18-HB20D4-1E-EN

5

W/TC*3036-060‡4
WCZ6036-060‡4
*CC4036-60‡4

BAYHTRV415

480

3

18

15.0

51200

2

10.0

5.0

23

25

25

W/TC*3048-060‡4
WCZ6048-060‡4
*CC4048-60‡4

BAYHTRV420

480

3

24

20.0

68300

2

10.0

10.0

30

30

30

W/TC*3060‡4
WCZ6048-060‡4
*CC4048-60‡4

BAYHTRV425

480

3

30

25.0

85300

2

15.0

10.0

38

40

40

1.

Any power supply and circuits must be wired and protected in accordance with local electrical codes.

2.

The values listed in the above table are for the electric heater only.

3.

Field wiring must be rated at least 75° C.

4.

* indicates an alpha character.

5.

‡ indicates model letter.

6.

# Heater uses fuses.

7.

& indicates a digit.

ALL VALUES ARE FOR THE ELECTRIC HEATER ONLY

(a)

The HACR circuit breaker is for U.S.A. installations only.

(b)

For Canada installation reference only.

Installer’s Guide

Follow these instructions to install the supplementary
heaters in packaged units as described in the heater
tables throughout this guide.

These instructions do not purport to cover all variations
in system hookups nor to provide for every possible
contingency to be met in connection with the
installation. Should further information be desired, or
should particular problems arise which are not covered
sufficiently for the purchaser’s purposes, refer the
matter to the manufacturer.

1. Check for any shipping damage and report any to

the carrier immediately.

2. Check the heater nameplate and compare with the

heater tables to ensure the available power supply
complies with the table for the particular heater
being used.

IIn

nsstta

allll H

He

ea

atte

errss

1. Remove screws that secure the heater panel

(located within control box access panel).

2. Remove and discard the patch plate covering the

opening where the heater will be inserted.

3. Slide the heater element section of heater assembly

into the opening and, tipping the heater slightly
forward against the unit barrier, slide the heater up
to engage the lip on the top of the barrier opening.
Push forward to engage the slot on the bottom of
the heater face into the tongue on the barrier. This
will hold the heater in place. Replace the four
screws removed in step 1. See

Figure 1, p. 6

4. Connect the polarized plug from the heater control

box to the matching polarized plug on the bottom
of the air conditioner or heat pump unit control box.
See

Figure 1, p. 6

L

Lo

ow

w V

Vo

olltta

ag

ge

e W

Wiirriin

ng

g

All low voltage connections have been made to the
heater via the polarized plug. The low voltage controls
can be connected to the room thermostat from the air
conditioner or heat pump Low Voltage leads. See
wiring diagrams. Low voltage is 24 Volts.

1. Open the heater’s control box access cover.

2. Remove the unit’s power supply knockout.

3. Route the field wire through the heater

compartment and strain relief bushing into the
bottom of the heater housing.

4. Connect the power supply to the heater’s wire leads

or fuse block depending on the particular heater
being used.

5. Connect the power supply ground lead to the

heater’s ground lead or ground lug depending on
the particular heater being used.

6. Place the included extra heater wiring diagram on

the inner surface of the control/heater access panel
next to the unit wiring diagram, as the diagram on
the heater may be only partially visible when
installed.

7. Close the heater housing cover.

8. Reinstall the control box/heater access panel.

9. Restore power to the unit.

The BAYHTRV115, 120, 125, 315, 3230 and 325 electric
heaters have an inner pivoting control box to allow
easy access to fuse links mounted on the heater back
plate. Remove the 2 screws from the top front of the
heater control box and pull the top of the inner control
box toward you. For easier replacement of contactors,
after pivoting the inner control box toward you,
remove the screws securing the top brace of the h eater
control box as shown in

Figure 1, p. 6

S

Su

up

pp

plle

em

me

en

ntta

arry

y E

Elle

eccttrriicc H

He

ea

atte

errss

Содержание BAYHTRV105

Страница 1: ...uipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment May 2022 1 18 8 H HB B2 20 0D D4 4 1 1E E E EN N Supplemental Electric Heaters BAYHTRV105 BAYHTRV108 BAYHTRV110 BAYHTRV115 BAYHTRV120 BAYHTRV125 BAYHTRV305 BAYHTRV308 BAYHTRV310 BAYHTR...

