background image

TEM6A0D60-SUB-1E-EN

7

1.

See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.

2.

Heater model numbers may have additional suffix digits.

Table 3. Electrical Data

TEM6A0D48H41SB, TEM6A0D60H51SB HEATER DATA

Heater Model No.

No. of

Circuits/

Phases

240 Volt

208 Volt

Capacity

Heater

Amps per

Circuit

Minimum

Circuit

Ampacity

Maximum

Overload

Protection

Capacity

Heater

Amps per

Circuit

Minimum

Circuit

Ampacity

Maximum

Overload

Protection

kW

BTUH

kW

BTUH

No Heater

6.8 *

9

15

6.8 *

9

15

BAYHTR1504BRK
BAYHTR1504LUG

1/1

3.84

13100

16.0

29

30

2.88

9800

13.8

26

30

BAYHTR1505BRK
BAYHTR1505LUG

1/1

4.80

16400

20.0

34

35

3.60

12300

17.3

30

30

BAYHTR1508BRK
BAYHTR1508LUG

1/1

7.68

26200

32.0

49

50

5.76

19700

27.7

43

45

BAYHTR1510BRK
BAYHTR1510LUG

1/1

9.60

32800

40.0

59

60

7.20

24600

34.6

52

60

BAYHTR1517BRK
Circuit 1

(a)

2/1

9.60

32800

40.0

59

60

7.20

24600

34.6

52

60

BAYHTR1517BRK
Circuit 2

4.80

16400

20.0

25

25

3.60

12300

17.3

22

25

BAYHTR1523BRK
Circuit 1

2/1

9.60

32800

40.0

59

60

7.20

24600

34.6

52

60

BAYHTR1523BRK
Circuit 2

9.60

32800

40.0

50

50

7.20

24600

34.6

43

45

BAYHTR1525BRK
Circuit 1

4/1

6.00

20500

25.0

40

40

4.50

15400

21.6

36

40

BAYHTR1525BRK
Circuit 2

6.00

20500

25.0

31

35

4.50

15400

21.6

27

30

BAYHTR1525BRK
Circuit 3

6.00

20500

25.0

31

35

4.50

15400

21.6

27

30

BAYHTR1525BRK
Circuit 4

6.00

20500

25.0

31

35

4.50

15400

21.6

27

30

BAYHTR3510LUG

1/3

9.60

32800

23.1

36

40

7.20

24600

20.0

33

35

BAYHTR3517LUG

1/3

14.40

49100

34.6

51

60

10.80

36900

30.0

45

45

* = Motor Amps

(a)

MCA and MOP for circuit 1 contains the motor amps

Features and Benefits

Painted metal cabinet with captured foil face
insulation

2% or less air leakage

R-4.2 Insulating Value

Multi-Position UP/Down Flow, Horizontal Left /Right

ALL Aluminum Coil with Enhanced Patented Coil
Fin

Electric Heaters with polarized plug connections
(sold as accessory)

R-410A Thermal Expansion Valve

Variable Speed ECM Motor

Low Voltage Pigtail Connections

Draw Through Design

Horizontal Drain Pan

Single Color

Fused 24V Power

3

3 y

ye

ea

arr w

wa

arrrra

an

ntty

y

1

10

0--y

ye

ea

arr w

wa

arrrra

an

ntty

y rre

eg

giisstte

erre

ed

d

O

Op

pttiio

on

na

all e

ex

xtte

en

nd

de

ed

d w

wa

arrrra

an

ntty

y a

av

va

aiilla

ab

blle

e

P

Pe

errffo

orrm

ma

an

ncce

e a

an

nd

d E

Elle

eccttrriicca

all D

Da

atta

a

Page 19 of 20  10/16/2019

MOHS, PLANS EXAMINER

REV #1                                                                                  .

2405 E AINSWORTH AVE                                  B19-2396

INSTALL HVAC SYSTEM/PORT OF PASCO    10/1/2019

Содержание BAYHTR1504BRKC

Страница 1: ...UCT CONTAINS FIBERGLASS WOOL INSULA TION FIBERGLASS DUST AND CERAMIC FIBERS ARE BE LIEVED BY THE STATE OF CALIFORNIA TO CAUSE CAN CER THROUGH INHALATION GLASSWOOL FIBERS MAY ALSO CAUSE RESPIRATORY SKIN OR EYE IRRITATION GENERAL This accessory electric heater is designed to provide power directly to the unit from the accessory heater s power supply eliminating the need for additional circuits The p...

