MUA-SVX01A-EN • Direct-Fired Make-up Air
89
Trouble Shooting
Short in room sensor/
selector or room
temperature sensor/
room temperature
selector circuit.
Remove wires connected
to amplifier terminals 4 &
5. Set room sensor/
selector or room
temperature selector to
maximum setting.
Measure resistance across
the wires. Meter should
read 6000 ohms ±1000
(room sensor/selector). If
room temperature sensor
and selector are used
meter should read 4500
ohms ±1000 (room
temperature sensor) and
2100 ohms ±150 (room
temperature selector)
a. If reading is
incorrect,
replace the
room sensor/
selector, room
temperature
sensor/room
temperature
selector, or
repair wiring.
8. Incorrect maximum/
minimum discharge air
temperature.
Improper discharge air
sensor location
Compare sensed
temperature reading at
discharge air sensor with
average discharge air
temperature.
a. Move
discharge air
sensor location
where average
temperature
can be sensed.
Incorrect discharge air
temperature calibration.
Follow procedures
outlined in
a. If proper
temperatures
are not
observed, refer
to discharge
air
temperature
calibration
procedures.
9. Burned out
transformer.
Short circuit in
modulator coil.
Measure resistance across
modulator coil.
a. If proper
resistances are
not observed,
replace
modulator
head or repair
wiring.
10. Continuous high fire
(electronics problem).
Open circuit in
discharge air sensor.
Measure resistance across
discharge air sensor.
a. If readings
are incorrect,
replace the
discharge air
sensor or
repair wiring.
11. Continuous
maximum discharge air
temperature.
Faulty amplifier.
Follow procedures
outlined in
a. If amplifier
is proven at
fault, install
replacement
amplifier.
Table 18.
Trouble shooting guide for Modulationg Room Temperature (MRT)
controls
Symptom
Probable Cause
Field Test
Solution
*
Control circuits external to MRT controls can cause burner malfunction. Always check manual valve
to be certain gas is on, and check limit controls for normal operation.