ARTC-SVX006A-EN
45
Heat Pump Performance Data
This manual uses a typical 60-ton air-cooled heat pump
consisting of two modules with brazed plate load heat
exchangers for example purposes. The model number and
a heat pump’s precise electrical and refrigerant data can be
found on the heat pump model nameplate. See
.
Table 9.
Typical AXM air-to-water heat pump selection of two 30 ton modules
Heat Pump System (two 30-ton heat pump modules) Model # AXM030
Unit
Number of modules
2
Refrigerant
R410A
Compressors per Module
Type
Scroll
Refrigerant Circuits
2
Number
2
Total refrigerant charge
42
Fans per module
Type
EC axial fan
Number
2
Evaporator per module
Type
Brazed Plate
Number
1
Weight per Module
Net weight per module
3,000 lbs.
Cooling conditions
Fluid
water
Outlet fluid temperature
44 °F (7 °C)
Fouling factor
0.00010 h ft2- °F/Btu
Design ambient temperature
95 °F (37.3 °C)
Inlet fluid temperature
54 °F (12 °C)
Elevation
0 ft
Cooling performance per bank
Cooling capacity
59.21 Tons
Flow rate
137.8 GPM
Minimum unloading
14.8 Tons
Pressure drop
10.2 ft H
2
O
Compressors Input Power
67.97 kW
EER (A1)
9.62 Btu/Wh
Fans Input Power
6.000 kW
Efficiency - 100% Load
1.2493 kW/Ton
Total Input Power (A1)
73.97 kW
NPLV.IP
0.9125 kW/Ton
Heating conditions
Inlet fluid temperature
109 °F
Design ambient temperature
19.99 °F
Outlet fluid temperature
120 °F
External Relative Humidity
0 %
Heating performance per bank
Heating capacity
541.10 MBtu/h
Pressure Drop
18.3 ft H
2
O
Compressors Input Power
68.00 kW
COP (A1)
2.14
Fans Input Power
5.990 kW
Total Air Flow
46,000 SCFM
Total Input Power (A1)
74.00 kW
Available Pressure
0 Psig
Flow Rate
98.01 GPM
Electrical performance per Module
Power Supply
460/3/60 V-ph-Hz
Chiller FLA
59.8 A
Содержание Arctic Thermafit AXM
Страница 69: ...ARTC SVX006A EN 69 Notes...
Страница 70: ...70 ARTC SVX006A EN Notes...
Страница 71: ...ARTC SVX006A EN 71 Notes...