![Trane Air-Fi WCS-SB Скачать руководство пользователя страница 44](http://html1.mh-extra.com/html/trane/air-fi-wcs-sb/air-fi-wcs-sb_installation-operation-and-maintenance-manual_1148928044.webp)
44
BAS-SVX40K-EN
WCS-SO, -SCO
2
, -SB/R Network Joining and Controller Association
After addresses are set, insure the network is open, then press the UP arrow once. You will see rotating
segments on the display while the sensor attempts to join the network and associate to the controller. If
successful you will see signal strength displayed.
•
Error code
E2
will appear on the sensor display until the WCS successfully joins the network. Until
network joining is successful, the WCS will repeat its attempt to join every 60 minutes .
•
Association between the WCS and the controller will automatically be initiated if not done manually.
The WCS will repeat its attempt to associate every 15 minutes until successful. Error code
E1
will be
displayed until association is successful.
•
You can press the UP arrow at any time an error is displayed or a blank display occurs to cause the
sensor to re-attempt to join the network and to associate with the WCI.
Rotating segments are displayed while the sensor attempts to join or associate. Signal strength is
displayed immediately afterwords.
To verify the strength of the network signal quality and of the WCS battery charge, refer to
WCS-to-WCI Signal Strength and Battery Life,” p. 52
.
WCS : Points and Referencers
If you have added an optional Relative Humidity module or have multiple sensors associated to a single
controller, you may need to add points to be able to see these values in TU or SC. See "Referencing
Individual Sensors" section for more information.
Mounting the WCS-SO, -SCO
2
, -SB/R Sensor Back Plate
Important:
Do not mount WCS-SO or WCS-SCO
2
sensors behind glass, clear plastic, or Plexiglas. The
passive infra-red motion sensor cannot "see" through these materials and will not be able
to detect motion.
To mount the sensor back plate:
1. Hold the back plate against the mounting surface and mark the screw locations.
2. Secure the back plate against the mounting surface using included hardware.
The following figure shows an example of mounting the back plate of the sensor into sheetrock or
plaster.