Страница 2: ... se e p pr ro op pe er r s se er rv vi ic ce e t to oo ol ls s m ma ay y r re es su ul lt t i in n e eq qu ui ip pm me en nt t d da am ma ag ge e o or r p pe er rs so on na al l i in nj ju ur ry y R Re ec co on nn ne ec ct t a al ll l g gr ro ou un nd di in ng g d de ev vi ic ce es s A Al ll l p pa ar rt ts s o of f t th hi is s p pr ro od du uc ct t t th ha at t a ar re e c ca ap pa ab bl le e o ...

Страница 3: ...18 HB20D4 1E EN 3 Supplementary Electric Heaters 4 Installer s Guide 5 Field Wiring Air Conditioners 7 Field Wiring Heat Pumps 8 Table of Contents ...

Страница 4: ...042 060 1 WCZ 048 060 1 BAYHTRV125 208 240 1 90 104 18 78 25 0 51200 68300 2 11 26 15 0 7 5 10 0 113 130 125 150 125 150 W TC 3036 060 3 W TCY4036 060 3 WCZ6036 060 3 CC4036 060 3 BAYHTRV305 208 240 3 10 12 3 76 5 0 64100 85300 1 3 76 5 0 13 15 15 15 15 15 W TC 3036 060 3 W TCY4036 060 3 WCZ6036 060 3 CC4036 060 3 BAYHTRV308 208 240 3 17 19 6 0 8 0 20500 27300 1 6 0 8 0 21 24 25 25 25 25 W TC 3036...

Страница 5: ...er slide the heater up to engage the lip on the top of the barrier opening Push forward to engage the slot on the bottom of the heater face into the tongue on the barrier This will hold the heater in place Replace the four screws removed in step 1 See Figure 1 p 6 4 Connect the polarized plug from the heater control box to the matching polarized plug on the bottom of the air conditioner or heat pu...

Страница 6: ...6 18 HB20D4 1E EN Figure 1 Typical Heater Installation S Su up pp pl le em me en nt ta ar ry y E El le ec ct tr ri ic c H He ea at te er rs s ...

Страница 7: ...igures 10 The 41A BR wire is first stage electric heat If the electric heater accessory has two heating stages the 41C BR wire is second stage electric heat Figure 2 Field Wiring B G Y W1 W2 R COMMON FAN COMPRESSOR HEAT FIRST STAGE HEAT SECOND STAGE 24V GR WH WH B G Y W1 W2 R B G Y W1 W2 R 3 PH POWER UNIT NOTE 1 8 3 PH POWER HEATER 1 PH POWER 1 PH POWER FIELD PROVIDED JUMPER NOTE 6 TO ECONOMIZER F...

Страница 8: ...O THE WCM F MODELS FIG 3 OUTDOOR THERMOSTAT ACCESSORY CONNECTIONS FIG 1 SINGLE POWER ENTRY ACCESSORY CONNECTIONS FIG 2 ECONOMIZER ACCESSORY CONNECTIONS GROUND WIRE SEE SPEK INSTALLER S GUIDE FOR ALL OTHER EXAMPLES PACKAGED HEAT PUMP UNIT Notes 1 Fused disconnect size power wiring and grounding of equipment must comply with codes 2 Be sure power supply agrees with equipment and heater nameplate 3 L...

Страница 9: ...18 HB20D4 1E EN 9 N No ot te es s ...

Страница 10: ...10 18 HB20D4 1E EN N No ot te es s ...

Страница 11: ...18 HB20D4 1E EN 11 N No ot te es s ...

Страница 12: ...pplications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice We are committed to using environmentally conscious print practices 18 HB20D4 1E EN 31 May 2022 Supersedes 18 HB20D4 1D EN July 2020 2022 ...

Отзывы: