16
WSHP-SVX02A-EN
Field Installed Power Wiring
Power wiring to the equipment must
conform to National and Local Electric
Codes (NEC) by a professional electri-
cian.
WARNING
Live Electrical
Components!
During installation, testing, ser-
vicing and troubleshooting of this
product, it may be necessary to
work with live electrical compo-
nents. Have a qualified licensed
electrician or other individual
who has been properly trained in
handling live electrical compo-
nents perform these tasks. Failure
to follow all electrical safety pre-
cautions when exposed to live
electrical components could re-
sult in death or serious injury.
Verify that the power supply available
is compatible with the unit’s name-
plate. Use only copper conductors to
connect the power supply to the unit.
CAUTION
Use Copper
Conductors Only!
Unit terminals are not designed
to accept other types of conduc-
tors. Failure to use copper con-
ductors may result in equipment
damage.
Main Unit Power Wiring
A field supplied disconnect switch
must be installed at or near the unit in
accordance with the National Electric
Code (NEC latest edition).
Location of the applicable electric ser-
vice entrance for HIGH (line voltage)
may be found on the unit submittal at
the front of this manual (pages 7
through 9).
The high voltage connection is made
at the 1TB1 terminal block for the 20-
ton equipment, and at 1K1 for the 2-
ton through 6-ton equipment. The ter-
minal block or contactor is located in-
side the unit control box. Refer to the
customer connection diagram that is
shipped with the unit for specific ter-
mination points.
Provide proper grounding for the unit
in accordance with the local and na-
tional codes.
Control Power Transformer
The 24-volt control power transform-
ers are to be used only with the acces-
sories called out in this manual.
Transformers rated greater than 50 VA
are equipped with internal circuit
breakers. If a circuit breaker trips, turn
OFF all power to the unit before at-
tempting to reset it.
WARNING
Hazardous Voltage!
Disconnect all electric power, in-
cluding remote disconnects be-
fore servicing. Follow proper
lockout/tagout procedures to en-
sure the power can not be inad-
vertently energized. Failure to
disconnect power before servic-
ing could result in death or seri-
ous injury.
The transformer is located in the
control box.
Installation
Power Wiring
Содержание EXWA
Страница 7: ...WSHP SVX02A EN 7 Dimensions WPWD GSWD 024 036 ...
Страница 8: ...8 WSHP SVX02A EN Dimensions WPWD GSWD 042 072 ...
Страница 9: ...WSHP SVX02A EN 9 Dimensions EXWA 240 ...
Страница 29: ...WSHP SVX02A EN 29 Unit Wiring 2 ton through 6 Ton Equipment ...
Страница 30: ...30 WSHP SVX02A EN Unit Wiring 20 Ton Equipment ...