WSHP-PRC001-EN
101
Performance data is tabulated for cooling at 80 F DB/67 F WB entering air and 45 F entering fluid at ARI 410 rated SCFM.
Table W1: Waterside Economizer Performance Data
(1/2 through 5 Tons)
Input Data
Output Data
Tonnage
of Heat
Pump
Model
GEH
SCFM
GPM
Total
Capacity
(MBH)
Sensible
Capacity
(MBH)
LVG. Air
DB
(Deg F)
LVG. Air
WB
(Deg F)
Standard
APD
(IN WG)
LVG.Flui
d Temp.
Degree F
Fluid PD
(FT H
2
O)
0.50
006
190
1.2
5.83
4.28
59.4
57.3
0.03
54.7
0.23
1.5
6.3
4.6
58.5
56.5
0.03
53.4
0.34
1.7
6.65
4.61
57.8
55.8
0.03
52.8
0.42
0.75
009
285
1.7
7.86
5.91
61.1
58.4
0.07
54.2
0.42
2.1
8.49
6.14
60.3
57.7
0.07
53.1
0.60
2.3
8.76
6.25
60.0
57.3
0.07
52.6
0.71
1.00
012
380
2.2
9.75
7.41
62.2
59.1
0.11
53.8
0.65
2.8
10.6
7.72
61.4
58.3
0.11
52.6
0.99
3.1
11.03
7.91
61.0
57.9
0.11
52.1
1.18
1.25
015
460
2.8
11.44
8.68
62.7
59.3
0.15
53.1
0.99
3.5
12.33
9.03
62.1
58.7
0.15
52.0
1.46
3.8
12.69
9.19
61.7
58.4
0.15
51.7
1.69
1.50
018
570
3.3
16.27
11.71
61.2
58.1
0.12
54.8
1.36
4.2
17.61
12.25
60.4
57.3
0.12
53.4
2.08
4.6
18.05
12.42
60.1
57.0
0.12
52.8
2.45
2.00
024
760
4.4
20.25
14.65
62.4
58.7
0.19
54.2
2.26
5.5
21.58
15.21
61.7
0.2
0.19
52.8
3.4
6.1
22.19
15.43
61.4
57.9
0.19
52.3
4.03
2.50
030
900
5.5
23.27
16.81
62.9
59.0
0.25
53.4
3.4
6.9
24.71
17.38
62.3
58.5
0.25
52.1
5.01
7.6
25.28
17.64
62.1
58.3
0.25
51.6
5.95
3.00
036
1140
6.6
29.28
21.57
62.7
59.1
0.19
53.8
2.39
8.3
31.47
22.41
62.0
58.4
0.19
52.6
5.25
9.1
32.2
22.2
61.8
58.2
0.19
52.1
6.19
3.50
042
1330
7.8
32.88
24.88
63.4
59.4
0.25
53.4
4.70
9.7
34.81
25.05
62.8
58.9
0.25
52.2
6.92
10.7
35.67
25.37
62.6
58.7
0.25
51.6
8.24
4.00
048
1520
8.8
39.77
29.11
62.5
58.9
0.17
54.0
1.24
11
42.44
30.25
61.8
58.3
0.17
52.7
1.86
12.1
43.65
30.69
61.5
58.0
0.17
52.2
2.21
5.00
060
1900
11.6
47.59
34.73
63.3
59.3
0.24
53.2
2.04
14.5
50.66
35.94
62.7
58.7
0.24
52.0
3.05
16
51.87
36.39
62.5
58.5
0.24
51.5
3.65
Table W2: Waterside Economizer Performance Data
(12 1/2 through 25 Tons)
Input Data
Output Data
Ton-
nage of
Heat
Pump
Model
GEV
SCFM
GPM
Air Velocity
(SFPM)
Total
Capacity
(MBH)
Sensible
Capacity
(MBH)
LVG. Air
DB
(Deg F)
LVG. Air
WB
(Deg F)
Standard
APD
(IN WG)
LVG.Flui
d Temp.
Degree F
Fluid PD
(FT H
2
O)
12.50
150
5000
27.5
308
160.4
120.6
58.0
56.9
0.175
56.6
6.93
35
308
177.4
127.3
56.7
55.7
0.183
55.1
11.22
38.75
308
184.0
130.0
56.2
55.2
0.185
54.5
13.75
15.00
180
6000
33
370
187.3
141.4
58.5
57.2
0.234
56.3
9.80
42
370
205.4
148.5
57.4
56.1
0.242
54.8
15.87
46.5
370
212.3
151.3
56.9
55.7
0.246
54.1
19.46
20.00
240
8000
44
438
241.7
183.4
59.0
57.5
0.305
56.0
8.56
56
438
263.0
191.8
58.1
56.6
0.315
54.4
13.86
62
438
271.3
195.1
57.7
56.2
0.319
53.7
16.99
25.00
300
10000
55
548
280.8
219.5
60.1
58.2
0.52
55.2
9.76
70
548
299.0
228.4
59.3
57.5
0.52
53.5
15.82
77.5
548
306.8
232.1
58.9
57.3
0.53
52.9
19.39
Performance Data
Waterside Economizer
Содержание Axiom GEH006
Страница 107: ...WSHP PRC001 EN 107 Control Wiring Basic 24V 1 PH 208V 60HZ 1PH ...
Страница 108: ...108 WSHP PRC001 EN Control Wiring Deluxe 24V 3 PH 208V 60HZ 3PH ...
Страница 109: ...WSHP PRC001 EN 109 Control Wiring Tracer ZN510 1PH 208V 60HZ 1PH ...
Страница 110: ...110 WSHP PRC001 EN Dimensional Data Tracer ZN524 3PH 460V 60HZ 3PH ...
Страница 123: ...WSHP PRC001 EN 123 Dimensional Data Front Return Back Supply 12 1 2 15 Ton ...
Страница 124: ...124 WSHP PRC001 EN Dimensional Data Back Return Front Supply 12 1 2 15 Ton ...
Страница 125: ...WSHP PRC001 EN 125 Dimensional Data Front Return Top Supply 12 1 2 15 Ton ...
Страница 126: ...126 WSHP PRC001 EN Dimensional Data Back Return Top Supply 12 1 2 15 Ton ...
Страница 143: ...WSHP PRC001 EN 143 GEV 12 1 2 to 25 Tons ...