Table 4. Controller menu structure (continued)

Menu

Parameter

Parameter
Default Value

Parameter
Range and
Increment

(a)

Parameter
Recommended
Value

(b)

Notes

DCVCAL ENA

MAN

MAN (manual)

AUTO

MAN

Turns on the DCV automatic control of
the dampers. Resets ventilation based
on the RA, OA and MA sensor
conditions. Requires all sensors (RA,
OA, MA and CO

2

). This operation is not

operable with a 2-speed fan unit.

MAT T CAL

(c)

0.0 F°

(+/-2.5°F)

0.0 F°

Allows for the operator to adjust for an
out of calibration temperature sensor.

OA T CAL

(c)

0.0 F°

(+/-2.5°F)

0.0 F°

Allows for the operator to adjust for an
out of calibration temperature sensor.

ADVANCED

SETUP

OA H CAL

(c)

0% RH

(+/-10% RH)

0% RH

Allows for the operator to adjust for an
out of calibration humidity sensor.

RA T CAL

(c)

0.0 F°

(+/-2.5°F)

0.0 F°

Allows for the operator to adjust for an
out of calibration temperature sensor.

RA H CAL

(c)

0% RH

(+/-10% RH)

0% RH

Allows for the operator to adjust for an
out of calibration humidity sensor.

DA T CAL

(c)

0.0 F°

(+/-2.5°F)

0.0 F°

DA T CAL is not available.

2SP FAN DELAY

(c)

5 Minutes

0 to 20 minutes in

1 minute

increments.

5 Minutes

When in economizing mode this is the
delay for the high speed fan to try to
satisfy the call for second stage cooling
before the first stage mechanical
cooling is enabled.

DAMPER VMIN-HS

N/A

N/A

N/A

Positions damper to VMIN position.

DAMPER VMAX-HS

(LS)

(c)

N/A

N/A

N/A

Positions damper to VMAX position.
With 2-speed fan units the damper will
position to VMAX low speed fan.

DAMPER OPEN

(c)

N/A

N/A

N/A

Positions damper to the full open
position. Exhaust fan contacts enable
during the DAMPER OPEN test. Make
sure you pause in this mode to allow
for exhaust contacts to energize due to
the delay in the system.

DAMPER CLOSE

(c)

N/A

N/A

N/A

Positions damper to the fully closed
position.

CHECKOUT

CONNECT Y1-O

(c)

N/A

N/A

N/A

Closes the Y1-O relay (Y1-O). See

Step

CONNECT Y2-O

(c)

N/A

N/A

N/A

N/A

CONNECT AUX1-O

(c)

N/A

N/A

N/A

CONNECT AUX1 O energizes the
AUX1-O output. If AUX1-O setting is:

NONE — No action taken

ERV — 24 Vac out. Turns on or
signals an ERV that the conditions
are not good for economizing but
are good for ERV operation.

SYS — 24 Vax out. Issues a
system alarm.

CONNECT EXH1

(c)

N/A

N/A

N/A

Closes the power exhaust fan 1 relay
(EXH1).

ALARMS(_)

(e)

MAT SENS ERR

N/A

N/A

N/A

CO

2

SENS ERR

(c)

N/A

N/A

N/A

E

Ecco

on

no

om

miizze

err C

Co

on

nttrro

olllle

err

Содержание BAYECON355 Series

Страница 1: ...d or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that...

Страница 2: ...r p pr ro op pe er r P PP PE E f fo or r t th he e j jo ob b b be ei in ng g u un nd de er rt ta ak ke en n c co ou ul ld d r re es su ul lt t i in n d de ea at th h o or r s se er ri io ou us s i in...

Страница 3: ...ri ig ge er ra an nt t h ha an nd dl li in ng g e et tc c W Wh he er re e l lo oc ca al l r re eg gu ul la at ti io on ns s a ar re e m mo or re e s st tr ri in ng ge en nt t t th ha an n t th he es...

Страница 4: ...he Keypad When Working with Menus 9 Time out and Screensaver 9 Controller Menu Structure 9 Sequence of Operation 15 Initiation of Operating Modes 16 Economizer Setup and Configuration Field and Factor...

Страница 5: ...nspection for Concealed Damage Visually inspect the components for concealed damage as soon as possible after delivery and before it is stored If concealed damage is discovered Notify the carrier s te...

Страница 6: ...installation Economizer Side Post Side Post 5 Connect the unit harness to the economizer harness See the figure that follows Additionally connect the green purple white and orange loose wires with mal...

Страница 7: ...orange wire is provided for a fault alarm relay or light When the controller s AUX1 OUT is set to SYS this wire will provide 24V when a fault is detected See Figure 7 p 7 Figure 7 Low voltage control...

Страница 8: ...emperature sensor is a system critical sensor if it is removed during the set up mode the controller will alarm After 60 minutes the controller will change to Operation mode and all components removed...

Страница 9: ...the currently displayed item Press the button to increase change the displayed parameter value Press the button to decrease change the displayed parameter value N No ot te e When values are displayed...

Страница 10: ...e OA TEMP c _ _ _ F 40 to 140 F N A Displays measured value of outdoor air temperature Displays F if sensor sends invalid value if not connected short or out of range OA HUM c _ _ 0 to 100 N A Display...

Страница 11: ...80 F increment by 1 32 F Setpoint determines outdoor temperature when the mechanical cooling cannot be turned on Commonly referred to as the Compressor lockout At or below the setpoint the Y1 O will n...

Страница 12: ...by CFM With 2 speed fan units VENTMIN L low speed fan and VENTMIN H high speed fan settings are required Default for VENTMIN L is 2 5V and VENTMIN H is 2 25V ERV OAT SP 32 F 0 to 50 F increment by 1...

Страница 13: ...l briefly flash YES and change to NO but all parameters will change to factory default values MA LO SET c 45 F 35 to 55 F increment by 1 F 45 F Temp to activate Freeze Protection close damper or modul...

Страница 14: ...increments 5 Minutes When in economizing mode this is the delay for the high speed fan to try to satisfy the call for second stage cooling before the first stage mechanical cooling is enabled DAMPER...

Страница 15: ...are active The menu title ALARMS _ includes the number of active alarms in parenthesis Sequence of Operation Table 5 Dry bulb operation no DCV CO2 sensor 1 speed fan DCV OA Good to economize Y1 I FAN...

Страница 16: ...cool when the damper is at 100 open The Economizer mode is controlled by the MAT getting above the MAT SET setting while the OAT is below the DRYBLB SET setting While the fans are not controlled by t...

Страница 17: ...ot te e When using the enthalpy Sylk Bus sensors there will be a slight delay while the controller and the sensor communicate Analog sensors do not communicate on the Sylk Bus and output a 20k ohm sig...

Страница 18: ...t all wiring connections at the Economizer module s terminals and verify compliance with the installation wiring diagrams For checkout review the status of each configured parameter and perform the ch...

Страница 19: ...sh hu ut td do ow wn n b be et tw we ee en n c ch he ec ck ko ou ut t t te es st ts s c co ou ul ld d r re es su ul lt t i in n c co om mp pr re es ss so or r d da am ma ag ge e D Do o n no ot t s sh...

Страница 20: ...20 RT SVN044A EN Figure 11 Ultra low leak economizer wiring diagram E Ec co on no om mi iz ze er r C Co on nt tr ro ol ll le er r...

Страница 21: ...RT SVN044A EN 21 N No ot te es s...

Страница 22: ...22 RT SVN044A EN N No ot te es s...

Страница 23: ...RT SVN044A EN 23 N No ot te es s...

Страница 24: ...formation please visit trane com or americanstandardair com Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and spec...

Отзывы: