V07-19.0
77/115
Night setback 1/4
Room setpoint
22.0°C
Min run time
30min
Supply
5000m3/h
Rturn
5000m3/h
Figure 96:
Night setback
Setpoint
Description
Default
Room setpoint
Room temperature setpoint for night setback
22 °C
Min run time
Minimum operating time, even if the
conditions are no longer met
30 minutes
Supply
Supply airflow rate, supply fan speed
Nominal value, 60%
Return
Return airflow rate, return fan speed
Nominal value, 60%
Table 23:
Night setback setpoints
15 Operating mode / scheduler
The on / off switching and the operating mode economy or comfort are determined by a variety of
sources, which have different priorities. A source with a higher priority overrides all lower prioritized
sources.
•
HMI
Request from HMI (Off, NightStb, Eco, Comfort, Auto)
with
Auto
the operating mode is determined by the BMS
•
BMS
Request from BMS (Off, NightStb, Eco, Comfort, Auto)
with
Auto
the operating mode is determined by the room unit
•
Room unit
Request from room unit (Off, Eco, Comfort, Auto)
with
Auto
the operating mode is determined by the scheduler
•
Scheduler
Request from scheduler (Off, NightStb, Eco, Comfort)
with no entry (display -) the AHU is off
Note: the AHU can be started and stopped at the electric cabinet (operating display mounted
on the electric cabinet) by setting the operating mode of the HMI.
Depending on the execution of the AHU, individual control devices / lines are not displayed; room
unit and building management system are optional. Only the operating mode of the HMI and, with
the expanded customer password, the building management system setting is adjustable (for test
purposes and in case of failure).
The current mode is displayed next to each control device. The
Operating mode
line shows the re-
sulting operating mode, which results from the various control devices and the scheduler. The
Scheduler
line shows the resulting operating mode switch of the scheduler, which results from the
scheduler setting.