104
WSHP-PRC001-EN
Mock-up Tests of the WSHP
Because the transfer function (the difference between sound pressure and sound power) of a water-source comfort system
is often a complex function of environment and operating mode, we have found it advantageous to supplement sound
power certification tests with sound pressure measurements taken in a mock-up of a typical environment. The model GEH
mock-up tests were conducted in a 15-ft x 15-ft room with the following characteristics. See
Figure 53
for room character-
istics during sound testing.
• Sheet rock walls and no windows
• Standard office-type carpeting
• Standard office-type 2-ft x 2-ft acoustical tile drop
ceiling
• Open light fixture directly under
the unit (line of sight from room to bottom of unit)
• 20-ft x 20-ft reflecting plane 8-inches above the unit
• Ducted discharge
• Ducted return with an 8-inch flex connection to room,
18-inches from the unit
For convenience, NC data for all GEH and GEV units are provided on Page 105.
Model GEH NC levels are tabulated in performance
Tables 59
and
60
. Test results are given for each of the four cabinet
sizes. Measurements were taken for the largest tonnage of each cabinet size.
Mock-up test data provides an excellent general look at how the units would perform in a typical environment. If the pro-
posed installation varies significantly from the mock-up facility and room acoustics are a concern an acoustical prediction
is justified. As mentioned before, a predictive analysis requires octave band sound power data.
Because of the large volume of ARI-260 sound power data, we refer you to the TOPSS program for octave band and overall
levels for various components.
Performance Data
Sound
Figure 53: Room characteristics
Содержание Axiom GEH006
Страница 107: ...WSHP PRC001 EN 107 Control Wiring Basic 24V 1 PH 208V 60HZ 1PH ...
Страница 108: ...108 WSHP PRC001 EN Control Wiring Deluxe 24V 3 PH 208V 60HZ 3PH ...
Страница 109: ...WSHP PRC001 EN 109 Control Wiring Tracer ZN510 1PH 208V 60HZ 1PH ...
Страница 110: ...110 WSHP PRC001 EN Dimensional Data Tracer ZN524 3PH 460V 60HZ 3PH ...
Страница 123: ...WSHP PRC001 EN 123 Dimensional Data Front Return Back Supply 12 1 2 15 Ton ...
Страница 124: ...124 WSHP PRC001 EN Dimensional Data Back Return Front Supply 12 1 2 15 Ton ...
Страница 125: ...WSHP PRC001 EN 125 Dimensional Data Front Return Top Supply 12 1 2 15 Ton ...
Страница 126: ...126 WSHP PRC001 EN Dimensional Data Back Return Top Supply 12 1 2 15 Ton ...
Страница 143: ...WSHP PRC001 EN 143 GEV 12 1 2 to 25 Tons ...