer Reference Enthalpy w o Barometric Relief N Downflow Low Leak Economizer Comparative Enthalpy w o Barometric Relief Digit 15 Supply...

Страница 7: ...tr ra at ti io on ns s r re eq qu ui ir ri in ng g a ad dd di it ti io on na al l r re es sp pi ir ra at to or ry y p pr ro ot te ec ct ti io on n U Us se e t th he e a ap pp pr ro op pr ri ia at te...

Страница 8: ...relay energizes and opens the 24 Vac control circuit disabling the unit A delay timer prevents the unit from starting for 3 minutes Phase Monitor The Phase Monitor is a three phase line monitor module...

Страница 9: ...he CO2 SPAN to 1600 ppm in the ADVANCED SETUP menu Occupancy Sensor A customer supplied occupancy sensor can also be added to provide damper control based on occupied unoccupied conditions Low Leak Ec...

Страница 10: ...zer airflows or recirculation of hot condenser air Figure 1 Typical installation clearance for single and multiple unit applications NOTES 1 FOR HORIZONTAL DISCHARGE UNIT THIS MEASUREMENT IS REDUCED T...

Страница 11: ...ONDENSATE DRAIN CONNECTION Figure 3 Cooling with optional electrical heat front and side views electric electric NOTES 1 THROUGH THE BASE ELECTRICAL IS NOT STANDARD ON ALL UNITS 2 VERIFY WEIGHT CONNEC...

Страница 12: ...DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION THROUGH THE BASE ELECTRICAL RETURN SUPPLY 64 9 16 71 15 16 14 15 16 7 7 16 7 3 8 123 1 8 36 1 16 6 15 16 6 13 16 68 9 16 Figure 5 Cooling with op...

Страница 13: ...51 MM 69 1 2 1765 MM Figure 7 Cooling with optional electrical heat downflow duct connections field fabricated 1 25 4 MM CURB FLANGE LONG SIDES 14 1 16 357 MM 7 7 16 189 MM 73 7 16 1865 MM 1 25 MM 19...

Страница 14: ...nal electric heat barometric relief and economizer NOTES 1 VERIFY WEIGHT CONNECTION AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION 2 BAROMETRIC RELIEF IS FOR USE WITH A DOWNFLOW ECONOM...

Страница 15: ...manual damper NOTE VERIFY WEIGHT CONNECTION AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION BACK VIEW OF UNIT LEFT VIEW OF UNIT FAN MANUAL DAMPER HOOD 123 1 8 18 1 4 26 7 8 24 7 8 12 1...

Страница 16: ...a as s n ne ec ce es ss sa ar ry y f fo or r e ev ve en n u un ni it t l li if ft t W WA AR RN NI IN NG G I Im mp pr ro op pe er r U Un ni it t L Li if ft t F Fa ai il lu ur re e t to o p pr ro op pe...

Страница 17: ...RT SVX50J EN 17 Figure 12 Rigging and center of gravity data CENTER OF GRAVITY LENGTH CENTER OF GRAVITY WIDTH W We ei ig gh ht ts s...

Страница 18: ...tion the unit and the curb must be level If the unit is installed at ground level elevate it above the snow line Provide concrete footings at each support location with a full perimeter support struct...

Страница 19: ...ermostat with or without switching subbase Connect properly sized control wiring to the proper termination points between the zone thermostat and the unit control panel Condensate Drain Configuration...

Страница 20: ...ce must be protected from over current and short circuit conditions in accordance with NEC requirements Protection devices must be sized according to the electrical data on the nameplate If the unit i...

Страница 21: ...t does not exceed three 3 ohms conductor for the length of the run N No ot te e Resistance in excess of 3 ohms per conductor could cause component failure due to insufficient AC voltage supply 3 Be su...

Страница 22: ...ct ts s b be ef fo or re e s se er rv vi ic ci in ng g F Fo ol ll lo ow w p pr ro op pe er r l lo oc ck ko ou ut t t ta ag go ou ut t p pr ro oc ce ed du ur re es s t to o e en ns su ur re e t th he...

Страница 23: ...ings need lubricating refer to the maintenance section of this manual for instructions Verify that a condensate trap is installed and the piping is properly sized and pitched Verify that the correct s...

Страница 24: ...of the factory installed disconnect switch Connect the power conductors to the lugs provided Connect the ground wire to the unit ground lug N No ot te e Wire size for the length of run should be dete...

Страница 25: ...ol ECA if applicable Electromechanical Controls Test Procedure See unit schematic for correct wire numbers F Fa an n T Te es st t a an nd d M Mi in ni im mu um m V Ve en nt ti il la at ti io on n Conn...

Страница 26: ...tside air dry bulb temperature Table 3 p 26 lists the selectable dry bulb values by potentiometer setting Table 3 Potentiometer settings Potentiometer Setting Dry Bulb Enthalpy A 27 Btu lb 63 kJ kg 73...

Страница 27: ...the trip point the COF relay energizes and opens the 24 Vac control circuit which disables the unit Once the 24 Vac control circuit is opened a delay timer will prevent unit start up for three minutes...

Страница 28: ...tor is a 3 phase line monitor module that protects against phase loss phase reversal and phase unbalance It is intended to protect compressors from reverse rotation It has an operating input voltage r...

Страница 29: ...to Full Open On On High 24 v On 0 v Off a VENTMIN to Full Open Closed to Full Open Above CO2 set No Off Off High 0 v Off 0 v Off VENTMIN to VENTMAX Closed On Off High 24 v On 0 v Off VENTMIN to VENTMA...

Страница 30: ...LY in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 O after the delay if the call for Y1 I and Y2 I have not been satisfied Table 9 Dry bulb operation no DCV CO2 sensor 2 speed fa...

Страница 31: ...satisfied b With 2SP FAN DELAY Advanced Setup Menu when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to hi...

Страница 32: ...alpy boundaries parameters ES1 through ES5 Enth Curve Temp dry Bulb F Temp dewpoint F Enthalpy btu lb da Point P1 Point P2 Temp F Humid RH Temp F Humid RH ES1 80 0 60 0 28 0 80 0 36 8 66 3 80 1 ES2 75...

Страница 33: ...r temperature discharge limit opens the compressor on the affected circuit is turned off Coil Frost Protection The Frostat control monitors the evaporator coil temperature to prevent the evaporator fr...

Страница 34: ...pressure should rise If a scroll compressor is rotating backwards it will not pump and a loud rattling sound can be observed b If the electrical phasing is correct before condemning a compressor inter...

Страница 35: ...nel if applicable for proper unoccupied operation Refer to the programming instructions for the specific panel Verify that the Remote panel System selection switch Fan selection switch and Zone Temper...

Страница 36: ...w belts do not stretch them over the sheaves Loosen the belts using the belt tension adjustment bolts on the motor mounting base Once the new belts are installed using a Browning or Gates tension gaug...

Страница 37: ...er ri io ou us s i in nj ju ur ry y D Di is sc co on nn ne ec ct t a al ll l e el le ec ct tr ri ic c p po ow we er r i in nc cl lu ud di in ng g r re em mo ot te e d di is sc co on nn ne ec ct ts s...

Страница 38: ...ch circuit superheat and subcooling each circuit Record this data on an operator s maintenance log like the one shown in Sample maintenance log table in Final Process Section If the operating pressure...

Страница 39: ...thin walls of the MCHE coils the traditional field maintenance method recommended for Round Tube Plate Fin RTPF coils does not apply to microchannel coils Moreover chemical cleaners are a risk factor...

Страница 40: ...id Press Psig kPa Super heat F C Sub cool F C Compr Oil Level Suct Press Psig kPa Disch Press Psig kPa Liquid Press Psig kPa Super heat F C Sub cool F C ok low ok low ok low ok low ok low ok low ok lo...

Страница 41: ...ic ca al l c co om mp po on ne en nt ts s p pe er rf fo or rm m t th he es se e t ta as sk ks s Standard Troubleshooting Failures Cooling Failure 1 Cooling and heating set points slide pot on the the...

Страница 42: ...the Mode selection switch at the thermostat to the Off position After approximately 30 seconds turn the Mode selection switch to the desired mode i e Heat Cool or Auto Method 2 To reset the system at...

Страница 43: ...agrams Type of Airflow Schematic Type Voltage Diagram Number Description Constant Volume Power 208 575 1213 3649 Schematic PWR EM CO CV Control 208 575 1213 2968 EBC180 300 60Hz Cooling only Electric...

Страница 44: ...r s obligations and liabilities under this warranty are limited to furnishing F O B factory or warehouse at the warrantor designated shipping point freight allowed to Buyer s city or port of export fo...

Страница 45: ...RT SVX50J EN 45 N No ot te es s...

Страница 46: ...46 RT SVX50J EN N No ot te es s...

Страница 47: ...RT SVX50J EN 47 N No ot te es s...

Страница 48: ...please visit trane com or americanstandardair com Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications...

Отзывы: