Page 11
INSTALLER'S GUIDE
Section 6. Tables
Table 6.1 BAYEA -- HEATER DATA
Heater Model No.
Number of
Circuits
240 VOLT
208 VOLT
Capacity
Heater Amps
per Circuit
Capacity
Heater Amps
per Circuit
kW
BTUH
kW
BTUH
BAYEACC25BK1
3
24.00
82000
40/40/20
18.00
61500
34.6/34.6/17.3
Important:
The BAYEA* electric heat accessory may include up to a combination of three 60 amp circuit breakers to
provide an electrical disconnect for service personnel that is intended to help protect internal electrical components in
the event of a short circuit or ground fault. As designed, the circuit breakers supplied in the BAYEA* accessory
DO NOT
provide overcurrent protection of the branch circuit. Therefore, the branch circuit(s) shall be sized and protected according
to the unit nameplate.
Table 6.2 MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX
MODEL NO.
BAYEACC25BK1
W/O HP / WITH HP
GAM5B0C48M41E
TAP 4 / TAP 5
GAM5B0C60M51E
TAP 4 / TAP 5
①②
TAM4A0C48S41E
TAP 2
③
/ TAP 3
TAM4A0C60S51E
TAP 4 / TAP 5
TAM9A0C48V41D
TAMXA0C48V41D
1625 / 1813
TAM9A0C60V51D
TAMXA0C60V51D
1625 / 1813
TAMGB0C48V41D
1625 / 1813
TAMGB0C60V51D
1625 / 1813
SEE AIR HANDLER NAMEPLATE OR PRODUCT DATA FOR EXCEPTIONS
①
If the air handler is applied in downflow or horizontal configurations, the airflow should not
exceed 2000 CFM. Airflow above 2000 CFM could result in water blow-off.
②
Tap 5 can be used but only when the external static pressure is .6" or above.
③
Not approved for 208V
NOTE: TAM9, TAMX and TAMGB are variable speed air handlers
ID HEAT TYPE ↔↕
EH* EH
ID HEAT TYPE ↔
HH EH
EH CFG #PH ↔↕
XX* XX
EHC AIRFLOW ↔↕
LOW* LOW
EHC AIRFLOW ↔↕
MED* LOW
EHC AIR
HI*
HT DLY PR ↔↕
HPPR X*
•
This configuration will provide a
an 08 or 011 coil if Hydronic is
with a “C” width TAM9 cabinet
Select heater size
- See EH menu (electric heater)
o
Option 4 = Enhanced Mode
STEP 12 -
For the TAM9 and TAMGB only, set the
heater size in the Configuration Menu.