72/115
V07-19.0
Setpoint
Description
Default
Summer compensation
Start
Outdoor temperature start point for shift
25 °C
End
Outdoor temperature end point for shift
30 °C
Delta
Shift value of the cooling setpoints at the end point
0 °C
Calculated
Shift due to the current outdoor temperature
… °C
Winter compensation
Start
Outdoor temperature start point for shift
0 °C
End
Outdoor temperature end point for shift
-10 °C
Delta
Shift value of the cooling setpoints at the end point
0 °C
Calculated
Shift due to the current outdoor temperature
… °C
Table 16:
Summer / winter compensation settings
14.2.5
Setpoint and control variable
At the end of the page, the currently used setpoints and the current control variable are displayed,
which vary depending on the control strategy.
Temperature setpoints 1/6
Supply temp.min
16.0°C
Supply temp.max
35.0°C
Summer compensation
0.0°C
-----------------------------
Controlled temp.
20.3°C
Heat set
16.0°C
Cool set
35.0°C
Figure 93:
Current setpoints
Setpoint
Description
Default
Controlled temp.
Current control variable (return air, supply air
or room temp.)
… °C
Heat set
Current setpoint for recovery, heating
batteries
… °C
Cool set
Current setpoint for cooling batteries
… °C
Table 17:
Heat / cool setpoint and controlled temperature
14.2.6
Recirculation damper
The recirculation damper is not modulating, but is opened or closed depending on the heating re-
quirement and the set base time (60min). The recirculation damper operates as the last heating se-
quence for temperature regulation (unless dehumidification by means of recirculation damper has