Figure 11: Coaxial water coil
Figure 12: Water connection device
Figure 13: 12 1/2-ton + water hook-up
Figure 14: Thermal expansion valve
Co-axial Water-to-Refrigerant Coil
The unit’s internal heat exchanging
water coil is engineered for maximum
heat transfer.
The copper or cupro-nickel seamless
tubing is a tube within a tube design.
The inner-water tube contains a deep
fluted curve to enhance heat transfer
and minimize fouling and scaling. It is
available in either copper or cu-
pro-nickel (selectable option) coil.The
outer refrigerant gas tube is made
from steel material. The coil is leak
tested to assure there is no cross leak-
age between the water tube and the
refrigerant gas (steel tube) coil. Co-ax-
ial heat exchangers are more tolerant
to freeze rupture. (See
Figure 11
for
co-axial water coil).
Compressor and Co-axial Coil
Isolation
For the 1/2-ton through 5-ton units, vi-
bration isolation of the compressor
and co-axial water coil is accom-
plished by increasing the rigidity and
stiffness at the base. This platform in-
cludes double isolation to the com-
pressor and single isolation to the
co-axial water coil. The combination in
the double isolation provide additional
attenuation during compressor start
and stop.
Water Connections
(1/2 thru 5-ton)
The water-in/water-out connections to
the co-axial water coil are located on
the right-hand chamfered corner of
the unit. The fittings are mounted flush
to the chamfered wall to help limit
shipping damage.
The water connection devices are con-
structed of copper or bronze material
and include a National Female Pipe
Thread (NFPT) junction. The connec-
tions are attached to the unit’s cham-
fer corner to alleviate the need for a
back-up wrench during installation.
(See
Figure 12
for water connection
device).
Water Connections
(12 1/2 thru 25-ton)
Water hookups for the larger tonnage
units are located internal to the unit to
help alleviate damage to the water
copper during shipment or job storage
of units prior to installation. Each unit
(although dual circuited) contains a
single supply and return water con-
nection. (See
Figure 13
for large ton-
nage water hook-up). Fittings for the
supply and return are internally
threaded.
Table 1
defines water connection siz-
ing for 1/2 ton through 25 ton configu-
rations
Expansion Valve
All Trane water-source systems in-
clude an expansion valve flow meter-
ing device.
This thermal expansion valve (TXV) al-
lows the unit to operate with an enter-
ing fluid temperature from 25 F to 110
F, and entering air temperatures from
40 F to 90 F. The valve is designed to
meter refrigerant flow through the cir-
cuitry to achieve desired heating or
cooling.
Unlike cap-tube assemblies, the ex-
pansion valve device allows the exact
amount of refrigerant required to meet
the coil load demands. This precise
metering by the TXV increases the ef-
ficiency of the unit. (See
Figure 14
for
thermal expansion valve).
Table 1: Water connection sizes
Unit Size
(MBH)
Fitting Size
(in)
FPT
006 thru 015
1/2 FTP
018 thru 042
3/4 FTP
048 thru 060
1 FPT
150 thru 180
1 5/8 FPT
240 thru 300
2 1/8 FPT
Features and
Benefits
Содержание Axiom GEH006
Страница 107: ...WSHP PRC001 EN 107 Control Wiring Basic 24V 1 PH 208V 60HZ 1PH ...
Страница 108: ...108 WSHP PRC001 EN Control Wiring Deluxe 24V 3 PH 208V 60HZ 3PH ...
Страница 109: ...WSHP PRC001 EN 109 Control Wiring Tracer ZN510 1PH 208V 60HZ 1PH ...
Страница 110: ...110 WSHP PRC001 EN Dimensional Data Tracer ZN524 3PH 460V 60HZ 3PH ...
Страница 123: ...WSHP PRC001 EN 123 Dimensional Data Front Return Back Supply 12 1 2 15 Ton ...
Страница 124: ...124 WSHP PRC001 EN Dimensional Data Back Return Front Supply 12 1 2 15 Ton ...
Страница 125: ...WSHP PRC001 EN 125 Dimensional Data Front Return Top Supply 12 1 2 15 Ton ...
Страница 126: ...126 WSHP PRC001 EN Dimensional Data Back Return Top Supply 12 1 2 15 Ton ...
Страница 143: ...WSHP PRC001 EN 143 GEV 12 1 2 to 25 Tons ...