28
WSHP-SVX02A-EN
Troubleshooting
Checklist
Problem
Heating
Cooling
Cause
Correction
No response to any
thermostat setting
X
X
Main power off
Check fuses
X
X
Defective control transformer
Replace
X
X
Broken or loose connection
Repair
X
X
Defective thermostat
Replace
X
X
Transformer
Reset Transformer
Unit short cycles
X
X
Thermostat or sensor improperly located
Relocate
Insufficient capacity
X
X
Low on refrigerant charge
Locate leak, repair and recharge by
weight (not by superheat)
X
X
Restricted thermal expansion valve
Replace
X
X
Defective reversing valve
See WSHP-IOM-# for touch test chart
X
X
Thermostat improperly located
Relocate
X
X
Unit undersized
Recalculate heat gains/losses
X
X
Inadequate water flow
Increase GPM
X
X
Scaling in heat exchanger
Clean or replace
X
Water too hot
Decrease temperature
X
Water too cold
Increase temperature
High pressure switch open
X
Inadequate GPM
Increase water flow to unit
X
Water too hot
Decrease temperature
X
X
Overcharged with refrigerant
Decrease charge
X
X
Defective pressure switch
Check or replace
High head pressure
X
Trash in heat exchanger
Backflush
X
Low water flow
Increase GPM
X
X
Overcharge of refrigerant
Decrease charge
X
X
Non-condensable in system
Evacuate and recharge by weight
X
X
Water too hot
Decrease temperature
Low suction pressure
X
X
Undercharged
Locate leak, repair and recharge
X
X
Restricted thermal expansion valve
Repair / replace
X
Inadequate GPM
Increase GPM
Low Pressure switch open
X
Inadequate GPM
Increase GPM
X
Water too cold
Increase temperature
X
X
Undercharged with refrigerant
Increase charge
X
X
Defective pressure switch
Replace
X
X
Heat transfer fluid too cold
Raise water temperature. For smaller
tonnage units, switch pressure switch
wires from 35 psig to 7 psig
Freezestat open
X
Inadequate GPM
Increase GPM
X
Water too cold
Increase GPM
X
X
Defective freezestat
Replace freezestat
X
Heat transfer fluid too cold
Replace freezestat. For smaller tonnage
units, switch pressure wires from 35 psig
to 7 psig.
Содержание EXWA
Страница 7: ...WSHP SVX02A EN 7 Dimensions WPWD GSWD 024 036 ...
Страница 8: ...8 WSHP SVX02A EN Dimensions WPWD GSWD 042 072 ...
Страница 9: ...WSHP SVX02A EN 9 Dimensions EXWA 240 ...
Страница 29: ...WSHP SVX02A EN 29 Unit Wiring 2 ton through 6 Ton Equipment ...
Страница 30: ...30 WSHP SVX02A EN Unit Wiring 20 Ton Equipment ...