Preventive Maintenance
Periodical Preventive
Maintenance
Record operation conditions for this unit
monthly. The operation datasheet can
be a precious diagnostic tool for service
personnel.
By
noticing
trends
in
operating conditions the operator can
often anticipate and prevent problem
situations before they become serious.
If the unit is not operating properly, refer
to the section on abnormal conditions
at the end of this manual.
Weekly Maintenance
When the equipment is operating for
approx. 30 minutes and the system is
stable, check the operating conditions
and perform the following checking
procedures:
Clean permanent air filters more
often, depending on the job site.
Monthly Maintenance
Clean the permanent air filter.
Throwaway filters should be replaced.
Check
fan
belt
tension,
alignment and condition.
Clean the fan volute.
Re-tighten all terminal screws.
Clean the evaporator tray, the
hose and the condensate water drain.
Check the liquid line sight glass.
Leak-test and repair, if required.
When the liquid sight glass and
the operational conditions indicate lack
of
gas,
measure
the
system
overheating and subcooling.
When
operational
conditions
indicate
overload,
remove
the
refrigerant slowly (to minimize oil
losses) through the Schrader service
valve in the liquid line.
Inspect the system to detect
abnormal conditions. Use a reading
sheet to record unit conditions. A
reading sheet completed can be a
precious tool for service personnel.
Quarterly Maintenance
Perform
all
monthly
maintenance tasks.
Check bearing and shave fixing
screws and adjust then, if required.
Clean
the
condenser
more
often, depending on the job site.
Clean
the evaporator
more
often, depending on the job site.
Check and write down fan motor
and compressor operation voltages
and currents.
Test safety controls.
Check
and
write
down
evaporator entering and leaving dry
bulb and wet bulb temperatures.
Check suction and discharge
pressures with the manifold.
Measure and record the system
overheating.
Measure and record the system
subcooling.
Annual Maintenance
Perform
all
recommended
monthly and quarterly maintenance
tasks.
Have a qualified technician to
check the adjustment and operation of
each control, and inspect and replace
counters or controls, if required.
Remove the cabinet panels and
remove rust spots.
Replace the thermal insulation
and defective gaskets.
Repair the external and internal
painting, if required.
Remove rust.
Inspect
and
clean
the
condenser pipes, if required.
Inspect the expansion valve
bulb. Clean it, if required. The contact
between the bulb and the suction line
should be excellent, and the bulb
should the properly insulated.
Measure the electrical insulation
of the compressor motor.
IMPORTANT
Failure
to
perform
preventive
maintenance tasks in the equipment
may lead to impaired performance and
even void the equipment warranty.
IMPORTANT
Perform all inspections and maintenance
services at the recommended intervals.
This will increase equipment life and
reduce possible equipment failures.
Содержание CXPA
Страница 30: ...30 SSC SVN001F EN Fig 37 Dimensions Condensing Units TRAE 150 2 circuits TRAE Dimensional Data...
Страница 31: ...SSC SVN001F EN 31 Fig 38 Dimensions Condensing Units TRAE 200 1 Circuit TRAE Dimensional Data...
Страница 32: ...32 SSC SVN001F EN TRAE Dimensional Data Fig 39 Dimensions Condensing Units TRAE 200 2 Circuits...
Страница 33: ...SSC SVN001F EN 33 TRAE Dimensional Data Fig 40 Dimensions Condensing Units TRAE 250 1 Circuit...
Страница 34: ...34 SSC SVN001F EN TRAE Dimensional Data Fig 41 Dimensions Condensing Units TRAE 250 2 Circuits...
Страница 35: ...SSC SVN001F EN 35 TRAE Dimensional Data Fig 42 Dimensions Condensing Units TRAE 300 2 Circuits...