background image

        15

INSTALLER’S GUIDE

CHECKOUT AND TROUBLESHOOTING

C

heckout requires a 9V battery, 620 ohm, 1.2K ohm, 5.6K 

ohm, and 6.8K ohm resistors. Use Table 4 and Fig. 18 for 

checkout.

5B. CHECKOUT - For Units with a Honeywell W7212 Control, Only. See 5A for W7459

Fig. 18. Meter location for checkout and 

troubleshooting (W7212 shown).

M20612

N1

P1

T1

N

2V

2V

2V

B

A

SR

SO

AQ

C

D

Free

Cool

10V

EXH

DCV

EXH

Set

10V

DCV

Max

10V

DCV

Set

Min

Pos

Open

P

T

AQ1

SO+

SR+

1

2

DC VOLTMETER

620 OHM RESISTOR

W7212

+

S

+

C7400

1

2

INSERT DC VOLTMETER BETWEEN AQ AND AQ1 FOR

CHECKOUT AND TROUBLESHOOTING.

JUMPER USED FOR SINGLE ENTHALPY CONTROL.

Equipment Damage Hazard.

Excessive force can damage potentiometer controls. 

Use a small screwdriver when adjusting enthalpy 

changeover and minimum damper position controls.

CAUTION

Table 4. Checkout for W7212, W7213, W7214 Economizer Connected to Honeywell Actuator

Step

Checkout Procedure

Proper Response

1.

CHECKOUT PREPARATION FOR ECONOMIZING ONLY

Disconnect power at TR and TR1

All LED are off; Exhaust Fan contacts are open

Disconnect devices at P and P1
Jumper P to P1 (defaults to on board MIN POS potentiometer).
Place 5.6K ohm resistor across T and T1 (Blue sleeve-provides 

input to economizer that the MAT is between 50-55F).
Jumper TR to 1 (call for cooling from the thermostat).

W7212 only jumper TR to N (places economizer in occupied 

mode).

If connected, remove C7400 Enthalpy Sensor from terminals S

O

 

and +.

Connect 1.2K ohm, from 4074EJM Checkout Resistor kit, (purple 

sleeve) across terminals S

O

 and + (makes OA enthalpy high).

Place 620 ohm resistor (white sleeve) across S

R

 and + (makes 

return enthalpy lower than OA).
Set MIN POS and DCV MAX potentiometers fully CCW.
Turn DCV setpoint potentiometer mid position (this sets the DCV 

ventilation at approximately 1000 ppm).
Turn exhaust potentiometer to mid position (motor will be ap-

proximately 50% open when the exhaust fan contacts make).

Set enthalpy potentiometer to D.
W7214 only Jumper TR to O.
Apply power (24 Vac) to terminals TR and TR1

Содержание BAYRLAY006A

Страница 1: ...TRIC SHOCK HAZARD Open and lock out all unit disconnects prior to ac cessory installation or unit maintenance to prevent injury or death from electrical shock or contact with moving parts SAFETY HAZARD Do not remove end covers from economizer actua tor the spring return assembly may release and cause personal injury Install Economizer Kit 1 Remove Power Disconnect and verify that power is off 2 Re...

Страница 2: ... left Blower partition using two sheetmetal screws See Figure 10 page 7 The male tabs on the Yellow and Yellow Black wires will connect to the Economizer wiring harness in a later step 2 Enthalpy Sensor If used install this option at this time per instructions provided in the sensor kit 7 Route Main Wiring 1 From the Economizer assembly pass the wire harness through the coil grommet See Figure 11 ...

Страница 3: ...B AC Economizer Kit Components Top Sealing Flange Horizontal Return Air Panel Down Flow Return Air Panel Coils Access Panel Blower Access Panel Control Box Access Panel Figure 3 Remove Panels Mixed Air Sensor Logic Module Economizer Assembly Return Air Damper Flange Screw and two 2 Mixed Air Sensor Sheetmetal Screws not shown Mist Eliminator Filter Rainhood Assembly Figure 2 BAYECON104AA AB AC Eco...

Страница 4: ...amper Economizer 2 Insert Assembly Screw Figure 5 Swing Down and Set Economizer Return Damper Figure 4 Insert Economizer in Shipping Position Dry bulb outside air temperature sensor Economizer actuator and Logic Module Insert economizer in folded shipping position ...

Страница 5: ... and hood Economizer and Return Air Damper Figure 7 Mounting Rain Hood 3 Tighten the two 2 top screws and the two 2 side screws 2 Drive six 6 self tapping screws into the keyhole openings on each side of hood 1 Loosen the two 2 screws to allow hood to slide under the unit Economizer Rain Hood Unit s top sealing slides under HVAC unit s top sealing HVAC unit s top HVAC unit Hood Detail ...

