Table 4. Controller menu structure (continued)
Menu
Parameter
Parameter
Default Value
Parameter
Range and
Increment
(a)
Parameter
Recommended
Value
(b)
Notes
OAT SENS ERR
N/A
N/A
N/A
DA ENTHL ERR
N/A
N/A
N/A
DA ENTHL ERR is not available.
SYS ALARM
N/A
N/A
N/A
When AUX1-O is set to SYS and there
is any alarm the AUX1-O terminal has
24 Vac out.
ALARMS(_)
ACT UNDER V
N/A
N/A
N/A
Voltage received by Actuator is above
expected range.
ACT OVER V
N/A
N/A
N/A
Voltage received by Actuator is below
expected range.
ACT STALLED
N/A
N/A
N/A
Actuator stopped before achieving
commanded position.
(a)
When values are displayed, pressing and holding the Up or Down button causes the display to automatically increment.
(b)
N/A = Not Applicable
(c)
This parameter is directly associated with the LLE economizer.
(d)
The Honeywell communicating actuator will report in XX.X% open versus XX.X Vdc for damper out.
(e)
Alarms display only when they are active. The menu title “ALARMS (_)” includes the number of active alarms in parenthesis ().
Sequence of Operation
Table 5. Dry bulb operation no DCV (CO
2
sensor) - 1 speed fan
DCV
OA Good to
economize?
Y1-I
FAN SPD
Y1-O
Occupied
Unoccupied
None
No
Off
High
0-v/Off
MIN POS
Closed
On
High
24-v/On
MIN POS
Closed
None
Yes
Off
High
0-v/Off
MIN POS
Closed
On
High
0-v/Off
MIN POS to Full-Open
Closed to Full-Open
On
High
24-v/On
MIN POS to Full-Open
Closed to Full-Open
Table 6. Dry bulb operation with DCV (CO
2
sensor) - 1 speed fan
DCV
OA Good to
economize?
Y1-I
FAN SPD
Y1-O
Occupied
Unoccupied
Below CO
2
set
No
Off
High
0-v/Off
VENTMIN
Closed
On
High
24-v/On
VENTMIN
Closed
Yes
Off
High
0-v/Off
VENTMIN
Closed
On
High
0-v/Off
VENTMIN to Full-Open
Closed to Full-Open
On
High
24-v/On
VENTMIN to Full-Open
Closed to Full-Open
Above CO
2
set
No
Off
High
0-v/Off
VENTMIN to VENTMAX
Closed
On
High
24-v/On
VENTMIN to VENTMAX
Closed
Yes
Off
High
0-v/Off
VENTMIN to VENTMAX
Closed
On
High
0-v/Off
VENTMIN to Full-Open
Closed to Full-Open
On
High
24-v/On
VENTMIN to Full-Open
Closed to Full-Open