Страница 2: ...he four tabs located at the center points of the edges of knock out plate 4 Discard knock out plate 8 Locate the two locking tabs on the top panel of the air handler shown as Left and Center in the drawing 9 Slide the breaker plate assembly into the appropriate tab Rotate the breaker assembly into place as shown in image 4 IMPORTANT The left side breaker mount location must be used for TEM8A0B24 3...

Страница 3: ...ship with a Heater Breaker Seal Kit See Seal Kit Installer s Guide for install instructions Note Follow the instructions in the Breaker Seal Kit 18 GJ85D1 1 latest rev The Breaker Seal Kit will ship with the TEM8A0B air handlers 25 KW heaters and single power entry kits for TEM A4AH4 air handlers Center knockouts Use for all other 4 20 kW heaters installations with all TEM A4AH4 air handler except...

Страница 4: ... L H TEM4A0C37S31SB A4AH4P37A1C030A L L L L L L H H L L TEM4A0C42S41SB A4AH4E42A1C030A L L L L L L L M L L TEM4A0C48S41SB A4AH4E48A1C030A TEM4A0C60S51SB A4AH4E60A1C030A L L L L L L L L L L L L Cooling HP Airflow Followed by one digit Note On the TEM4A0C42S41SB TEM4A0C48S41SB TEM4A0C60S51SB A4AH4E42A1C030A A4AH4E48A1C030A and A4AH4E60A1C030A models taps 1 3 Low tap 4 Med tap 5 High TEM6 MINIMUM HEA...

Страница 5: ...del No BAYHTR1504BRK BAYHTR1504LUG BAYHTR1505BRK BAYHTR1505LUG BAYHTR1508BRK BAYHTR1508LUG BAYHTR1510BRK BAYHTR1510LUG BAYHTR1517BRK BAYHTR1523BRK BAYHTR1525BRK BAYHTR3510LUG BAYHTR3517LUG Electric Heat Stages 1 1 1 1 2 2 2 1 1 Stage 1 Capacity kW 3 84 4 8 7 68 9 6 9 6 9 6 12 0 9 6 14 4 Stage 2 Capacity kW 3 84 4 8 7 68 9 6 14 4 19 2 24 0 9 6 14 4 Page 5 of 20 10 16 2019 MOHS PLANS EXAMINER REV 1 ...

Страница 6: ...Page 6 INSTALLER S GUIDE 18 HB22D1 14 Page 6 of 20 10 16 2019 MOHS PLANS EXAMINER REV 1 2405 E AINSWORTH AVE B19 2396 INSTALL HVAC SYSTEM PORT OF PASCO 10 1 2019 ...

Страница 7: ...Page 7 INSTALLER S GUIDE 18 HB22D1 14 Page 7 of 20 10 16 2019 MOHS PLANS EXAMINER REV 1 2405 E AINSWORTH AVE B19 2396 INSTALL HVAC SYSTEM PORT OF PASCO 10 1 2019 ...

Страница 8: ...9010 Since the manufacturer has a policy of continuous product and product data improvement it reserves the right to change design and specification without notice Page 8 of 20 10 16 2019 MOHS PLANS EXAMINER REV 1 2405 E AINSWORTH AVE B19 2396 INSTALL HVAC SYSTEM PORT OF PASCO 10 1 2019 ...

Страница 9: ...r altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment June 2016 4A6H5060H SUB 1A EN Split System Heat Pump 4A6H5060H1000A N No ot te e Graphics in this document are for representation only Actual model may differ in appearance...

Страница 10: ...VEL Model A Weighted Sound Power Level dB A Full Octave Sound Power dB 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz 4A6H5060H 72 77 75 72 70 67 62 59 52 Note Rated in accordance with AHRI Standard 270 2008 For reference only Page 10 of 20 10 16 2019 MOHS PLANS EXAMINER REV 1 2405 E AINSWORTH AVE B19 2396 INSTALL HVAC SYSTEM PORT OF PASCO 10 1 2019 ...

Страница 11: ...ed in accordance with Natl Elec Codes Use only HACR circuit breakers or fuses d This value shown for compressor RLA on the unit nameplate and on this specification sheet is used to compute minimum branch circuit ampacity and max fuse size The value shown is the branch circuit selection current e No means no start components Yes means quick start kit components PTC means positive temperature coeffi...

Страница 12: ...se C Co on nd de en ns se er r C Co oi il l The outdoor coil provides low airflow resistance and efficient heat transfer The coil is protected on all four sides by louvered panels L Lo ow w A Am mb bi ie en nt t C Co oo ol li in ng g As manufactured this system has a cooling capacity to 55 F The addition of an evaporator defrost control permits operation to 40 F The addition of an evaporator defro...

Страница 13: ... and on the tags stickers and labels that are attached to the equipment March 2018 T TE EM M6 6A A0 0D D6 60 0 S SU UB B 1 1E E E EN N Variable Speed Convertible Air Handler 5 Ton TEM6A0D60H51SB N No ot te e The TEM6 series air handler is designed for installation in a closet utility room alcove basement crawlspace or attic These versatile units are applicable to air conditioning and heat pump app...

Страница 14: ...D ON THE UNIT RATING NAMEPLATE PRODUCT DIMENSIONS Air Handler Model A B C D E F H Flow Control Gas Line Braze TEM6A0D60H51SB 53 87 26 50 24 50 24 75 7 01 9 66 27 19 TXV 7 8 All dimensions are in inches Page 14 of 20 10 16 2019 MOHS PLANS EXAMINER REV 1 2405 E AINSWORTH AVE B19 2396 INSTALL HVAC SYSTEM PORT OF PASCO 10 1 2019 ...

Страница 15: ...z 208 230 1 60 F L Amps 6 8 FILTER Filter Furnished c No REFRIGERANT R 410A Ref Line Connections Brazed Coupling or Conn Size in Gas 7 8 Coupling or Conn Size in Liq 3 8 DIMENSIONS H x W x D Crated In 55 3 8 x 30 1 2 x 25 1 2 Uncrated 53 7 8 x 26 1 2 x 21 1 8 WEIGHT Shipping Lbs Net Lbs 181 168 a These Air Handlers are A H R I certified with various Split System Air Conditioners and Heat Pumps AHR...

Страница 16: ...3517LUG 1300 1125 BAYHTR1523BRK 1380 1125 BAYHTR1525BRK 1550 1345 TEM6A0D60H51SB Airflow Performance with Auxiliary Heat Airflow Settings Dip Switch Settings Nominal Airflow See following tables for heater application Pressure Drop for Electrical Heaters Minimum Heating Airflow Matrix on unit nameplates Switch 7 Switch 8 Low ON ON 997 Med Lo OFF ON 1129 Med Hi ON OFF 1350 High OFF OFF 1597 Page 16...

Страница 17: ...0 13 BAYHTR1510 2 1500 0 02 0 04 0 06 0 12 BAYHTR1516 3 1400 0 02 0 04 0 06 0 12 BAYHTR1517 3 1300 0 02 0 04 0 05 0 11 BAYHTR3510 3 1200 0 01 0 04 0 05 0 10 BAYHTR3517 3 1100 0 01 0 03 0 05 0 09 BAYHTR3515 3 1000 0 01 0 03 0 04 0 09 BAYHTR1522 4 900 0 01 0 03 0 04 0 08 BAYHTR1523 4 800 0 01 0 03 BAYHTR1525 4 700 0 01 0 02 600 0 01 0 02 Page 17 of 20 10 16 2019 MOHS PLANS EXAMINER REV 1 2405 E AINS...

Страница 18: ... 476 1892 556 1900 635 1902 714 1760 650 a Factory Default Setting Table 2 Air Flow Performance TEM6A0D48H41SB TEM6A0D60H51SB HEATING AIRFLOW PERFORMANCE NO FILTER NO HEATER OUTDOOR UNIT SIZE TONS SPEED SETTING AIRFLOW SETTING DIP SWITCH SETTING AIRFLOW POWER EXTERNAL STATIC PRESSURE SW1 SW2 SW3 SW4 0 1 0 3 0 5 0 7 0 9 3 LOW 360 CFM ton ON ON OFF ON CFM Watts 1087 111 1091 153 1081 199 1055 249 10...

Страница 19: ... 4 1 6 00 20500 25 0 40 40 4 50 15400 21 6 36 40 BAYHTR1525BRK Circuit 2 6 00 20500 25 0 31 35 4 50 15400 21 6 27 30 BAYHTR1525BRK Circuit 3 6 00 20500 25 0 31 35 4 50 15400 21 6 27 30 BAYHTR1525BRK Circuit 4 6 00 20500 25 0 31 35 4 50 15400 21 6 27 30 BAYHTR3510LUG 1 3 9 60 32800 23 1 36 40 7 20 24600 20 0 33 35 BAYHTR3517LUG 1 3 14 40 49100 34 6 51 60 10 80 36900 30 0 45 45 Motor Amps a MCA and ...

Страница 20: ... and efficiency We are a global business committed to a world of sustainable progress and enduring results ingersollrand com Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice We are committed to using environmentally conscious print practices TEM6A0D60 SUB 1E EN 19 Mar 2018 Supersedes TEM6A0D60 ...

Отзывы: