background image

RT-SVN044A-EN

11

Table 4. Controller menu structure (continued)

Menu

Parameter

Parameter
Default Value

Parameter
Range and
Increment

(a)

Parameter
Recommended
Value

(b)

Notes

ACT COUNT

(c)

N/A

1 to 65,535

N/A

Displays number of times actuator has
cycled. 1 Cycle equals the sum of 180°
of movement in any direction.

ACTUATOR

(c)

N/A

OK/Alarm (on

Alarm menu)

N/A

Displays Error if voltage or torque is
below actuator range.

EXH1 OUT

(c)

OFF

ON/OFF

N/A

Output of EXH1 terminal. Displays ON
when damper position reaches
programmed percentage setpoint.
ON = 24 Vac Output; OFF = No
Output.

STATUS

EXH2 OUT

OFF

ON/OFF

N/A

EXH2 OUT is not available.

ERV

OFF

ON/OFF

N/A

ERV is not available.

MECH COOL ON

(c)

0

0, 1, or 2

N/A

Displays number of mechanical cooling
stages that are active.

FAN SPEED

(c)

N/A

LOW or HIGH

N/A

Displays speed of fan on a 2-speed fan
unit.

W (HEAT IN)

(c)

N/A

ON/OFF

N/A

Displays status of heat on a 2-speed
fan unit.

MAT SET

(c)

53ºF

38 to 70°F;

increment by 1

53ºF

The economizer will modulate the OA
damper to maintain the mixed air
temperature at the setpoint.

LOW T LOCK

(c)

32ºF

-45 to 80°F;

increment by 1

32ºF

Setpoint determines outdoor
temperature when the mechanical
cooling cannot be turned on.
Commonly referred to as the
Compressor lockout. At or below the
setpoint the Y1-O will not be energized
on the controller.

DRYBLB SET

(c)

63ºF

48 to 80°F;

increment by 1

67ºF

Setpoint determines where the
economizer will assume outdoor air
temperature is good for free cooling;
e.g.; at 63ºF setpoint unit will
economizer at 62ºF and below and not
economize at 64 ºF and above. There
is a a 2ºF deadband.

SETPOINTS

ENTH CURVE

(c)

ES3

ES1, ES2, ES3,

ES4, or ES5

ES3

Enthalpy boundary “curves” for
economizing using single enthalpy.
See

Table 9, p. 17

for description of

enthalpy curves.

DCV SET

(c)

1100ppm

500 to 2000 ppm

increment by 100

1100 ppm

Displays ONLY if a CO

2

sensor is

connected. Setpoint for Demand
Control Ventilation of space. Above the
setpoint, the OA dampers will
modulate open to bring in additional
OA to maintain a space ppm level
below the setpoint.

MIN POS

(c)

2.8V

2 to 10 Vdc

2.8V/3.2V LO/

2.8V HI

Displays ONLY if a CO

2

sensor is NOT

connected. With 2-speed fan units MIN
POS L (low speed fan) and MIN POS H
(high speed fan) settings are required.
Default for MIN POS L is 3.2V and MIN
POS H is 2.8V.

E

Ecco

on

no

om

miizze

err C

Co

on

nttrro

olllle

err

Содержание BAYECON355 Series

Страница 1: ...d or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that...

Страница 2: ...r p pr ro op pe er r P PP PE E f fo or r t th he e j jo ob b b be ei in ng g u un nd de er rt ta ak ke en n c co ou ul ld d r re es su ul lt t i in n d de ea at th h o or r s se er ri io ou us s i in...

Страница 3: ...ri ig ge er ra an nt t h ha an nd dl li in ng g e et tc c W Wh he er re e l lo oc ca al l r re eg gu ul la at ti io on ns s a ar re e m mo or re e s st tr ri in ng ge en nt t t th ha an n t th he es...

Страница 4: ...he Keypad When Working with Menus 9 Time out and Screensaver 9 Controller Menu Structure 9 Sequence of Operation 15 Initiation of Operating Modes 16 Economizer Setup and Configuration Field and Factor...

Страница 5: ...nspection for Concealed Damage Visually inspect the components for concealed damage as soon as possible after delivery and before it is stored If concealed damage is discovered Notify the carrier s te...

Страница 6: ...installation Economizer Side Post Side Post 5 Connect the unit harness to the economizer harness See the figure that follows Additionally connect the green purple white and orange loose wires with mal...

Страница 7: ...orange wire is provided for a fault alarm relay or light When the controller s AUX1 OUT is set to SYS this wire will provide 24V when a fault is detected See Figure 7 p 7 Figure 7 Low voltage control...

Страница 8: ...emperature sensor is a system critical sensor if it is removed during the set up mode the controller will alarm After 60 minutes the controller will change to Operation mode and all components removed...

Страница 9: ...the currently displayed item Press the button to increase change the displayed parameter value Press the button to decrease change the displayed parameter value N No ot te e When values are displayed...

Страница 10: ...e OA TEMP c _ _ _ F 40 to 140 F N A Displays measured value of outdoor air temperature Displays F if sensor sends invalid value if not connected short or out of range OA HUM c _ _ 0 to 100 N A Display...

Страница 11: ...80 F increment by 1 32 F Setpoint determines outdoor temperature when the mechanical cooling cannot be turned on Commonly referred to as the Compressor lockout At or below the setpoint the Y1 O will n...

Страница 12: ...by CFM With 2 speed fan units VENTMIN L low speed fan and VENTMIN H high speed fan settings are required Default for VENTMIN L is 2 5V and VENTMIN H is 2 25V ERV OAT SP 32 F 0 to 50 F increment by 1...

Страница 13: ...l briefly flash YES and change to NO but all parameters will change to factory default values MA LO SET c 45 F 35 to 55 F increment by 1 F 45 F Temp to activate Freeze Protection close damper or modul...

Страница 14: ...increments 5 Minutes When in economizing mode this is the delay for the high speed fan to try to satisfy the call for second stage cooling before the first stage mechanical cooling is enabled DAMPER...

Страница 15: ...are active The menu title ALARMS _ includes the number of active alarms in parenthesis Sequence of Operation Table 5 Dry bulb operation no DCV CO2 sensor 1 speed fan DCV OA Good to economize Y1 I FAN...

Страница 16: ...cool when the damper is at 100 open The Economizer mode is controlled by the MAT getting above the MAT SET setting while the OAT is below the DRYBLB SET setting While the fans are not controlled by t...

Страница 17: ...ot te e When using the enthalpy Sylk Bus sensors there will be a slight delay while the controller and the sensor communicate Analog sensors do not communicate on the Sylk Bus and output a 20k ohm sig...

Страница 18: ...t all wiring connections at the Economizer module s terminals and verify compliance with the installation wiring diagrams For checkout review the status of each configured parameter and perform the ch...

Страница 19: ...sh hu ut td do ow wn n b be et tw we ee en n c ch he ec ck ko ou ut t t te es st ts s c co ou ul ld d r re es su ul lt t i in n c co om mp pr re es ss so or r d da am ma ag ge e D Do o n no ot t s sh...

Страница 20: ...20 RT SVN044A EN Figure 11 Ultra low leak economizer wiring diagram E Ec co on no om mi iz ze er r C Co on nt tr ro ol ll le er r...

Страница 21: ...RT SVN044A EN 21 N No ot te es s...

Страница 22: ...22 RT SVN044A EN N No ot te es s...

Страница 23: ...RT SVN044A EN 23 N No ot te es s...

Страница 24: ...formation please visit trane com or americanstandardair com Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and spec...

Отзывы: