RT-SVN044A-EN
13
Table 4. Controller menu structure (continued)
Menu
Parameter
Parameter
Default Value
Parameter
Range and
Increment
(a)
Parameter
Recommended
Value
(b)
Notes
FAN SPEED
1 speed
1 speed/ 2 speed
See unit
nameplate:
Digit 15 = 0 or 1 -
1 speed;
Digit 15 = 7 or 9 -
2 speed
Sets economizer controller for
operation of 1 speed or 2 speed supply
fan. The controller does not control the
fan but positions the OA and RA
dampers to the heating or cooling
mode. See page 23 for modes and
position.
Note:
2-speed fan option also needs
Heat (W1) programmed in AUX
2 In.
FAN CFM
5000cfm
100 to 15000 cfm;
increment by 100
5000 cfm
This is the capacity of the RTU. The
value is found in the Unit Catalog. The
cfm of the fan is only used with DCV
CAL ENABLE AUO.
SYSTEM
SETUP
AUX1 OUT
NONE
NONE
ERV
EXH2
SYS
NONE
AUX1 OUT is a programmable output
used for System Alarm output.
INPUT
INPUT or ALWAYS
ALWAYS
When using a setback thermostat with
occupancy out (24 Vac), the 24 Vac is
input “INPUT” to the OCC terminal. If
no occupancy output from the
thermostat then change program to
“ALWAYS” OR add a jumper from
terminal R to OCC terminal.
FACTORY DEFAULT
NO
NO or YES
NO
Resets all set points to factory defaults
when set to YES. LCD will briefly flash
YES and change to NO but all
parameters will change to factory
default values.
MA LO SET
45ºF
35 to 55°F;
increment by 1°F
45ºF
Temp to activate Freeze Protection
(close damper or modulate to MIN POS
if temp falls below set value).
FREEZE POS
CLO
CLO
MIN
CLO
Damper position when freeze
protection is active (closed or MIN
POS).
CO
2
ZERO
0ppm
0 to 500 ppm;
increment by 10
0ppm
CO
2
ppm level to match CO
2
sensor
start level. 0-10 Vdc CO
2
sensors
require CO
2
ZERO to be 400.
ADVANCED
SETUP
CO
2
SPAN
2000ppm
1000 to 3000
ppm; increment
by 50
2000 ppm
CO
2
ppm span to match CO
2
sensor;
e.g.; 500-1500 sensor output would
be 500 CO
2
zero and 1000 CO
2
span.
0-10 Vdc CO
2
sensors require CO
2
SPAN to be 1600.
STG3 DLY
2.0h
0 min, 5 min, 15
min, then 15 min
intervals. Up to 4h
or OFF
2.0h
Delay after stage 2 for cool has been
active. Turns on 2nd stage of
mechanical cooling when economizer
is 1st stage call and mechanical
cooling is 2nd stage call. Allows three
stages of cooling, 1 economizer and 2
mechanical. OFF = no Stage 3 cooling.
SD DMPR POS
CLO
CLO
OPN
CLO
Indicates shutdown signal from space
thermostat or unitary controller. When
controller receives 24 Vac input on the
SD terminal in conventional mode, the
OA damper will open if programmed
for OPN and OA damper will close if
programmed for CLO. All other
controls, e.g., Y1-O, EXH1, etc. will
shut off.