Страница 6: ...and Filter Economizer Rain Hood A Mist Eliminator Relief Damper Return Duct Roofcurb order separately Outside air dampers Return air dampers Economizer Unit Application Models A BAYECON103AA AB AC 20 1 8 BAYECON104AA AB AC 24 3 8 WCZ 024 036 DCZ 024 036 YCZ 024 036 WCZ 048 060 DCZ 048 060 YCZ 048 060 ...

Страница 7: ...1 From economizer assembly pass wire harness through coil Grommet See View A 2 Continue routing behind compressor compartment and into Blower Compartment Coil Grommet 3 Pull the two 2 Mixed Air Sensor wires with female quick connects from the harness and route down near the Mixed Air Sensor Connect to sensor pigtail wire leads 4 Continue Routing the Remaining Harness Through the Grommet and into t...

Страница 8: ...ure 12 YCZ Economizer Connection Diagram A A A A IMPORTANT Retain this wiring diagram please return this document to service information pack upon completion of work Wiring Diagram for Economizer Using a Honeywell W7459 Logic ...

Страница 9: ... A IMPORTANT Retain this wiring diagram please return this document to service information pack upon completion of work Wiring Diagram for Economizer Using a Honeywell W7459 Logic Figure 13 WCZ DCZ Economizer Connection Diagram ...

Страница 10: ...A A A A ACCESSORY MODELS BAYECON103AA AB AC BAYECON104AA AB AC BAYECON203AA AB AC BAYECON204AA AB AC IMPORTANT Retain this wiring diagram please return this document to service information pack upon completion of work Wiring Diagram for Economizer Using a Honeywell W7212 Logic ...

Страница 11: ...A A A ACCESSORY MODELS BAYECON103AA AB AC BAYECON104AA AB AC BAYECON203AA AB AC BAYECON204AA AB AC IMPORTANT Retain this wiring diagram please return this document to service information pack upon completion of work Wiring Diagram for Economizer Using a Honeywell W7212 Logic ...

Страница 12: ...and Dual Fuel models When outdoor air conditions are suf ficient for Free Cooling and the thermostat sends a signal for 2nd stage cooling G Y1 Y2 O for Heat Pumps 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 3 0 3 2 3 4 3 6 3 8 4 0 4 2 4 4 4 6 9 0 1 0 0 8 0 7 0 6 0 5 0 4 0 3 0 20 10 E N T H A L P Y B T U P E R P O U N D D R Y A I R 85 29 90 32 95 35 100 38 105 41 110 43 35 2 35 2 40 4 40 4 105 41 110 43 45...

Страница 13: ... Connect 1 2K ohm 4074EJM Checkout Resistor across terminals So and 2 Turn enthalpy setpoint potentiometer to A LED turns on indicating low enthalpy Motor drives toward open 3 Turn enthalpy setpoint potentiometer to D LED turns off indicating high enthalpy Motor drives toward closed 4 Disconnect the 1 2K ohm checkout resistor D 1 To verify sensor operation reconnect the lead of the outdoorenthalpy...

Страница 14: ...9 6 32 2 204 2 714 91 4 33 2 111 2 676 93 2 34 2 023 2 639 95 0 35 1 938 2 600 96 8 36 1 858 2 561 98 6 37 1 781 2 526 100 4 38 1 708 2 484 Temp vs OHM for MAS Mixed Air Sensor Table 3 Temp vs OHM Values for MAS Mixed Air Sensor 1 1 2 2 M9097 ENTHALPY CHANGEOVER SETPOINT LED LIGHTS WHEN OUTDOOR AIR IS SUITABLE FOR FREE COOLING INSERT DC MILLIAMMETER BETWEEN SO AND S FOR CHECKOUT AND TROUBLESHOOTIN...

Страница 15: ...e Proper Response 1 CHECKOUT PREPARATION FOR ECONOMIZING ONLY Disconnect power at TR and TR1 All LED are off Exhaust Fan contacts are open Disconnect devices at P and P1 Jumper P to P1 defaults to on board MIN POS potentiometer Place 5 6K ohm resistor across T and T1 Blue sleeve provides input to economizer that the MAT is between 50 55F Jumper TR to 1 call for cooling from the thermostat W7212 on...

Страница 16: ...at 45 degrees open Adjust DCV MAX towards CW Motor will move to position set by DCV MAX pot Adjust DCV MAX to fully CCW Motor will drive closed Reconnect jumper to N terminal Adjust DCV MAX and MIN POS pots Motor will drive to the most open position of the pots Adjust DCV MAX and MIN POS pots to fully CCW Remove power from N terminal adjust MIN POS towards CW Motor should not move Adjust DCV MAX t...

Страница 17: ...pplications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice We are committed to using environmentally conscious print practices 2022 18 HE85D1 1D EN 09 Sep 2022 Supersedes 18 HE85D1 1C EN May 2022 ...

Отзывы: