Section 7. Heater Operation

7.1 TAM7/TAMG Heater Operation
Electric Heat 

1.     R-W contacts close on the comfort control sending 24VAC to 

W1 of the AFC. 

2.     R-G contacts close on the comfort control sending 24VAC to G 

of the AFC.

3.     The AFC communicates to the EHC that 1st stage electric heat 

is being called upon.

4.     The EHC determines the number of elements that are used for 

1st stage and sends a message to the AFC for that correct cfm. 

(The EHC determines the amount of heat per stage by either 

factory programming or by the kw jumper position) 

5.     The AFC micro-processor sends a command to the serial com-

municating blower motor to run and close the blower interlock 

relay on the EHC. The blower motor will now run at the W1 

electric heat cfm.

6.     On subsequent calls for W2 and/or W3, the EHC will communi-

cate to the AFC the required airflow request and energize the 

additional relays. 

NOTE: 

The EHC has “lead-lag” logic built in that energizes the elec-

tric heat relays based upon cycle counts. 

For example: BAYEV**15 – The first time W1 only is energized; the 

K1 relay would close and energize the “A” heater. The second 

time W1 only is energized; the K2 relay would close and ener-

gize the “B” heater. The third time W1 only is energized; the K3 

relay would close and energize the “C” heater.  

Electric Heat

 

1.    

When a request for electric heat is received, the AFC com-

municates to the EHC how much demand for auxiliary heat 
is being requested

2.   The EHC determines the number of elements that will be 

used for this request and sends a message to the AFC for 
proper airflow. (The EHC determines the amount of heat 
available per stage by either factory programming or by the 
kW jumper position) 

3.   The AFC sends a command to the serial communicating 

blower motor to run proper airflow and close the blower 
interlock relay on the EHC. 

4.   As demand from the thermostat increases, the EHC will com-

municate to the AFC the required airflow when energizing 
additional relays. 

NOTE: 

The EHC has “lead-lag or rotating” logic built in that en-

ergizes the electric heat relays based upon cycle counts. To 

verify operation of all heating elements, switch thermostat 

to Emergency Heat and raise the setpoint of the thermostat 

at least 5 degrees above the actual room temperature.

7.2 TAM8 Heater Operation

Control Board Jumper Settings

When the heater comes from the factory, all dip switches will be 
in the ON (park) position. The control is already configured for the 
heater size that is required, so no adjustments are necessary.  

NOTE:  If the dip switches are changed to another kw rating, 

the original "Park" programming is not lost;, however the dip 

switches must be placed in the ON (park) position or the cor-

rect kw of the heater model for normal operation.

Heater Wattage Selection Table
Heater Wattage

S1 SW1

S1 SW2

S1 SW3

S1 SW4

S1 SW5

PARK

ON

ON

ON

ON

ON

4 KW

ON

ON

ON

OFF

OFF

5 KW

OFF

ON

ON

ON

ON

8 KW

ON

OFF

ON

ON

ON

10 KW

ON

ON

OFF

ON

ON

15 KW

ON

ON

ON

OFF

ON

20 KW

ON

ON

ON

ON

OFF

25 KW

OFF

ON

ON

ON

OFF

Содержание BAYEVCC25BK1

Страница 1: ...itioning product may result in personal injury and or property damage The manufacturer or seller cannot be responsible for the interpretation of this information nor can it as sume any liability in co...

Страница 2: ...or damage Report any defects or shortages to the transportation company im mediately 3 Be sure the power supply matches the listing shown on the heater nameplate Section 2 General Information Section...

Страница 3: ...ght front of the heater and connected with a ring terminal to the heater base plate 3 Disconnect the two ground wires from the lug on the heater base plate Note It is recommended that the ducting be a...

Страница 4: ...order to comply with National Electric Code NEC Section 240 81 The NEC requires that circuit breakers operated verti cally must be oriented so that the on position of the breaker is upward Field Conne...

Страница 5: ...nplug and dispose of pigtail harness Section 5 Install Heater STEP 1 Remove Heater Compartment Panel Heater Compartment Panel 3 Place the circuit breakers back into the control box The tabs on the bre...

Страница 6: ...e retainer tab into recess in air handler cabinet 2 Tighten screws to hold tab securely 3 Repeat actions to secure the other tab STEP 5 Select a conduit entry point See the orientations on the followi...

Страница 7: ...Page 7 INSTALLER S GUIDE Upflow Route conduit as shown Downflow Route conduit as shown Note A minimum of 8 is required for installation and servicing of the control box 8 Min...

Страница 8: ...Page 8 INSTALLER S GUIDE Horizontal Left Route conduit as shown Horizontal Right Route conduit as shown...

Страница 9: ...he screw removed earlier See Section 4 Step 1 for illustration 4 Reconnect the 3 pin plug on the heater to the 3 pin plug in the air handler case 5 Reconnect the two ground wires to the lug on the bas...

Страница 10: ...low voltage harness to Electric Heat Control connector on the board as shown Low Voltage Harness STEP 10 Place Wiring Diagram 1 Attach the wiring diagram included in the documenta tion packet to the...

Страница 11: ...ircuit Therefore the branch circuit s shall be sized and protected according to the unit nameplate Table 6 1 BAYEV HEATER DATA Heater Model No Number of Circuits 240 VOLT 208 VOLT Capacity Heater Amps...

Страница 12: ...only is energized the K2 relay would close and ener gize the B heater The third time W1 only is energized the K3 relay would close and energize the C heater Electric Heat 1 When a request for electric...

Отзывы: