Installation - Controls
UNT-SVX041D-EN
59
Agency Compliance
Wireless Display Sensor (WDS)
Configuration Procedure
Note:
Sensors shipped with the fan coil are pre-
configured for three speeds.
The configuration of the sensor determines which system
features can be accessed and changes can be made by the
tenant (for example, changes to cooling/heating mode,
setpoint, or fan speed. Verify system and associated unit
features before configuring the sensor.
The building owner or operator may choose to limit tenant
access to certain features. This can be done through
configuration. Or, if a sensor is configured to match all
control capabilities of the building automation system, the
locking feature can be used to restrict the tenant from
making changes.
To configure settings on the wireless display sensor
(WDS), follow this procedure in the order presented.
1. Press the configuration button for three seconds.
The display will change to configuration mode. When the
sensor is in configuration mode, a wrench symbol appears
on the display and the menus are separated by lines, as
shown in the figure below.
Table 27. Agency compliance information for wireless sensors
Agency
Compliance
United States
compliance
(all models)
UL listed: UL 94-5VA Flammability rating
UL 916: Energy management equipment
FCC CFR47, Section 15.247 & Subpart E Digital Modulation Transmission with no SAR (FCC Identification TFP-
13651127)
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received,
including interference that may cause undesired operation.
Warning: Changes or modifications not expressly approved by the party responsible for compliance could void the
user’s authority to operate the equipment.
20 cm separation distance:
To comply with FCC’s RF exposure limits for general population/uncontrolled exposure, the antenna(s) used for this
transmitter must be installed to provide a separation distance of at least 20 cm from all persons and must not be
co-located or operating in conjunction with any other antenna or transmitter.
Canada compliance
(all models)
CSA22.2 No. 205-M1983 Signal Equipment
Industry Canada (Certification no: IC: 6178A-13651127)
Industry Canada statement:
the term “IC” before the certification/registration number signifies only that the Industry Canada technical
specifications were met.
Section 14 of RSS-210:
The installer of this radio equipment must ensure that the antenna is located or pointed such that it does not emit
RF field in excess of Health Canada limits for the general population.
IEEE compliance for
radio frequency range
(all models)
IEEE 802.15.4-2003, IEEE Standard for Information Technology—Telecommunications and information exchange
between systems—Local and metropolitan area networks—Specific requirements, Part 15.4: Wireless Medium Access
Control (MAC) and Physical Layer (PHY) Specifications for Low Rate Wireless Personal Area Networks (LR-WPANs)
Figure 52.
Configuration button
Figure 53.
Wrench is shown in configuration mode
Configuration
button